Match the complete marking
Include IS200VRTDH1DAC and every hardware or assembly-revision marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered IS200VRTDH1DAC reference with the installed equipment and applicable General Electric documentation.
Technical specifications for IS200VRTDH1DAC
-
Manufacturer:General Electric
-
Product Category:Gas Turbine Control
-
Spare Part Number:IS200VRTDH1DAC
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
RTD input capacity:16
-
Sensor connection:3 wire
-
RTD excitation:10 mA DC, pulsed
-
ADC resolution:14 bit
-
Normal scan period:250 ms
-
Fast scan provision:40 ms / 25 Hz; not TMR
-
Input electrical span:0.3532-4.054 V
-
Maximum two-way lead resistance:15 ohm
-
Maximum stated lead distance:300 m
-
Processor consumption:Less than 12 W
-
Front indicators:3: RUN, FAIL, STATUS
-
Configurable input groups:2 x 8 inputs
-
Normal line-frequency rejection:50 Hz or 60 Hz
-
Higher-gain resistance condition:Gain 2.0 below 190 ohm
Information
- General Electric IS200VRTDH1DAC turns detector resistance into temperature using selected curves and two independently configured input groups, so group settings are central to fault isolation.
Conversion choices: Resistance and temperature modes require different acceptance records.
Fault isolation: Invalid channels can be removed from scanning without stopping all RTD processing.
The first eight and second eight inputs have independent rate and gain choices. The normal 4 Hz mode includes a 50 Hz or 60 Hz rejection selection; the 25 Hz option has architecture restrictions and is not available for TMR. Gain 2.0 is intended for improved accuracy below 190 ohms, while the 10 ohm copper selection has its own gain option.
Hardware electrical checks and configurable temperature limits have different consequences. A hardware-invalid input leaves the scan, whereas a system limit can generate enabled/latching application signals. A diagnosis should retain the resistance, curve, group settings and reset history, so a repaired wire is not confused with an unreset or not-yet-reinstated channel.
-
General Electric IS200VRTDH1DAC official technical excerpt
Original GEH-6421H system-architecture pages for the RTD processing architecture. PDF, 2 pages. -
General Electric IS200VRTDH1DAC engineering guide
Apter Power field guide: group gain/filter settings, resistance simulation and reinstatement. PDF, 2 pages.
Integration boundary: This processor selects curve, gain and line-frequency rejection. It must be matched to the physical detector, not to a generic temperature-input label.
-
Mixed detector characteristics
Use each configured detector curve to convert resistance without assigning the same temperature span to unlike sensors. -
Low-resistance accuracy planning
Consider the documented higher-gain setting only within its resistance condition and test it over the intended working region. -
Mains-noise rejection
Select the 50 Hz or 60 Hz group filter to suit the installation while preserving the required scan behavior. -
Resistance-based acceptance
Use the Ohms input selection or the approved simulator method to separate sensor resistance from temperature-linearization errors.
Record rate, line-frequency rejection and gain for each eight-input group before removing the VRTD.
Preserve CU10, the selected PT100 variant, N120 or other approved characteristic exactly; nominal resistance alone does not identify every curve.
Confirm the architecture before enabling 25 Hz operation; use the supported normal filtered mode in TMR.
Keep unconnected inputs configured unused so an absent detector does not become a misleading active measurement.
Diagnose hardware removal from scan separately from a latching high/low system limit before issuing a reset.
Use several resistance points within the selected curve and gain region, recording input resistance and converted temperature together.
Alternative Names
Technical notes
Recovery timing: An automatically reinstated channel can take up to the documented 20-second recovery interval; compare that behavior with manual-reinstatement configuration after repairing the circuit.
Electrical range: The 0.3532-4.054 V input electrical span is an internal measurement boundary, not a common operating temperature range for all detectors.
Channel identifiers: A connector ID contains the termination type and location. A wrong terminal/cable identity must be corrected before a curve or calibration adjustment is used to explain the fault.
FAQ View All FAQ
-
Why do eight inputs on IS200VRTDH1DAC show a different response time from the other eight?Group A and Group B have independent rate/filter settings. Compare the two group configurations and use the same controlled resistance transition before attributing the difference to the sensor wiring.
-
How should a Pt100 test above 190 ohms be planned for IS200VRTDH1DAC?The Gain 2.0 accuracy provision is conditioned on resistance below 190 ohms. Review the configured gain and intended working region; do not extend that accuracy implication beyond its stated resistance condition.
-
Can IS200VRTDH1DAC use one generic Pt100 curve for every platinum detector?Several Pt100 characteristics are selectable. Match the actual detector standard, then compare resistance/temperature points across the required range; a common 100-ohm nominal value does not establish identical conversion.
-
What does diagnostic 156 mean when IS200VRTDH1DAC is commissioned in TMR?The configured 25 Hz rate is incompatible with TMR. Restore the supported 4 Hz setting with the appropriate 50/60 Hz rejection, then verify the configuration and channel diagnostics.
-
Why can IS200VRTDH1DAC continue to report a repaired input as invalid?The channel may remain removed from scan or latched according to recovery configuration. Check present resistance, the original hardware diagnostic and reinstatement/reset state before making another hardware change.
-
How can IS200VRTDH1DAC help distinguish a wrong curve from a cable compensation error?Compare a known resistance applied at the termination with the selected linearization, then repeat through the field leads using the approved three-wire method. A terminal test that passes while the field-path test fails directs investigation to leads/connections.
-
Why should an unused input on IS200VRTDH1DAC be disabled rather than assigned a fictitious resistance?Unused is a supported channel selection that removes an absent detector from scanning. A fabricated valid value hides the true channel allocation and can mislead the temperature application.
-
What should be checked when IS200VRTDH1DAC indicates a cable-ID failure on J3 or J4?Trace the named connector and termination identity, then inspect its cable and seating. This is an interface-identification path; changing detector coefficients does not repair a failed ID connection.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.