Match the complete marking
Include 07EA61R1 GJV3074351R1 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered 07EA61R1 GJV3074351R1 reference with the installed equipment and applicable ABB documentation.
Technical specifications for 07EA61R1 GJV3074351R1
-
Manufacturer:ABB
-
Product Category:PLC Systems
-
Spare Part Number:07EA61R1 GJV3074351R1
-
Weight:0.48 kg
-
Analog input channels:8
-
Current signal range:4 to 20 mA
-
Conversion resolution:8 bit
-
ANAI U/I code:0
-
ANAI 8/12 code:1
-
ANAI normal raw EA:8 to 255
-
ANAI normal converted QA:0 to 4080
-
ANAI wire-break current:<3.6 mA
-
ANAI wire-break raw EA:<=2
-
ANAI wire-break ERR / QA:1 / 0
Information
- 07EA61 R1 current acquisition and ANAI conversion must be assessed together. The neighboring twelve-bit 07EA63 uses a different raw range and wire-break threshold; a shared 4–20 mA label does not preserve application interpretation.
Raw-to-process traceability: ANAI exposes received and converted values for diagnosing scaling before engineering-unit interpretation.
Fault-aware lower-end interpretation: The error state distinguishes a wire-break result from a valid low-end process value.
The applicable ANAI function-block call selects current mode with U/I = 0 and eight-bit conversion with 8/12 = 1. Its normal raw EA range is 8 to 255 and converted QA range is 0 to 4080. Compare those stages before changing the final engineering-unit scaling.
ANAI detects the documented 07EA61 wire-break condition below 3.6 mA when raw EA is 2 or less, setting ERR to 1 and QA to 0. A zero converted value can therefore have different meanings: inspect EA and ERR together, then verify the receiving application’s actual alarm response under an approved loop test.
07EA61R1 GJV3074351R1 Original Technical Reference Excerpt
Selected original manufacturer pages for the applicable interfaces and technical data. PDF · 3 pages · 418.1 KB.07EA61R1 GJV3074351R1 Installation & Commissioning Guide
ANAI Raw-Value, Conversion and Wire-Break Diagnosis. Follow the current loop through raw EA, converted QA and application alarm handling; use the 07EA61 eight-bit path rather than borrowing 07EA63 behavior. PDF · 2 pages · 92.6 KB.
Application scope: Separate hardware current acquisition, function-block conversion and final process scaling. The twelve-bit 07EA63 has a different conversion/diagnostic relationship.
Eight isolated current loops
Retain the transmitter-to-channel schedule and loop supply/return. Input isolation does not identify the process variable or establish transmitter power.Eight-bit ANAI conversion
Use current-mode and eight-bit selections for the 07EA61 path. Compare raw and converted values before altering engineering-unit scale.Wire-break alarm integration
Observe EA, QA and ERR together during the approved fault test. Verify how the application converts that error into its plant alarm.07EA63 migration review
Compare raw coding, resolution selection and wire-break threshold. A range match alone does not make the twelve-bit module a transparent change.
Locate the actual transmitter supply before moving current wiring.
Tag each process-variable channel and return path.
Do not land a voltage-output transmitter on a current channel by analogy.
Apply the plant loop-test procedure and respect the receiving circuit.
Use an authorized loop-fault test to observe raw EA, converted QA, ERR and the actual plant alarm separately.
Use the actual configured under-range/burnout behavior and documented test method.
Alternative Names
Technical notes
Conversion context: The displayed EA/QA and selector codes belong to the ANAI software call for 07EA61. They are not additional hardware conversion bits.
Zero with context: Use raw EA and ERR with QA: a valid lower-end value and an open-circuit result must not be interpreted from QA alone.
Timing boundary: ANAI execution times depend on the receiving CPU; they are not the sampling rate or conversion time of this input module.
FAQ View All FAQ
-
Why can QA be zero in two different situations with 07EA61R1 GJV3074351R1?The normal ANAI converted range starts at zero, while the documented wire-break path also forces QA to zero. Compare raw EA and ERR: an open-circuit result uses EA <= 2 and ERR = 1. Do not create a plant alarm from QA = 0 alone.
-
Which ANAI setting can disable the expected wire-break monitoring on 07EA61R1 GJV3074351R1?The monitoring described for the current-input path depends on U/I = 0. In voltage mode, U/I = 1, ERR remains zero for that monitoring function. Compare the retained call before attributing a missing alarm to failed hardware.
-
What should be compared if 07EA61R1 GJV3074351R1 receives the correct current but displays the wrong process magnitude?Observe raw EA, converted QA and final engineering units in sequence. Verify the eight-bit selector, U/I setting and downstream scale; the fault can lie in conversion/application interpretation rather than in the measured current loop.
-
Why is the twelve-bit 07EA63 not a transparent replacement for 07EA61R1 GJV3074351R1?The ANAI table gives 07EA61 a normal raw range of 8–255 and converted range of 0–4080; 07EA63 uses different coding and a different wire-break threshold. Review the block selection, scaling and alarms before approving migration.
-
Does ERR from the ANAI call for 07EA61R1 GJV3074351R1 directly prove the plant alarm operated?No. ERR is a function-block result. During an authorized loop-fault test, trace that result through the actual application interlocks, indications and alarm handling; record the block result and plant response separately.
-
Can the ANAI execution time be used as the input sampling rate of 07EA61R1 GJV3074351R1?No. The execution-time table refers to the function block on particular T200 CPUs. It does not specify this module’s acquisition or conversion rate; do not use it to qualify a fast measurement requirement.
-
How should the normal raw and converted ranges be used when testing 07EA61R1 GJV3074351R1?Apply approved current test points and observe both EA and QA before final scaling. The documented normal ranges are 8–255 and 0–4080; use the installation’s approved tolerance and avoid deriving an unlisted absolute accuracy from those codes.
-
What must be checked after the wire-break test on 07EA61R1 GJV3074351R1 is complete?Restore the valid loop and confirm raw and converted values recover, ERR returns to its valid operating state, and the application alarm/reset behavior follows the approved plant procedure. Retain channel identity and the before/after observations.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.