Match the complete marking
Include IS200EXAMG1AAB and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request current label, board and connector photos of IS200EXAMG1AAB. Compare the offered reference and host configuration with the installed equipment before approval.
Technical specifications for IS200EXAMG1AAB
-
Manufacturer:General Electric
-
Product Category:General Automation
-
Spare Part Number:IS200EXAMG1AAB
-
Weight:0.4 kg
-
Tariff Code:8537101190
-
Ground-detection path:EXAM to EGDM via EPBP backplane
-
Field-bus range:125–1000 V dc in the documented EX2100 system
-
PPT voltage range:120–1300 V ac rms in the documented EX2100 system
-
J1 connection:53B field-flashing auxiliary contact
-
J2 connection:Ground-detection test and sense signals
-
Field-bus terminals:E1: VBUS-P; E2: VBUS-N
-
Shield-ground terminal:TB1 to cabinet chassis
-
JP1 / JP2 selection:PPT secondary below or above 750 V rms
-
JP3 selection:PPT secondary below or above 375 V rms
Information
- The original EXAM instruction identifies field terminals E1 and E2, locking connector J1 and D-sub connector J2. Jumper positions JP1 through JP3 are part of the documented voltage-selection arrangement and must be set for the installed system.
Interfaces: E1/E2 and J1/J2
Configuration: JP1–JP3 jumper selection
The original EXAM instruction identifies field terminals E1 and E2, locking connector J1 and D-sub connector J2. Jumper positions JP1 through JP3 are part of the documented voltage-selection arrangement and must be set for the installed system.
The EX2100 and EX2100e arrangements use different companion interfaces, so an EXAM replacement requires the host drawing, cabinet version and AAB execution to be checked together. Follow the GE instruction and site isolation procedure during service.
-
GE IS200EXAMG1AAB technical reference
2-page reference on exciter attenuation module, verified identification and installation planning. -
GE IS200EXAMG1AAB installation verification guide
1-page guide for identification, connection review, installation checks and handover evidence.
Host compatibility: EX2100 and EX2100e use different companion interfaces; the AAB board and jumper selection must match the installed cabinet.
-
EX2100 ground detection
Use with the applicable EX2100 companion interface and approved cabinet wiring. -
EX2100e ground detection
Confirm the EAUX/ERAX host arrangement before applying a family-level connection. -
Auxiliary cabinet installation
Match the high-voltage interface cabinet location and wiring. -
Service replacement
Reproduce terminal, connector and jumper configuration from the installed unit.
Apply the high-voltage cabinet safety procedure.
Distinguish EX2100 from EX2100e companion wiring.
Capture E1/E2 connections before disassembly.
Match connector keying and seating.
Set jumper positions to the approved system voltage selection.
Perform the approved ground-detection functional test.
Alternative Names
Technical notes
Original instruction: GEI-100509C describes the EXAM family and its field interfaces.
Host distinction: EX2100 and EX2100e companion interfaces differ.
Configuration check: Match AAB revision and jumper settings to the installed cabinet.
FAQ View All FAQ
-
What role does IS200EXAMG1AAB play in ground detection?The EXAM family attenuates the ground-detection connection within the configured exciter system.
-
Why must JP1–JP3 be checked on IS200EXAMG1AAB?Their positions select the documented voltage arrangement and must match the cabinet design.
-
How are E1 and E2 used on IS200EXAMG1AAB?They are the identified field terminals; their destination must follow the installed GE wiring drawing.
-
What is connector J2 on IS200EXAMG1AAB?The EXAM instruction identifies a nine-pin D connector; verify the host cable and cabinet version.
-
How does the EX2100e host affect IS200EXAMG1AAB?Its companion interface differs from the EX2100 arrangement and requires the proper host drawing.
-
What should be recorded before IS200EXAMG1AAB replacement?Photograph board marking, E1/E2 leads, J1/J2 cables and jumper positions.
-
Is a different EXAM revision automatically compatible with IS200EXAMG1AAB?No. Confirm the AAB execution, connector implementation and approved configuration.
-
What completes the IS200EXAMG1AAB acceptance check?The site-approved ground-detection functional test and restored cabling record.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
IS200EXAMG1AABProduct Details -
DS3820PS7A1B1CProduct Details -
IS200WETBH1BAAProduct Details -
DS200TCQAG1AProduct Details -
DS200DDTBG2ABBProduct Details -
IS200EMCSG1AAProduct Details -
IS200WETBH1ABAProduct Details -
DS200SDCCG5AProduct Details -
IS200ECTBG1ABBProduct Details -
IC698CHS017Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.