Match the complete marking
Include AAI135-H00 S1 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered AAI135-H00 S1 reference with the installed equipment and applicable Yokogawa documentation.
Technical specifications for AAI135-H00 S1
-
Manufacturer:Yokogawa
-
Product Category:DCS Systems
-
Spare Part Number:AAI135-H00 S1
-
Weight:0.25 kg
-
Tariff Code:8537101190
-
Analog inputs:8 channels
-
Input signal:4–20 mA DC
-
Input current limit:25 mA
-
Input accuracy:±16 µA
-
Data update:10 ms
-
Powered input resistance:290 Ω at 20 mA; 450 Ω at 4 mA
-
Unpowered input resistance:≥500 kΩ
-
Transmitter voltage at 20 mA:≥15.0 V
-
Transmitter voltage at zero current:≤29.3 V
-
5 V supply consumption:360 mA maximum
-
24 V supply consumption:450 mA maximum
-
Temperature drift:±16 µA / 10°C
-
Field/system withstand:500 V AC, 1 minute
-
Channel/channel withstand:500 V AC, 1 minute; complete MIL cable assembly subject to cable rating
Information
- Independently referenced transmitters can share one FIO slot without making their channel circuits a common electrical group.
Communication choice: H specifies digital HART communication alongside the current measurement.
Environmental selection: H00 is the basic type; the H03 G3/temperature option is a different order selection.
The powered input includes a protection-circuit voltage drop in addition to its sensing resistance. A two-wire transmitter must retain its minimum terminal voltage after the cable drop is deducted from the available module supply; a correct current range alone does not establish a workable loop. With a two-wire transmitter at 20 mA the module provides at least 15.0 V at the transmitter terminals before external wire loss. The corresponding zero-current maximum is 29.3 V, so both minimum compliance and maximum permissible instrument voltage matter.
Pressure-clamp, MIL and KS1 connections are alternative termination arrangements. The external cable can become the limiting insulation element, so the module withstand test cannot be treated as an unconditional rating for the entire installed harness. For the pressure-clamp route, /13A00 denotes ATI3A-00 and /K4A00 denotes ATK4A-00. ATI3S and ATI3D selections distinguish simplex and dual-redundant terminal arrangements; the bare H00 S1 marking does not include one of these adapters.
-
Yokogawa AAI135-H00 S1 official technical excerpt
Original legacy electrical data and H00/H03 suffix selection for the applicable FIO module. PDF, 2 pages. -
Yokogawa AAI135-H00 S1 engineering guide
Apter Power engineering guide for CENTUM FIO analog I/O. Use the HART-capable legacy node configuration and the termination specified for the actual eight-input assignment. PDF, 3 pages.
Integration boundary: Use the HART-capable legacy node configuration and the termination specified for the actual eight-input assignment. The isolated-input family is used in ESB, ER and compact FIO arrangements with the applicable node. A remote HART path additionally requires EB401 Rev 2 or later; a local current reading does not establish that remote digital path.
-
Mixed transmitter references
Separate channel circuits support measurements whose field references cannot be combined into a non-isolated input group. -
Two-wire field instruments
The module can feed a transmitter when the channel setting and full-current voltage budget are correct. -
Independently powered instruments
A four-wire transmitter requires the corresponding channel arrangement rather than a second unintended loop supply. -
Redundant FIO input design
The family permits dual redundancy; the node and terminal configuration must implement it rather than relying on one module.
Identify two-wire and four-wire circuits before removing the existing terminal connection.
Include field-wire loss at maximum operating current, not just at the midrange reading.
Check cable insulation specifications before assigning a channel-to-channel withstand level.
Use the specified isolation barrier for intrinsically safe loops; never connect a Zener barrier directly.
A remote-node installation needs EB401 firmware Rev 2 or later for the documented HART function.
Inject current into each of the eight inputs, confirming its measured value and assigned channel.
Alternative Names
Technical notes
Input protection: The legacy input-burden calculation includes a protection drop of up to 0.8 V, which changes the source compliance needed at low current.
Remote digital access: EB401 revision is part of a remote HART path; analog conversion alone does not prove digital access.
Terminal selection: ATI3A and ATK4A adapter choices have distinct ordering identities; retain the installed terminal mapping.
FAQ View All FAQ
-
Can AAI135-H00 S1 replace an AAI141 without changing the field grouping?No direct equivalence follows from the current range. Check the eight-versus-sixteen input allocation and the isolated-versus-non-isolated circuit design before assigning the node channels.
-
Why can AAI135-H00 S1 read correctly on a bench but fail with the field transmitter connected?A current calibrator may have more compliance voltage than the transmitter loop. Measure transmitter voltage at the high-current end, including cable loss and the powered input burden.
-
Does AAI135-H00 S1 need the same channel setting for two-wire and four-wire devices?No. Identify whether the field instrument needs module power, then use the corresponding channel setting and verify that two supplies are not connected against one another.
-
Can the cable defeat the isolation expected from AAI135-H00 S1?Yes. The complete assembly is limited by the MIL cable electrical specification. Check the actual harness rating and common connections before accepting the isolated-channel arrangement.
-
What should be checked when AAI135-H00 S1 passes current signals but HART is absent at a remote node?Check the HART-enabled module execution and the remote EB401 firmware revision before changing the analog calibration. The documented remote path requires Rev 2 or later.
-
Can AAI135-H00 S1 be connected directly to a Zener safety barrier?The applicable FIO specification excludes that connection. Use an isolation-barrier design approved for the intended intrinsically safe loop and verify its separate compliance-voltage requirement.
-
How should the input accuracy of AAI135-H00 S1 be expressed on a 4–20 mA process span?The ±16 µA input limit corresponds to ±0.1% of the 16 mA signal span, rather than ±0.1% of the instantaneous reading. Convert it using the configured process span and include calibrator uncertainty and the applicable temperature contribution when defining a loop-test acceptance limit.
-
Can eight transmitter currents alone determine the node power budget for AAI135-H00 S1?No. Field-loop demand is not the complete module load. Budget the published 5 V and 24 V rail maxima separately, together with the other fitted node modules. Do not add currents from different voltage rails or treat eight times the loop current as a complete node-supply calculation.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.