Technical specifications for IS200TPROH1CBB
-
Manufacturer:General Electric
-
Product Category:Gas Turbine Control
-
Spare Part Number:IS200TPROH1CBB
-
Weight:0.9 kg
-
Tariff Code:8537101190
-
Field terminals:2 removable 24-point barrier blocks
-
PPRO positions:3: JR1 / JS1 / JT1
-
Trip-board cable interfaces:3 x DC-37: JX1 / JY1 / JZ1
-
Speed input paths:9; 3 per R/S/T section
-
Magnetic pickup frequency:2-20000 Hz, documented matched system
-
Pulse-rate accuracy:0.05% of reading, documented matched system
-
Sensitivity, 0-2 kHz:27 mV peak-to-peak required
-
Sensitivity, 2-6 kHz:50 mV peak-to-peak required
-
Sensitivity, 6-10 kHz:100 mV peak-to-peak required
-
Sensitivity, 10-15 kHz:160 mV peak-to-peak required
-
Sensitivity, above 15 kHz:250 mV peak-to-peak required
-
PT input burden:<3 VA per input
-
PT synchronization range:75-130 Vrms
-
PT isolation barrier:1500 Vrms
-
Customer sensor outputs:3 x 24 VDC, 25 mA maximum each; not voted
-
Operating temperature:-30 to 65 deg C, documented board design
Information
- GE IS200TPROH1CBB combines field-signal termination with a three-pack backup-protection interface; H1C uses removable barrier terminals rather than the H2C Euro-style terminals.
Pack positions: R, S and T PPRO packs occupy JR1, JS1 and JT1.
Platform distinction: TPROH#C belongs to Mark VIe and is not supported by Mark VI control.
The board conditions nine speed-input paths and includes bus/generator PT input functions. Magnetic pickup sensitivity depends on frequency, so a nominal pulse frequency is insufficient for an input test. The PT function also has an application enable condition; a disabled live value is not automatically a failed transformer input.
Customer P24 outputs are sourced from the ORed pack power path and are not voted outputs. Removing one pack therefore does not establish that the field sensor supply is dead. The connected trip board must be selected for its actual emergency-stop voltage, relay arrangement and output requirements; TPRO alone does not establish the complete trip-system rating.
-
General Electric IS200TPROH1CBB technical reference
Apter Power technical reference to H1C interfaces, frequency-dependent sensitivity and matched-system limits. PDF, 1 pages. -
General Electric IS200TPROH1CBB engineering guide
Apter Power speed/PT injection and backup-trip interface acceptance guide. PDF, 2 pages.
Integration boundary: Accept the H1C terminal form, pack generation, speed-sensor electrical type and selected trip-relay board as a coordinated protection path.
-
Magnetic speed protection
Use the frequency-dependent sensitivity requirement when testing turbine speed pickups. -
Bus/generator PT monitoring
Retain the enabled PT function, rated test voltage and input isolation arrangement. -
Three-pack backup protection
Map R/S/T packs and their trip-board cables to the approved redundant design. -
Powered speed sensors
Review the non-voted P24 output and return path when using active/TTL sensor wiring.
Use the approved turbine-protection outage and test procedure before disturbing the backup path.
Retain the removable barrier blocks and point map; do not infer H2C Euro-terminal equivalence.
Use the applicable sensitivity band when simulating magnetic speed inputs.
Compare the K25A_Enab configuration before diagnosing a missing bus/generator live value.
Account for ORed pack supplies and measure P24 before handling active-sensor conductors.
Verify relay-board type, E-stop voltage and cable allocation; keep 240 VAC and DC circuits from unintended cross-connection.
Alternative Names
Technical notes
Pack power versus board load: The certificate pack supply figure belongs to the combined I/O pack system and is not a standalone TPRO consumption rating.
P24 continuity: The sensor output can remain powered by the other packs when one pack is off; isolation must be verified electrically.
Sensitivity acceptance: A low-amplitude high-frequency pulse can fail detection even when its frequency is within range; evaluate amplitude and frequency together.
FAQ View All FAQ
-
Does a TTL speed input on IS200TPROH1CBB use the same signal landing as a passive pickup?The documented TTL table uses TB3 for TTL High and a corresponding even-numbered TB2 return. For the first R-path example, TTL High is TB3 pin 1 and its return is TB2 terminal 32. Reconcile sensor type, path and the approved wiring table together; copying a passive-pickup landing does not establish the TTL connection.
-
Can unused P24 capacity from other IS200TPROH1CBB outputs automatically support a 40 mA sensor?Each of the three customer 24 V outputs is specified for a maximum 25 mA. The presence of three outputs does not document permission to pool them or parallel connections for a larger load. Compare each sensor demand with its assigned output and use an approved power arrangement when that demand exceeds the individual limit.
-
What PT cable condition should be retained when verifying IS200TPROH1CBB from a remote test point?The documented PT input allows up to 1000 ft of 18 AWG wiring. That condition does not establish an arbitrary cable installation as equivalent. Record the installed conductor and length, compare voltage at the board under its input burden, and retain the bus/generator allocation; a correct voltage at the remote source alone is incomplete evidence.
-
Can equal bus and generator PT test voltages conceal swapped inputs on IS200TPROH1CBB?Yes. The board has two separate bus/generator PT input functions, so applying the same test value to both does not distinguish their allocation. Under the authorized test plan, identify each source and compare its corresponding live channel separately, with the required application enable condition established before interpreting a missing value.
-
Does working PPRO Ethernet communication prove the trip-board cable path of IS200TPROH1CBB?The pack network, direct pack-to-terminal connection and DC-37 relay-board connection are different interfaces. A healthy network service does not prove the correct JX1/JY1/JZ1 cable or relay-board identity. Reconcile the hardware ID and cable allocation, then verify the required end-to-end trip function under the approved protection test.
-
Do three pack mounting positions make every IS200TPROH1CBB arrangement a valid TMR system?Mounting capacity alone does not define the installed protection architecture. The compatibility table distinguishes trip boards: TREG and TREL entries are TMR, while the listed TRES entries support simplex as well as TMR. Confirm the selected pack count, trip-board execution and controller configuration together before approving an arrangement.
-
Can the IS200TPROH1CBB PCB be mounted directly on metal when the carrier is changed?The documented assembly includes a plastic insulator between TPRO and its sheet-metal carrier or panel-mount assembly. Preserve that insulating component and the intended mounting method during a mechanical change. A matching hole pattern does not establish the same electrical or mechanical assembly condition.
-
Does the 1500 Vrms PT isolation figure permit a 1500 V signal at an IS200TPROH1CBB input?No. The isolation barrier and the 75-130 Vrms synchronization input envelope describe different conditions. Keep the actual signal within its operating envelope and follow the approved test method; a barrier withstand figure is not a measurement range or permission for a connected-system high-voltage test.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
IS200TPROH1CBBProduct Details -
IS200EPSMG1ADCProduct Details -
DS200TBPAG1ACCProduct Details -
IS200TRLYH1BHHProduct Details -
IS200VRTDH1DACProduct Details -
IS200EPSMG1AECProduct Details -
IS200TVIBH2BCCProduct Details -
IS200EDCFG1AEDProduct Details -
IS200TSVOH1BDCProduct Details -
IS200EISBH1AABProduct Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.