Speak to a sourcing specialist
sales13@apterpower.com

IS200EXAMG1AAB

Exciter Attenuation Module
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

GE IS200EXAMG1AAB is an EXAM exciter attenuation module in the EX2100 excitation-control architecture. It conditions the ground-detection connection within the approved excitation-system arrangement.
  • Manufacturer part number
    IS200EXAMG1AAB
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    4cm × 18.6cm × 26.1cm
  • Country of Origin
    USA
Get a quick price for IS200EXAMG1AAB
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the full IS200EXAMG1AAB marking, quantity and label photos. We review the item and any version details that need clarification.

  • 1

    Confirm the offer

    Check the quoted IS200EXAMG1AAB reference, condition, included items and expected dispatch date before approving your order.

  • 2

    Arrange dispatch

    Confirm delivery details and receive the tracking number when it becomes available for IS200EXAMG1AAB.

  • Match the complete marking

    Include IS200EXAMG1AAB and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.

  • Check the offered item before ordering

    Request current label, board and connector photos of IS200EXAMG1AAB. Compare the offered reference and host configuration with the installed equipment before approval.

Technical specifications for IS200EXAMG1AAB

  • Manufacturer:
    General Electric
  • Product Category:
    General Automation
  • Spare Part Number:
    IS200EXAMG1AAB
  • Weight:
    0.4 kg
  • Tariff Code:
    8537101190
  • Ground-detection path:
    EXAM to EGDM via EPBP backplane
  • Field-bus range:
    125–1000 V dc in the documented EX2100 system
  • PPT voltage range:
    120–1300 V ac rms in the documented EX2100 system
  • J1 connection:
    53B field-flashing auxiliary contact
  • J2 connection:
    Ground-detection test and sense signals
  • Field-bus terminals:
    E1: VBUS-P; E2: VBUS-N
  • Shield-ground terminal:
    TB1 to cabinet chassis
  • JP1 / JP2 selection:
    PPT secondary below or above 750 V rms
  • JP3 selection:
    PPT secondary below or above 375 V rms

Information

Overview Downloads Applications / Compatibility Product Precautions
  • The original EXAM instruction identifies field terminals E1 and E2, locking connector J1 and D-sub connector J2. Jumper positions JP1 through JP3 are part of the documented voltage-selection arrangement and must be set for the installed system.
Role: Ground-detection attenuation
Interfaces: E1/E2 and J1/J2
Configuration: JP1–JP3 jumper selection
GE IS200EXAMG1AAB is an EXAM exciter attenuation module in the EX2100 excitation-control architecture. It conditions the ground-detection connection within the approved excitation-system arrangement.

The original EXAM instruction identifies field terminals E1 and E2, locking connector J1 and D-sub connector J2. Jumper positions JP1 through JP3 are part of the documented voltage-selection arrangement and must be set for the installed system.

The EX2100 and EX2100e arrangements use different companion interfaces, so an EXAM replacement requires the host drawing, cabinet version and AAB execution to be checked together. Follow the GE instruction and site isolation procedure during service.
Controller platform reference: GE EX2100 excitation control. Match the installed configuration and interfaces.
GE IS200EXAMG1AAB technical reference and installation verification downloads for Exciter Attenuation Module. Check the installed assembly, configuration and project records before service.
Match IS200EXAMG1AAB with the complete installed marking, connector layout and approved equipment documentation before commissioning.
Installation and commissioning checks for General Electric IS200EXAMG1AAB.
Isolate the excitation circuit

Apply the high-voltage cabinet safety procedure.

Identify host variant

Distinguish EX2100 from EX2100e companion wiring.

Record terminal leads

Capture E1/E2 connections before disassembly.

Check J1/J2

Match connector keying and seating.

Review JP1–JP3

Set jumper positions to the approved system voltage selection.

Verify detection

Perform the approved ground-detection functional test.

Alternative Names

IS 200EXAMG1AAB

Technical notes

Original instruction: GEI-100509C describes the EXAM family and its field interfaces.

Host distinction: EX2100 and EX2100e companion interfaces differ.

Configuration check: Match AAB revision and jumper settings to the installed cabinet.

FAQ View All FAQ

  • What role does IS200EXAMG1AAB play in ground detection?
    The EXAM family attenuates the ground-detection connection within the configured exciter system.
  • Why must JP1–JP3 be checked on IS200EXAMG1AAB?
    Their positions select the documented voltage arrangement and must match the cabinet design.
  • How are E1 and E2 used on IS200EXAMG1AAB?
    They are the identified field terminals; their destination must follow the installed GE wiring drawing.
  • What is connector J2 on IS200EXAMG1AAB?
    The EXAM instruction identifies a nine-pin D connector; verify the host cable and cabinet version.
  • How does the EX2100e host affect IS200EXAMG1AAB?
    Its companion interface differs from the EX2100 arrangement and requires the proper host drawing.
  • What should be recorded before IS200EXAMG1AAB replacement?
    Photograph board marking, E1/E2 leads, J1/J2 cables and jumper positions.
  • Is a different EXAM revision automatically compatible with IS200EXAMG1AAB?
    No. Confirm the AAB execution, connector implementation and approved configuration.
  • What completes the IS200EXAMG1AAB acceptance check?
    The site-approved ground-detection functional test and restored cabling record.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.