Match the complete marking
Include AAI835-H03 S1 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered AAI835-H03 S1 reference with the installed equipment and applicable Yokogawa documentation.
Technical specifications for AAI835-H03 S1
-
Manufacturer:Yokogawa
-
Product Category:DCS Systems
-
Spare Part Number:AAI835-H03 S1
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
Analog inputs:4 channels
-
Input signal:4–20 mA DC
-
Input current limit:25 mA
-
Input accuracy:±16 µA
-
Data update:10 ms
-
Powered input resistance:290 Ω at 20 mA; 450 Ω at 4 mA
-
Unpowered input resistance:≥500 kΩ
-
Transmitter voltage at 20 mA:≥15.0 V
-
Transmitter voltage at zero current:≤29.3 V
-
5 V supply consumption:360 mA maximum
-
24 V supply consumption:450 mA maximum
-
Temperature drift:±16 µA / 10°C
-
Field/system withstand:500 V AC, 1 minute
-
Channel/channel withstand:500 V AC, 1 minute; complete MIL cable assembly subject to cable rating
-
Analog outputs:4 channels
-
Output signal:4–20 mA DC
-
Output accuracy:±48 µA
-
Output load:0–750 Ω; 200–750 Ω at 60–70°C in a qualified remote node
-
Open-output threshold:<0.65 mA
-
Temperature option:−20 to +70°C; compatible host/node required
-
Atmosphere option:ISA Standard G3
Information
- The environmental suffix and output-load window must be considered together when an isolated four-loop interface operates in a qualified remote node.
Hot-node constraint: At 60–70°C in an eligible remote node, output load must remain within 200–750 Ω.
Signal separation: The combined input/output architecture retains isolated channels rather than the non-isolated AAI841 topology.
The high-temperature remote-node load restriction is a functional circuit requirement, not a packing or storage condition. The sum of receiver and cable resistance must remain in the applicable window, including a minimum resistance that can be overlooked in a short bench test. For eligible remote installations at 60–70°C, each output needs 200–750 Ω. A 100 Ω bench receiver can therefore demonstrate current delivery without reproducing the documented hot-service load condition.
The input half and output half impose different commissioning tasks. Incoming transmitter current must be mapped to the intended measurement, while outgoing current must be verified at the receiver; environmental identity and HART communication are additional checks rather than substitutes for either electrical test. Input drift is ±16 µA per 10°C and output drift is ±48 µA per 10°C. These are different influences on the two directions; retain the measured ambient and direction of test when investigating a temperature-dependent process-loop discrepancy.
-
Yokogawa AAI835-H03 S1 official technical excerpt
Original legacy electrical data and H00/H03 suffix selection for the applicable FIO module. PDF, 2 pages. -
Yokogawa AAI835-H03 S1 engineering guide
Apter Power engineering guide for CENTUM FIO analog I/O. Confirm G3/temperature execution, node qualification and output compliance as separate parts of the finished installation. PDF, 3 pages.
Integration boundary: Confirm G3/temperature execution, node qualification and output compliance as separate parts of the finished installation. The /B3A00 ATB3A-00 and /K4A00 ATK4A-00 terminations must retain the four-plus-four allocation. HART in a remote node also depends on the documented EB401 Rev 2-or-later path.
-
Temperature-qualified isolated loops
Retain H03 where the installation requires the extended environmental execution and individual channel separation. -
Remote output-load engineering
Account for both the lower and upper resistance limits at the documented hot-node condition. -
Mixed field instruments and receivers
Keep the transmitter input and command output roles explicit in each loop’s terminal allocation. -
HART-enabled combined I/O
Verify the supporting digital path without assuming it validates output delivery or process response.
Record node ambient and determine whether the remote-node 60–70°C output-load restriction applies.
Include wiring resistance rather than testing only the receiving device nameplate value.
An H00 card with equal channel count does not establish the required environmental option.
Identify loop-current directions; never place a source-mode calibrator across an active output.
Check terminal and cable ratings together when qualifying the complete isolated assembly.
Compare commanded current, receiver current and actuator response at the same approved operating point.
Alternative Names
Technical notes
Load-window selection: Use the node’s actual operating condition to select the permitted output resistance range; a room-temperature continuity check cannot settle this.
Independent acceptance: Input scaling, output delivery and HART access each require their own observation.
Suffix substitution: The common signal range between H00 and H03 does not establish equal environmental execution.
FAQ View All FAQ
-
Why can a short-loop bench test misrepresent AAI835-H03 S1 at a hot remote node?A near-zero-ohm test connection can miss the documented minimum output load at 60–70°C. Compare the installed receiver-plus-wire resistance with the applicable range before accepting the circuit.
-
Can cable resistance be counted toward the load on AAI835-H03 S1?It forms part of the series output load, so include it in the complete circuit assessment. Check both resistance limits at the actual temperature condition rather than using the receiver value alone.
-
What should be checked before substituting H00 for AAI835-H03 S1?Establish whether G3 and extended-temperature execution are required. If they are, an H00 unit is not established as equivalent merely by matching current range and channel count.
-
Does AAI835-H03 S1 make a nonqualified node suitable for extended ambient operation?No. The node, power arrangement, termination and enclosure retain separate environmental conditions. Verify the complete supported installation before applying the module option.
-
How can an incorrect input/output terminal assignment on AAI835-H03 S1 be detected?Trace one measurement circuit and one command circuit independently, then compare their project assignments. A plausible measurement does not validate the output terminal map.
-
Why can a commanded output on AAI835-H03 S1 coexist with an open-loop fault?The command is a requested value, whereas the output status reports the physical current path. Inspect the receiver connection and continuity before adjusting controller scaling.
-
Does the channel isolation of AAI835-H03 S1 remove barrier-selection work?No. The legacy specification calls for an isolation-barrier arrangement for intrinsically safe duties and excludes a direct Zener-barrier connection. Review the entire approved field loop.
-
What evidence should accompany a successful AAI835-H03 S1 commissioning test?Keep the H03 label, node qualification, ambient condition, measured load and input/output test results together. HART access and the external receiver response should be recorded separately from numerical channel checks.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studies-
Honeywell FC-RUSIO-3224 Delivered for an Oman Government ProjectRead case > -
Receiving Inspection and Acceptance of Replacement Control ModulesRead case > -
Invensys 3806E Sourcing: Five Spares Delivered to the CustomerRead case > -
28 ABB BRC410 Units: Ready to Inspect, Collected on Order DayRead case >
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.