-
Match the complete marking
Include the full 1756-OF8 reference, hardware series, firmware label, RTB type and installed output configuration.
-
Check the offered item before ordering
Request label and connector photographs. Have your maintenance team compare the offered 1756-OF8 with the installed module and applicable Rockwell Automation ControlLogix analog I/O instructions.
Technical specifications for 1756-OF8
-
Manufacturer:Allen-Bradley
-
Product Category:PLC Systems
-
Spare Part Number:1756-OF8
-
Weight:0.35 kg
-
Tariff Code:8537101190
-
Output channels:8 voltage or current
-
Selectable output ranges:±10 V; 0–20 mA
-
Current resolution:15 bit across 21 mA; 650 nA/bit
-
Voltage resolution:15 bit across 10.4 V; 320 µV/bit
-
5.1 V backplane current:150 mA
-
24 V backplane current:210 mA
-
Backplane power:5.8 W
-
Voltage load:>2000 Ω
-
Current load:0–750 Ω
-
Resistive-load settling:<2 ms to 95% of final value
-
Calibrated accuracy at 25 °C:Better than 0.05% of range, 4–21 mA and −10.4 to +10.4 V
-
Typical calibration interval:12 months
-
Typical voltage offset drift:50 µV/°C
-
Typical current offset drift:0.1 µA/°C
-
Maximum voltage gain drift:25 ppm/°C
-
Maximum current gain drift:50 ppm/°C
-
Voltage module error:0.15% of range
-
Current module error:0.3% of range
-
Minimum scan, floating point:12 ms
-
Minimum scan, integer:8 ms
-
Output data formats:Integer; IEEE 32-bit floating point
-
Channel isolation:No individual output-channel isolation
-
Output-to-backplane insulation:250 V continuous, reinforced
-
Removable terminal blocks:1756-TBNH or 1756-TBSH
-
TBNH terminal torque:1.36 N·m
-
Operating ambient:0 to +60 °C
-
Storage temperature:−40 to +85 °C
-
Relative humidity:5–95%, non-condensing
Information
- Allen-Bradley 1756-OF8 links controller demand values to analog actuators and signal receivers. Correct operation depends on the selected data format, load circuit and transition behavior as well as the requested output magnitude.
Controlled output changes: Configured initialization and transition behavior determine how demand is applied after a state change.
Diagnostic feedback: Output echo and channel status help compare the module command path with the field response.
Communication format affects available functionality. In the Series A reference configuration, floating-point mode supports engineering-unit scaling, run-mode ramping and clamps with limit alarms. Integer mode retains selected program/fault transition and initialization functions but must not be assumed to offer every floating-point feature.
A command value, the module’s data echo and the physical actuator position represent different points in the control path. Commissioning must compare them under stable loading and during agreed program, fault and restart transitions. Hold-for-initialization can intentionally retain an output until the controller command matches the held value; this should be distinguished from a broken output circuit.
1756-OF8 Official Hardware and Operation Excerpt
Original English Series A reference wiring and ratings, plus output data-format, ramping, hold, clamping and data-echo behavior. PDF · 9 pages.1756-OF8 Installation & Verification Guide
Apter Power commissioning workbook for 1756-OF8, covering RTB mapping, load checks, project configuration and controlled state-transition testing. PDF · 5 pages.
Application scope: The technical ratings here concern the Series A reference arrangement. Evaluate hardware-series and software-profile compatibility, signal loading and grounding before applying the module to a new or modified installation.
Analog actuator commands
Drive supported current or voltage receivers after matching their burden and signal reference to the selected channel.Engineering-unit control
Use a supported floating-point configuration to relate controller engineering values to the intended analog endpoints.Managed state transitions
Apply the configured program, fault and initialization response as part of the approved process-control design.ControlLogix output replacement
Retain the exact RTB assignment, output type, project profile and operating-state behavior when restoring an installed channel.
Compare the actual module label and firmware with the installed project before relying on Series A reference values.
Trace each VOUT or IOUT circuit and the internally common RTN connections.
Include receivers, indicators and cable resistance in a current-loop burden assessment.
Confirm which ramping, scaling and clamp functions the selected data format supports.
Check agreed program, fault, restart and initialization behavior under the approved maintenance state.
Compare commanded output, echo/status and the connected receiver before restoring automatic control.
Revisions
Revision Part #
Also known as
Alternative Names
Technical notes
Open-circuit detection: Detection applies to current operation and requires an output above 0.1 mA. A zero-current command is not a reliable open-wire proving condition.
Initialization hold: The Series A reference behavior holds the output until the commanded value matches the held terminal value within 0.1% of full scale. Inspect InHold when an output appears unresponsive after a transition.
Terminal practices: 1756-TBNH permits at most two appropriately sized conductors per terminal; 1756-TBSH uses a single conductor per terminal. Apply the selected RTB’s wire-size and temperature requirements.
FAQ View All FAQ
-
Why might 1756-OF8 retain its old output after a return to Run mode?Hold for Initialization may be active. Check the channel InHold status and reconcile the controller command with the held output within the specified matching tolerance before treating the condition as a hardware failure.
-
Can an open-wire test at a zero-current command validate 1756-OF8?No. Current-mode open-circuit detection needs an output above 0.1 mA. Use an approved nonzero test condition and verify both channel status and the actual field circuit.
-
Why can a command above a configured limit produce no further change on 1756-OF8?In a supported floating-point configuration, clamping holds the terminal output at the configured boundary and can assert a limit alarm. Compare the demand, clamp settings and alarm status before altering the field device.
-
Can run-mode ramping be retained when 1756-OF8 is changed from floating-point to integer format?The Series A reference supports run-mode ramping only in floating-point mode. Review the feature set before changing communication format; program/fault ramping is a separate behavior.
-
Does data echo from 1756-OF8 prove that an actuator reached its demanded position?No. Echo represents the module output data and associated status, not independent actuator travel. Compare terminal signal and separate position or process feedback where the application requires it.
-
How should an additional recorder be assessed in a current loop driven by 1756-OF8?Include the recorder’s burden and wiring resistance with the other series loads. The Series A reference current-load ceiling is 750 Ω; verify adequate total burden margin and correct wiring before inserting the device.
-
Can separately grounded receivers create unwanted interactions on 1756-OF8?Yes, the RTN terminals are connected internally and the channels are not individually isolated. Review reference potentials and grounding before combining circuits; backplane isolation does not establish channel-to-channel isolation.
-
Why can the end-to-end response of 1756-OF8 exceed its analog settling specification?The settling figure concerns the analog output’s response into a resistive load. Module scan, requested packet interval, controller execution, configured ramps and the field device can add delays; test the complete path.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.











