IS200TVIBH2BCC

Vibration Input Terminal Board
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

This Mark VI vibration termination interfaces machine transducers with a VVIB processor. The correct sensor class and channel configuration determine whether the path measures vibration, position or phase; the terminal board itself does not perform the processor conversion.
  • Manufacturer part number
    IS200TVIBH2BCC
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    33cm x 17.7cm x 4cm
  • Country of Origin
    USA
Get a quick price for IS200TVIBH2BCC
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the full marking, quantity and label photos. We review the item and any version details that need clarification.
  • 1

    Confirm the offer

    Check the quoted reference, condition, included items and expected dispatch date before approving your order.
  • 2

    Arrange dispatch

    Confirm delivery details and receive the tracking number when it becomes available.
  • Match the complete marking

    Include IS200TVIBH2BCC and every hardware or assembly-revision marking visible on the item. Keep the exact reference on your enquiry and quotation.
  • Check the offered item before ordering

    Request available label and interface photos. Have your maintenance team compare the offered IS200TVIBH2BCC reference with the installed equipment and applicable General Electric documentation.

Technical specifications for IS200TVIBH2BCC

  • Manufacturer:
    General Electric
  • Product Category:
    Gas Turbine Control
  • Spare Part Number:
    IS200TVIBH2BCC
  • Weight:
    0.58 kg
  • Tariff Code:
    8537101190
  • Transducer supply:
    -24 V DC, current limited
  • Transducer supply limit:
    12 mA per transducer
  • Proximity displacement span:
    0-4.5 V peak-to-peak
  • Proximity accuracy, 5-200 Hz:
    +/-0.030 V peak-to-peak
  • Proximity accuracy, 200-500 Hz:
    +/-0.150 V peak-to-peak
  • Seismic velocity input span:
    0-2.25 V peak
  • Integrated-acceleration tracking band:
    10-233 Hz
  • Static position input span:
    -0.5 to -20 V DC
  • Static position accuracy:
    +/-0.2 V
  • Phase span:
    0-360 degrees
  • Conditional 1X phase accuracy:
    +/-2 degrees up to 14,000 rpm
  • Integrated velocity span:
    0-2.25 V peak
  • Integrated velocity accuracy:
    +/-0.015 V peak, 10-233 Hz

Information

Overview Downloads Applications / Compatibility Product Precautions
  • General Electric IS200TVIBH2BCC routes different machine-transducer signals into the VVIB measurement chain; displacement, velocity and DC position require different test stimuli and units.
Measurement classes: Keep AC vibration amplitude separate from DC position.
Channel pairing: An X/Y pair can raise a fault when either member exceeds its limit.
Phase reference: Phase acceptance requires the configured once-per-revolution reference.
IS200TVIBH2BCC is the TVIB field termination in a Mark VI VVIB measurement chain. Its H2B CC identity must be retained with the installed transducer and cable allocation. Dynamic vibration processing occurs in VVIB; the terminal-board identity alone does not establish sensor sensitivity, machine alarm values or every physical connector option.

Different measurement classes require different amplitude conventions: proximity displacement is expressed in peak-to-peak voltage, seismic velocity in peak voltage, and static position in DC voltage. An amplitude accepted in one convention can be wrong in another. Preserve the transducer sensitivity and unit conversion before judging an apparent change in vibration.

The chain checks electrical input limits separately from configured system limits. Position functions use the DC component for applications such as thrust wear or differential expansion; phase uses the 1X component relative to the key-slot reference. Static, dynamic and phase acceptance must therefore remain separate records even when they originate in the same terminal assembly.
Controller platform reference: GE Mark VI VVIB vibration inputs. Match the transducer and VVIB configuration.
Retain the transducer class and measurement convention before injecting vibration, position or phase stimuli.
Trace each transducer class

Record probe type, sensitivity and intended units before disturbing TVIB field wiring.

Check negative probe power

Confirm the intended -24 V supply polarity and sensor load; a conventional positive-voltage transmitter is not automatically compatible.

Distinguish peak and peak-to-peak

Set the test instrument and injected waveform convention to the measurement class used by the channel.

Use band-appropriate accuracy

Apply the correct frequency band when comparing injected proximity or velocity amplitude with the controller value.

Retain both X/Y channels

Test each probe independently because either member of the pair can initiate a configured limit condition.

Separate position from phase proof

Use DC points for position and a synchronized dynamic/reference stimulus for phase; neither test substitutes for the other.

Alternative Names

GE IS200TVIBH2BCC General Electric IS200TVIBH2BCC

Technical notes

Velocity uncertainty: For the shared seismic/velocity path, use the greater of 2% of reading or 0.008 V peak in the 5-200 Hz band; the percentage term changes to 5% at 200-500 Hz.

Integration boundary: The accelerometer-derived velocity tracking band is not the same as the proximity displacement band; keep the configured processing class with the test record.

Position diagnostics: A static-position electrical limit must be distinguished from a configured thrust/expansion operating limit before the sensor zero is adjusted.

FAQ View All FAQ

  • Why can a sine-wave test on IS200TVIBH2BCC appear wrong by a factor of two?
    Check whether the instrument reports peak or peak-to-peak amplitude and whether the configured channel is velocity or displacement. Convert the source convention before investigating hardware gain.
  • What should be checked if only one member of an X/Y pair through IS200TVIBH2BCC reaches a limit?
    Review the two channel inputs and their limit states separately. The chain can report a pair fault when either member exceeds its limit; a normal companion reading does not invalidate that diagnostic.
  • Can a valid DC position reading prove vibration measurement through IS200TVIBH2BCC?
    DC position uses the static component, whereas vibration uses dynamic amplitude and frequency processing. Apply a separate in-band AC stimulus and preserve the sensor scaling before accepting vibration performance.
  • Why can the error allowance for IS200TVIBH2BCC increase above 200 Hz?
    The shared measurement specifications use different accuracy bands. Compare the actual test frequency with the applicable proximity or seismic band instead of applying the low-frequency allowance across the complete spectrum.
  • How can low-amplitude velocity readings through IS200TVIBH2BCC be assessed?
    Use the specified absolute floor as well as the percentage term when calculating the acceptance allowance. A percentage-only calculation overstates precision close to zero.
  • What is required to test phase through IS200TVIBH2BCC near its stated speed limit?
    Use the configured 1X vibration component and valid key-slot reference under the documented conditions. A free-running signal without that reference cannot prove the stated phase accuracy.
  • Why should a position-limit fault through IS200TVIBH2BCC not be cleared by re-zeroing immediately?
    Record the raw DC input, electrical diagnostic and configured operating limit first. Re-zeroing can conceal a real target movement or wiring problem without repairing its cause.
  • Can all transducers connected to IS200TVIBH2BCC use the same current allowance?
    Check the intended sensor supply and each transducer demand against the current-limited chain. A probe power fault is different from an amplitude-range fault and needs a supply/load test before calibration is changed.