Speak to a sourcing specialist
sales13@apterpower.com

IS220STAIH2A

Analog Input Terminal Board
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

GE IS220STAIH2A is a analog input terminal board for GE Mark VIe analog-input system.
  • Manufacturer part number
    IS220STAIH2A
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    25cm x 20cm x 10cm
  • Country of Origin
    USA
Get a quick price for IS220STAIH2A
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the complete IS220STAIH2A marking, installed-position photographs and required quantity.

  • 1

    Confirm the offer

    Confirm the offered revision, condition, included items and documented system fit in the quotation.

  • 2

    Arrange dispatch

    Agree quantity, dispatch date and delivery details in the quotation.

  • Match the complete marking

    Include IS220STAIH2A and any visible revision or assembly number on the enquiry and quotation.

  • Check the offered item before ordering

    Request available label and connector or terminal photos. Have your maintenance team compare the offered IS220STAIH2A with the installed equipment and applicable GE documentation.

Technical specifications for IS220STAIH2A

  • Manufacturer:
    General Electric
  • Product Category:
    Gas Turbine Control
  • Spare Part Number:
    IS220STAIH2A
  • Weight:
    0.56 kg
  • Tariff Code:
    8537101190
  • Board function:
    Analog input termination
  • Assembly relationship:
    IS230SNAIH2A
  • Companion I/O pack:
    PAICH1B
  • Control family:
    Mark VIe / EX2100e
  • Signal role:
    Field analog input routing
  • Application arrangement:
    Simplex assembly
  • Replacement basis:
    Terminal map and connector identity

Information

Overview Downloads Applications / Compatibility Product Precautions
  • Within the GE Mark VIe analog-input system arrangement, IS220STAIH2A performs its documented paich1b role and must be matched by complete marking.
Separated hardware roles: Field termination remains on the board while acquisition and communications remain with the companion pack.
Analog-loop traceability: Terminal numbering, loop type, polarity and shielding are preserved for every configured channel.
Calibrated verification: Controlled signal injection confirms the restored controller reading against an accepted instrument.
IS220STAIH2A is the field-termination element associated with a PAICH1B analog I/O pack in the IS230SNAIH2A Mark VIe module. It routes installed analog loops to the companion pack.

The terminal board preserves channel termination, common references and field wiring, while the pack performs acquisition and network communication. These two hardware roles should not be conflated during selection.

Record terminal numbering, loop type, polarity, shielding and connector orientation before removal. Recommission with controlled signal injection and compare controller readings against the approved channel baseline.
Controller platform reference: GE Mark VIe analog-input system. Follow the approved system drawing and manufacturer procedure for installation and commissioning.
Product references for GE IS220STAIH2A: a technical identity reference and a separate installation and verification guide.
The separate technical reference and field guide provide product identity and controlled service information for IS220STAIH2A.
Prepare GE IS220STAIH2A for its configured installation using these checks.
Confirm the full marking

Match IS220STAIH2A and every visible revision or assembly identifier.

Preserve the as-found map

Record connectors, terminals, orientation and companion hardware before removal.

Apply the approved isolation

Use the complete system maintenance procedure and prove the required isolation.

Protect the hardware

Use ESD control and prevent mechanical load on connectors or board surfaces.

Restore configuration deliberately

Reapply only the approved installed settings, wiring and application records.

Retain acceptance evidence

Keep label photographs, test results, deviations and responsible sign-off.

Alternative Names

GE IS220STAIH2A IS220STAIH2A Analog Input Terminal Board

Technical notes

Installation relationship: IS220STAIH2A belongs to the configured GE Mark VIe analog-input system hardware chain; the complete installed relationship governs replacement.

Protection: Follow the approved isolation, ESD and system-specific commissioning procedure before handling IS220STAIH2A.

Technical reference: GEH-6781L EX2100e I/O module relationship and exact-model industrial records. STAIH2A is the analog-input terminal-board element paired with PAICH1B in the IS230SNAIH2A module; pack-level conversion and network functions remain with PAICH1B.

FAQ View All FAQ

  • How should the PAICH1B relationship be confirmed for IS220STAIH2A?
    Verify the companion PAICH1B I/O pack and the IS230SNAIH2A assembly relationship from the installed marking and drawing. Record pack, terminal-board and connector identities together.
  • What signal information must be captured before replacing IS220STAIH2A?
    Record each terminal number, channel assignment, signal type, loop-power arrangement, polarity and field-device tag. Do not infer a common analog input configuration for all connected points.
  • How should shields and returns be restored on IS220STAIH2A?
    Follow the approved loop drawing for shield termination, signal return and protective earth. Avoid creating a second ground path when the board or field wiring is reconnected.
  • Why is terminal numbering critical when servicing IS220STAIH2A?
    The terminal board is the physical mapping between field conductors and controller channels. Photograph numbering and conductor tags so the same field loop returns to the same logical input.
  • What simplex boundary applies to IS220STAIH2A?
    Treat the installed IS220STAIH2A path as the documented simplex terminal arrangement. Redundant behavior or alternative terminal hardware must be proven by the project design rather than assumed from the Mark VIe family.
  • How can a field-loop problem be separated from an IS220STAIH2A fault?
    Check field-device output, loop power, terminal continuity, PAICH1B diagnostics and controller indication in sequence. Use a calibrated source at the approved point to locate the break in the measurement path.
  • How should IS220STAIH2A channels be calibrated or verified?
    Inject controlled values appropriate to each documented signal type, compare the controller reading and record error at the selected test points. Do not apply one test range to channels configured for different inputs.
  • What acceptance evidence is required for IS220STAIH2A?
    Retain the terminal map, companion-pack identity, loop-power and shield checks, injected values, controller readings and final channel diagnostics for every used input.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.