Speak to a sourcing specialist
sales13@apterpower.com

IC676PBI016-EA

Profibus Input Block
In Stock
Ships by Sunday, November 29
Fast Shipping Available
General Electric IC676PBI016-EA Profibus input block, angled view of M12 input ports
General Electric IC676PBI016-EA Profibus input block, rear view with black cover and screws
General Electric IC676PBI016-EA Profibus input block, close-up of label and M12 connectors
General Electric IC676PBI016-EA Profibus input block, angled view of M12 input ports
General Electric IC676PBI016-EA Profibus input block, rear view with black cover and screws
General Electric IC676PBI016-EA Profibus input block, close-up of label and M12 connectors
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

GE IC676PBI016-EA is a VersaMax IP 16-point digital input block for a PROFIBUS-DP slave station. It uses M12 bus, power and sensor connections and provides IP67 protection with module and sensor-supply diagnostics.
Get a quick price for IC676PBI016-EA
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for IC676PBI016-EA

  • Manufacturer:
    General Electric
  • Product Category:
    PLC Systems
  • Spare Part Number:
    IC676PBI016-EA
  • Estimated shipping dimensions:
    5.3x8.5x8.1cm
  • Weight:
    0.25 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Product family:
    VersaMax IP
  • Module function:
    16-point digital input module
  • Network role:
    PROFIBUS-DP slave
  • Bus connection:
    M12 BUS IN and BUS OUT connectors
  • Sensor connection:
    M12; supports 2-, 3- and 4-wire sensors
  • Nominal module voltage:
    24 VDC
  • Module supply range:
    18 to 30 VDC
  • Module-supply current at 24 VDC:
    35 mA typical; 100 mA maximum
  • Sensor-supply current at 24 VDC:
    8 mA typical plus sensor current; 1.2 A maximum
  • Input nominal voltage:
    24 VDC
  • Input permissible range:
    -30 VDC < UIN < +30 VDC
  • Input nominal current:
    3 mA
  • Switching thresholds:
    Low <5 V; high >11 V
  • Input delay:
    On <1 ms typical; off 2 ms typical
  • Sensor cable length:
    100 m maximum
  • Sensor current:
    75 mA nominal per channel; 1.2 A nominal per module
  • Protection:
    Electronic overload and short-circuit protection per module
  • Degree of protection:
    IP67 to IEC 60529
  • PROFIBUS baud rate:
    Up to 12 Mbaud with autobaud
  • Station address:
    1 to 99; a new setting is accepted at power-up
  • Process input data:
    16 bits in two bytes
  • PROFIBUS ID number:
    06FB hex
  • Diagnostic data:
    12 bytes to the PROFIBUS master
  • Indicators:
    BF, UL, US and sixteen input-status LEDs
  • Isolation test:
    500 VAC, 50 Hz for 1 minute
  • Operating temperature:
    -25 to +60 deg C
  • Storage temperature:
    -25 to +85 deg C
  • Operating/storage humidity:
    95%; slight short-term outer-housing condensation permitted
  • Complete order identity:
    IC676PBI016-EA
  • Base catalog number:
    IC676PBI016

Information

Overview Manuals Common Applications Product Precautions
GE IC676PBI016-EA is a VersaMax IP 16-point digital input block for a PROFIBUS-DP slave station. It uses M12 bus, power and sensor connections and provides IP67 protection with module and sensor-supply diagnostics.
  • Accepts sixteen 24 VDC digital input signals
  • Connects to PROFIBUS-DP through M12 bus connectors
  • Provides IP67 protection and M12 sensor connections
  • Reports bus, supply, overload and input-channel status

IC676PBI016-EA operates only in the documented GE VersaMax IP distributed I/O system position with its approved companion hardware and configuration.

Important Notice: Confirm the complete IC676PBI016-EA identity, installed interfaces, configuration and controlled acceptance results before commissioning.

