Match the complete marking
Include MU-TLPA02 51309204-125 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered MU-TLPA02 51309204-125 with the installed equipment and applicable Honeywell documentation.
Technical specifications for MU-TLPA02 51309204-125
-
Manufacturer:Honeywell
-
Product Category:DCS Systems
-
Spare Part Number:MU-TLPA02 51309204-125
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
Connected FTAs:2 maximum in the documented configuration
-
Channels per FTA:16
-
System input capacity:32 channels with two FTAs
-
Maximum IOP-to-adapter cable:50 m
-
Maximum adapter-to-FTA cable:305 m
-
Adapter-side local cable connector:6 pins
-
FTA-side local cable connector:4 or 6 pins
-
Local cable construction:2 individually shielded twisted pairs
Information
- The 51309204-125 execution is the nonconformally coated CE-compliant adapter. The coated 51309204-175 execution and the older non-CE 51304467-100 have different assembly identities that must be checked before replacement.
Mixed input flexibility: Two connected FTAs can serve the same sensor type or combine RTD and thermocouple groups.
Remote field deployment: Separate processor-side and field-side cable limits support distributed temperature acquisition.
Processor-to-adapter connections use MU-KFTAxx for internal cabinet routes or shielded MU-KFTSxx for external cabinet routes. The longest processor-side run is limited to 50 m. CE installation additionally requires the specified shielded cable and a CE-compliant card file.
The field-side connection can extend to 305 m using the specified external cable. Local 51304465-xxx cabling uses individually shielded twisted pairs, with grounding at both ends for CE installations. The termination assemblies require their approved grounded enclosure and upright orientation.
Honeywell LLMux Configuration and Placement Excerpt
Original HPM Planning pages covering exact adapter identity, connected assemblies, placement and cable requirements.MU-TLPA02 51309204-125 Installation and Verification Guide
Cable selection, CE grounding, branch-level diagnosis and temperature-channel acceptance.
Application scope: Use it with the documented RTD and thermocouple LLMux assemblies. Preserve CE cable, cabinet and grounding conditions where the installation requires compliance.
RTD acquisition
Connect the documented MU-TAMR03 RTD FTA through the adapter to MU-PLAM02.Thermocouple acquisition
Use MU-TAMT03 for local cold-junction reference or MU-TAMT13 for the documented remote-reference arrangement.Mixed temperature inputs
One RTD and one thermocouple FTA can share the adapter when their assignments are configured correctly.Remote FTA installation
Apply the specified external cable and grounded enclosure when the field termination is remote from the processor cabinet.
Confirm that both termination and processor assemblies are LLMux components before disconnection.
Photograph the IOP-side and both FTA-side connections, labels and shield landings.
Include the complete installed processor-to-adapter cable in the 50 m limit.
Keep the longest adapter-to-FTA connection within 305 m using the specified cable.
For a CE installation, restore the specified shielded cable and both-end grounding of local FTA cables.
Confirm the grounded mounting channel, safety-ground connection and upright FTA installation before returning channels to service.
Alternative Names
Technical notes
Coating distinction: 51309204-125 is the nonconformally coated CE execution. The 51309204-175 assembly is the conformally coated execution.
Two independent distance checks: Apply the 50 m IOP-side limit and 305 m FTA-side limit to their respective cable routes.
CE installation relationship: The adapter identity alone does not establish compliance. Review the card file, cable selection, shielding and enclosure grounding together.
FAQ View All FAQ
-
Can MU-TLPA02 51309204-125 connect to an RHMUX termination assembly?The documented LLMux assemblies are compatible only with each other. Identify the IOP and FTA labels before approving a replacement because the RHMUX architecture uses different assemblies.
-
How should CE compliance be reviewed when replacing MU-TLPA02 51309204-125?Review the adapter execution together with the CE-compliant card file and specified MU-KFTSxx cable. Check shield and safety-ground connections against the approved installation.
-
Can MU-TLPA02 51309204-125 serve one RTD FTA and one thermocouple FTA?The two FTAs may be the same or different types. Record which branch serves RTDs and which serves thermocouples, then verify channel configuration and sensor response after reconnection.
-
Which cable distinction matters at the IOP side of MU-TLPA02 51309204-125?Internal cabinet routes use MU-KFTAxx, while external routes use shielded MU-KFTSxx. Check the actual cabinet boundary and compliance requirements before selecting a cable.
-
How does local cable shield grounding change for a CE installation of MU-TLPA02 51309204-125?For the specified 51304465-xxx local cable, CE applications ground shields at both ends. Non-CE applications ground them at the adapter end only. Record the installation basis before restoring the shield landings.
-
What should be checked when only one FTA branch fails behind MU-TLPA02 51309204-125?Compare the failed branch with the working branch using its connector, cable identity, shield landing and FTA configuration. Keep the two channel groups identified and use the approved I/O service procedure before disturbing connections.
-
Does replacing MU-TLPA02 51309204-125 change the thermocouple cold-junction reference arrangement?The FTA determines the reference arrangement. MU-TAMT03 uses a local reference and MU-TAMT13 uses the documented remote reference. Preserve that FTA identity and its reference wiring during adapter replacement.
-
What evidence should close replacement work on MU-TLPA02 51309204-125?Retain the complete adapter marking, IOP and FTA identities, cable-route lengths and shield connections. Verify representative sensor indications on both connected FTA groups against the accepted plant baseline.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
MU-TLPA02 51309204-125Product Details -
146056-38-10-02-02-05Product Details -
330903-00-11-10-01-CNProduct Details -
330104-06-14-10-02-00Product Details -
330101-00-10-10-01-05Product Details -
CC-PAIH02 51405038-376Product Details -
21504-00-24-10-02Product Details -
330102-00-80-10-01-05Product Details -
330102-00-85-10-01-05Product Details -
ICMK14F1 1SBP260050R1001Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.