Match the complete marking
Compare every token in 330101-00-40-05-02-05 with the installed label and the applicable manufacturer document.
-
Verify the assembly boundary
Confirm the terminal board, I/O pack, connector, carrier or matched-system components that belong with 330101-00-40-05-02-05.
Technical specifications for 330101-00-40-05-02-05
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330101-00-40-05-02-05
-
Weight:0.05 kg
-
Tariff Code:8537101190
-
Probe family:3300 XL 8 mm proximity probe
-
Thread:3/8-24 UNF
-
Armor:Without armor
-
Unthreaded length option 00:0.0 in
-
Overall case length option 40:4.0 in
-
Total electrical length option 05:0.5 m
-
Connector / cable option 02:Miniature coaxial ClickLoc connector; standard cable; without connector protector
-
Approval option 05:CSA, ATEX and IECEx approvals
-
Probe tip diameter:8.0 mm
-
Probe cable:75 ohm triaxial FEP-insulated cable
-
Probe case material:AISI 303 or 304 stainless steel
-
Probe tip material:Polyphenylene sulfide (PPS)
-
Standard probe operating / storage range:-52 to +177 deg C
-
System linear range:2 mm / 80 mils; applies to a complete matched 3300 XL 8 mm system
-
System incremental scale factor:7.87 V/mm / 200 mV/mil; applies to the complete matched system
-
Nominal target gap:1.27 mm / 50 mils; complete matched-system reference condition
-
Extension cable capacitance:69.9 pF/m typical; matched-system cable reference
-
Maximum field wiring length:305 m between Proximitor sensor and monitor; complete-system reference
Information
- 330101-00-40-05-02-05 has a defined 3300 xl 8 mm proximity probe role in the Bently Nevada 3300 XL 8 mm proximity transducer system; approval depends on the complete catalog number and installed assembly boundary.
Electrical execution: 0.5 m total length with miniature ClickLoc connector and standard cable.
Approval execution: Option 05 identifies CSA, ATEX and IECEx approvals.
The 05/02 electrical selection specifies 0.5 m total electrical length and a miniature coaxial ClickLoc connector on standard cable without a connector protector. The final 05 option identifies CSA, ATEX and IECEx approvals.
The published 2 mm linear range, 7.87 V/mm scale factor and 1.27 mm nominal gap apply to a complete matched 3300 XL 8 mm system under the stated reference conditions. Keep the probe, extension cable and Proximitor sensor electrical length compatible when commissioning the channel.
330101-00-40-05-02-05 Applicable Manufacturer Document
Verified manufacturer material - PDF. Exact catalog mapping, applicable hardware composition and technical boundary.330101-00-40-05-02-05 Installation & Commissioning Guide
Apter Power engineering guide - PDF, 5 pages. Identity checks, interface restoration, diagnostics, acceptance and handover.
Compatibility boundary: Match the complete 330101-00-40-05-02-05 marking, mating hardware and installed configuration before replacement.
Radial vibration measurement
Use within a matched 3300 XL 8 mm transducer chain for fluid-film bearing machinery.Axial position measurement
Apply the documented probe gap and target geometry for position monitoring.Keyphasor and speed reference
Use only where the installed monitor and mechanical target arrangement are approved for the function.Matched-system maintenance
Preserve total electrical length, connector execution and hazardous-area documentation during replacement.
Compare the full 330101-00-40-05-02-05 code with the installed probe and maintenance record.
Do not kink, crush or contaminate the 75 惟 triaxial cable and ClickLoc connector.
Match the probe and extension cable to the Proximitor sensor total-length selection.
Use the approved machine drawing and gap-setting procedure before returning the channel to service.
Confirm option 05 approval markings and the complete installed circuit against the applicable control drawing.
Perform an approved gap or vibration response check and retain the result with monitor diagnostics.
Alternative Names
Technical notes
Matched-system rule: Use 330101-00-40-05-02-05 only with extension cable and Proximitor sensor selections that preserve the approved total electrical length.
Mechanical setting: Confirm 3/8-24 thread engagement, installed case clearance and the documented probe gap before tightening the locknut.
Approval boundary: Option 05 identifies CSA, ATEX and IECEx approvals; verify the complete installed circuit and applicable control drawing.
FAQ View All FAQ
-
How should 330101-00-40-05-02-05 be identified before replacement?Match all six option groups in 330101-00-40-05-02-05: probe family, unthreaded length, case length, electrical length, connector/cable and approvals.
-
What installed interfaces must be checked for 330101-00-40-05-02-05?Verify the 3/8-24 UNF mounting, 4.0 in case length, 0.0 in unthreaded length and ClickLoc connection used by 330101-00-40-05-02-05.
-
Which configuration values must be preserved before removing 330101-00-40-05-02-05?Record the matched probe, extension cable and Proximitor sensor identities associated with 330101-00-40-05-02-05; do not mix system lengths.
-
How should the field wiring for 330101-00-40-05-02-05 be verified?Protect the 75 ohm triaxial cable, maintain the approved bend route and keep connector contamination away from 330101-00-40-05-02-05.
-
What should be checked before energizing 330101-00-40-05-02-05?Confirm thread engagement, probe gap, cable routing, matched 0.5 m electrical length and applicable hazardous-area drawing for 330101-00-40-05-02-05.
-
How can a suspected 330101-00-40-05-02-05 fault be separated from an external fault?Check probe gap, connector condition, cable continuity and the matched Proximitor sensor before replacing 330101-00-40-05-02-05.
-
What proves that 330101-00-40-05-02-05 is operating correctly after installation?A controlled gap or vibration check must show the expected matched-system response and stable monitor indication for 330101-00-40-05-02-05.
-
What should be retained in the handover record for 330101-00-40-05-02-05?Retain the 330101-00-40-05-02-05 label, installed gap, matched-system components, approval record and functional-test result.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
330101-00-40-05-02-05Product Details -
3300/50-02-01-00-00Product Details -
330910-00-05-10-02-00Product Details -
330101-00-16-10-02-05Product Details -
330101-00-20-90-02-05Product Details -
330101-00-49-90-12-05Product Details -
22810-00-10-10-02Product Details -
3500/15 106M1079-01Product Details -
81724-00-08-10-02Product Details -
330103-05-10-02-00Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.