GE IC676PBI016-EA Manuals & Downloads
GE IC676PBI016-EA Technical Reference (PDF)GE IC676PBI016-EA Installation & Commissioning Guide (PDF)

These documents are different: the first consolidates exact-model technical and engineering data; the second provides installation, connection and commissioning guidance.

Machine sensor collection
Collect sixteen discrete sensor states close to machine equipment through protected M12 connections.
IP67 distributed input stations
Install the module in a documented exposed-field arrangement where the specified IP67 sealing rules are maintained.
PROFIBUS-DP remote I/O
Exchange two bytes of cyclic input data with a PROFIBUS-DP master at the configured station address.
Field diagnostic monitoring
Use the BF, UL, US and channel LEDs together with the twelve-byte diagnostic telegram for controlled fault isolation.
Read the applicable GE instructions before work. Verify IC676PBI016-EA and every installed interface before isolation, wiring or commissioning.
1
Verify the full IC676PBI016-EA label and assigned PROFIBUS station before work.
2
Place the PROFIBUS master and connected machine process in the approved maintenance state.
3
Isolate the module and sensor supplies before disconnecting any M12 power or input cable.
4
Record the X10/X1 station address, BUS IN/OUT order, input assignments and current LED state.
5
Maintain the FE and shield connections and protect every opened M12 interface from contamination.
6
Confirm 18-30 VDC supply polarity and sensor loading before reconnecting the module.
7
Apply power only after setting the required 1-99 station address because changes are accepted at start-up.
8
Verify cyclic two-byte input data, all sixteen channel states and diagnostic telegrams before release.

Alternative Names

IC676PBI016 EA IC676PBI016EA GE IC676PBI016-EA

Technical notes

The -EA suffix is retained from exact product-label evidence; the functional and electrical data are taken from GE publication GFK-2293 for base catalog IC676PBI016. Do not assign undocumented suffix-specific electrical differences. Set the 1-99 station address before power-up, preserve FE shielding and cap every unused connector required for IP67 protection.

FAQ View All FAQ

  • How should the full IC676PBI016-EA identity be handled during replacement?
    Retain the complete IC676PBI016-EA order identity from the product label. Apply GFK-2293 functional data to base catalog IC676PBI016, but do not infer an undocumented electrical meaning for the -EA suffix.
  • When does IC676PBI016-EA accept a newly selected PROFIBUS station address?
    Set the X10 and X1 rotary switches to an address from 1 to 99 before energizing the module; GFK-2293 states that a new address is accepted only at power-up.
  • What does the BF LED indicate on the IC676PBI016-EA input block?
    A red BF indication can mean no cyclic data exchange, a missing PROFIBUS connection, an offline master, an address or configuration mismatch, synchronization or parameterization activity, or an expired timeout.
  • How does IC676PBI016-EA report a sensor-supply overload or short circuit?
    The module electronically switches off the affected sensor supply and sends diagnostic information to the PROFIBUS master; diagnostic byte 7 also reports sensor-supply undervoltage and overload status.
  • What network hardware rule applies above 3 Mbaud for IC676PBI016-EA?
    The PROFIBUS interface supports up to 12 Mbaud, but GFK-2293 requires T-pieces with integrated series inductance when the transmission rate is above 3 Mbaud.
  • How is IP67 protection maintained on IC676PBI016-EA?
    Connect functional earth as specified, tighten the M12 bus, power and sensor connections, and fit the documented male or female protective caps to every unused connector.
  • How are the sixteen IC676PBI016-EA inputs represented in cyclic process data?
    The module returns 16 bits in two input bytes: byte 0 carries inputs 16 through 9 and byte 1 carries inputs 8 through 1 in the documented bit order.
  • Which electrical checks belong in IC676PBI016-EA commissioning?
    Confirm an 18-30 VDC module supply, correct polarity, sensor-supply loading within 75 mA per channel and 1.2 A per module, and input switching consistent with low below 5 V and high above 11 V.