Speak to a sourcing specialist
sales13@apterpower.com

IS200VAICH1DBC

Analog Input/Output Processor Board
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

This VME processor converts Mark VI analog signals and serves two TBAI terminations. The H1D generation requires the later H1C-or-later terminal pairing, with a higher documented 20 mA load capability than the earlier VAIC generation.
  • Manufacturer part number
    IS200VAICH1DBC
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    2cm x 18.6cm x 26.1cm
  • Country of Origin
    USA
Get a quick price for IS200VAICH1DBC
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the full marking, quantity and label photos. We review the item and any version details that need clarification.
  • 1

    Confirm the offer

    Check the quoted reference, condition, included items and expected dispatch date before approving your order.
  • 2

    Arrange dispatch

    Confirm delivery details and receive the tracking number when it becomes available.
  • Match the complete marking

    Include IS200VAICH1DBC and every hardware or assembly-revision marking visible on the item. Keep the exact reference on your enquiry and quotation.
  • Check the offered item before ordering

    Request available label and interface photos. Have your maintenance team compare the offered IS200VAICH1DBC reference with the installed equipment and applicable General Electric documentation.

Technical specifications for IS200VAICH1DBC

  • Manufacturer:
    General Electric
  • Product Category:
    Gas Turbine Control
  • Spare Part Number:
    IS200VAICH1DBC
  • Weight:
    0.34 kg
  • Tariff Code:
    8537101190
  • Analog input capacity:
    20
  • Analog output capacity:
    4
  • TBAI terminations per processor:
    2
  • Normal input acquisition:
    100 Hz
  • Inputs 1-4 acquisition provision:
    200 Hz
  • ADC conversion:
    16 bit
  • Effective input resolution:
    14 bit
  • DAC resolution:
    12 bit
  • Input accuracy:
    Better than 0.1% full scale
  • Output accuracy:
    0.5%
  • 20 mA output load, matched generation:
    800 ohm
  • 200 mA output load:
    50 ohm
  • Healthy-current threshold setting:
    0-21 mA
  • Hardware diagnostic reset:
    RESET_DIA
  • System-limit reset:
    RESET_SYS

Information

Overview Downloads Applications / Compatibility Product Precautions
  • General Electric IS200VAICH1DBC performs analog conversion, channel validation and output regulation; its diagnostics distinguish an out-of-range field signal from a failed rack path.
Conversion role: Two terminal groups feed the rack processor.
Channel health: Hardware limits and configured system limits are separate tests.
Output supervision: Current feedback and range relays participate in diagnostic checking.
The H1D processing generation of IS200VAICH1DBC requires TBAIH1C-or-later or STAI, rather than the early TBAI/DTAI combination. Its increased output drive belongs to that matched pair. Retaining a compatible field termination is therefore part of selecting the processor, not a detail to be deferred until commissioning.

The normal acquisition path and the faster first-four-input provision serve different dynamics. Input range is selected at the terminal board, while engineering scaling and software filtering determine the controller value. Preserve the signal-source assignment before changing a filter; a slower configured response must not be diagnosed as loss of ADC resolution.

Fixed hardware checks remove an input from scanning when its electrical limits are exceeded. Configurable system limits instead provide application alarm behavior. The composite L3DIAG_VAIC identifies a board-level diagnostic condition; channel detail and the appropriate reset class are needed to decide whether the problem is wiring, configuration or conversion hardware.
Controller platform reference: GE Mark VI analog conversion. Retain the H1D terminal pairing.
Keep conversion configuration and the cause of each hardware/system limit with the rack replacement record.
Remove rack power

Follow the VME power-down procedure before inserting or removing the processor; the terminal isolation plan must also cover externally powered loops.

Restore both cable groups

Latch J3 and J4 to the recorded terminations and verify channel numbering across the group boundary.

Preserve range and units together

Load the approved electrical-range/scaling relationship before using displayed engineering values as a calibration result.

Use the correct reset class

Clear the cause first, then distinguish RESET_DIA for latched diagnostics from RESET_SYS for configured limit signals.

Check output feedback

Compare commanded current, measured load current and the reported drive status before changing current-range relay settings.

Assess redundant deviation

Investigate a rack that departs from the voted median even when the plant variable remains stable on the other paths.

Alternative Names

GE IS200VAICH1DBC General Electric IS200VAICH1DBC

Technical notes

Limit recovery: An input removed from scanning by a hardware check must regain valid electrical conditions before a reset is interpreted as successful recovery.

Healthy-current thresholds: Min_MA_Input and Max_MA_Input allow a configured healthy 4-20 mA band within the documented 0-21 mA setting range; these are diagnostic thresholds, not a transmitter calibration span.

Front-panel interpretation: Flashing green RUN, solid red FAIL and normally-off STATUS describe processor/diagnostic state. STATUS orange calls for channel-level investigation even if a process value remains available.

FAQ View All FAQ

  • Why does IS200VAICH1DBC remain in RUN while an analog input stops updating?
    A hardware-limit violation can remove one input from scanning without stopping the board. Read its individual diagnostic and actual electrical signal; clearing a process alarm alone will not restore an invalid input.
  • How can IS200VAICH1DBC distinguish a process alarm from an electrical-range fault?
    Compare the fixed hardware-limit result with the enabled high/low system limits and their latch settings. Record the input signal at the terminal so the alarm source is identified before either reset is issued.
  • What makes a TMR deviation diagnostic on IS200VAICH1DBC useful before total channel failure?
    A single signal can depart from the voted median while the remaining measurements sustain the controller value. Trend the individual rack against the vote and trace its input path instead of accepting the stable overall indication.
  • Why should IS200VAICH1DBC current-loop acceptance include more than the commanded value?
    The processor monitors converter/output feedback, total current, shutdown relays and range relays. Compare those states with a load-connected current measurement; a correct software command does not demonstrate drive continuity.
  • Can a filter change on IS200VAICH1DBC be used to repair a wrong transmitter range?
    Filtering changes dynamic response, while electrical selection and scaling establish amplitude. First inject a steady known signal and establish correct end points; only then evaluate the required filter response.
  • What should be checked if IS200VAICH1DBC reports a terminal-ID fault only on J4?
    Trace the second cable group and its termination identity independently of J3. Check connector seating and the expected terminal generation before disturbing the first ten inputs or replacing both terminations.
  • How are latched diagnostic and system-limit signals on IS200VAICH1DBC cleared differently?
    RESET_DIA addresses latched diagnostic signals and RESET_SYS addresses configured out-of-limit signals. Verify the originating condition has cleared and observe the corresponding signal, rather than repeatedly applying a general reset.
  • Why can IS200VAICH1DBC pass a static input test but differ during a pressure transient?
    The selected channel, acquisition provision, software filter and controller processing jointly determine response. Compare the time record with the saved pressure-channel configuration using a controlled dynamic stimulus; a static span check cannot establish bandwidth.