Technical specifications for IS200TRTDH1CC
-
Manufacturer:General Electric
-
Product Category:Gas Turbine Control
-
Spare Part Number:IS200TRTDH1CC
-
Weight:0.5 kg
-
Tariff Code:8537101190
-
Field terminal positions:48
-
Terminal blocks:2
-
Positions per block:24
-
Processor connectors:2 x DC-37
-
RTD connection:3 wire
-
Supported VRTD RTD inputs:16
-
Maximum lead distance, stated conditions:300 m
-
Maximum two-way lead resistance:15 ohm
-
VRTD excitation:10 mA DC, pulsed
-
Maximum terminal conductor:12 AWG
-
Terminal-block retaining screws:2 per block
-
Hardware configuration jumpers:0
Information
- General Electric IS200TRTDH1CC retains the three-conductor sensor circuit through a simplex RTD termination, where shield routing and lead allocation directly affect temperature measurement.
Field construction: Two 24-position blocks terminate sixteen three-wire circuits.
Hardware settings: The TRTD board has no configuration jumpers.
Each sensor circuit carries its three wires to the terminal block so the VRTD measurement can compensate lead resistance. The two removable blocks each provide 24 positions, and their adjacent shield strips bond to the chassis. Keep lead identification with the sensor rather than inferring conductor function from a displayed temperature.
RTD conversion is configured in the processor; there are no TRTD jumpers to select a sensor curve. Grounded and ungrounded detectors are accommodated by the documented input method. Cable distance and two-way lead resistance are simultaneous constraints, so a cable shorter than the distance limit can still be unsuitable if its conductor resistance is excessive.
-
General Electric IS200TRTDH1CC official technical excerpt
Original GEH-6421H system-architecture pages for the VRTD/TRTD temperature path. PDF, 2 pages. -
General Electric IS200TRTDH1CC engineering guide
Apter Power field guide: three-wire restoration, terminal construction and shield verification. PDF, 2 pages.
Integration boundary: Sensor wiring, block retention and the chassis shield termination remain serviceable field interfaces separate from the processor configuration.
-
Three-wire detector replacement
Keep each detector and its compensation lead together when transferring bearing or process-temperature wiring. -
Shielded cabinet entry
Terminate the sensor-cable shields at the dedicated chassis strips, retaining the documented CE wiring arrangement where applicable. -
Block-level maintenance
Use the two removable terminal blocks to identify and restore sensor groups without confusing terminal count with detector count. -
Legacy platform retention
Retain the H1C-to-VRTD simplex path when a replacement is intended to preserve the existing Mark VI temperature system.
Confirm the two same-end RTD leads and the opposite element lead from the approved wiring record before disconnecting the block.
Each 24-position block is secured by two screws; seat the block fully before tightening and pulling on the harness.
Use conductors and terminations within the terminal acceptance up to #12 AWG, with no exposed strands bridging adjacent points.
For the documented CE arrangement use double-shielded cable, land all shields at the shield strip and do not terminate the shields at the end detector.
Check the actual two-way resistance, not just route length, before relying on the input compensation.
Inject or simulate each restored three-wire circuit and compare it with its configured channel before reconnecting all detectors.
Alternative Names
Technical notes
Excitation meaning: The connected RTD measurement uses pulsed, multiplexed 10 mA excitation. It is a measurement source rather than continuous transmitter loop power.
Shield versus signal: The chassis shield strip and sensor signal terminals have different functions; using a shield as a compensation conductor defeats the three-wire arrangement.
Temperature assignment: Choose the detector material and nominal-resistance curve in VRTD; terminal-board replacement does not select a universal temperature span.
FAQ View All FAQ
-
Does IS200TRTDH1CC require jumper changes when a Pt100 detector replaces another RTD type?TRTD has no sensor-selection jumpers. Review the VRTD characteristic and field detector wiring, then verify the conversion with a resistance appropriate to the newly selected curve.
-
Why can a loose compensation lead on IS200TRTDH1CC cause an error without an obviously open element?The processor relies on the three-wire relationship to compensate the leads. Check all three terminal connections and compare the lead resistances; continuity across the element alone leaves the compensation path untested.
-
Can a TMR rack cable set be transferred directly to IS200TRTDH1CC?H1C uses the simplex two-connector arrangement. Trace the actual R/S/T requirement before selecting a termination; the H1B redundant arrangement is a different connection topology.
-
What should be checked if one eight-channel group fails after servicing IS200TRTDH1CC?Inspect that group's block seating and processor cable before disturbing every detector. A common group connection failure can affect multiple otherwise intact sensor elements.
-
How can a shield-related temperature disturbance on IS200TRTDH1CC be investigated?Compare the cabinet shield-strip bond, detector-end termination and cable routing with the approved scheme. Correlate noise with nearby switching while keeping the measurement conductors separate from chassis/shield paths.
-
Why does a short cable not automatically satisfy IS200TRTDH1CC lead requirements?Conductor size and contact resistance can exceed the permitted two-way resistance before the route reaches its maximum distance. Measure the installed path and include connections in the result.
-
Can an RTD simulator prove all circuits on IS200TRTDH1CC through one terminal pair?A two-wire injection bypasses part of a three-wire field arrangement. Use an approved simulation connection that exercises the intended three conductors, then repeat for each assigned channel.
-
How is a credible wrong temperature after installing IS200TRTDH1CC distinguished from a failed terminal board?Compare channel assignment, detector curve and resistance at the terminals. A swapped sensor group or wrong linearization can produce a valid-looking value; controlled resistance points separate conversion/configuration errors from intermittent connections.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.