Product Describe:

GE IS200STTCH2A is a Mark VIe thermocouple terminal board used with a specified input pack. It provides field termination for thermocouple measurement channels in the approved assembly.
  • Manufacturer part number
    IS200STTCH2A
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    2cm x 18.6cm x 26.1cm
  • Country of Origin
    USA
Get a quick price for IS200STTCH2A
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the complete IS200STTCH2A marking, installed I/O-pack suffix, channel drawing and required quantity.

  • 1

    Confirm the offer

    Confirm revision, condition, included items and thermocouple-channel requirements in the written quotation.

  • 2

    Arrange dispatch

    Agree quantity, dispatch date and delivery details in the quotation.

  • Match the complete marking

    Match the complete IS200STTCH2A terminal-board marking with the installed thermocouple input assembly. Verify the companion I/O pack, board revision and field termination against the as-built drawing.

  • Check the offered item before ordering

    Request full-label and termination photographs. Compare the exact offered board, condition and included items with the approved channel configuration before ordering.

Technical specifications for IS200STTCH2A

  • Manufacturer:
    General Electric
  • Product Category:
    Gas Turbine Control
  • Spare Part Number:
    IS200STTCH2A
  • Weight:
    0.3 kg
  • Tariff Code:
    8537101190
  • Function:
    Thermocouple field termination
  • Published I/O-pack pairing:
    IS220PTCCH1B
  • Pack input, paired assembly:
    28 V DC; 0.16 A maximum
  • Thermocouple signal, paired assembly:
    −8 to +45 mV DC
  • Field output voltage Uo:
    0.5 V DC
  • Field output current Io:
    25 nA
  • Field output power Po:
    13 nW
  • External capacitance Co:
    1000 µF
  • External inductance Lo:
    100 mH
  • Certified ambient, paired assembly:
    −30 to +65 °C

Information

Overview Downloads Applications / Compatibility Product Precautions
  • IS200STTCH2A belongs to the Mark VIe thermocouple input chain. The terminal board and the matched I/O pack must be identified separately when maintaining a temperature-measurement channel.
Signal role: The board terminates thermocouple field circuits for the matched input pack.
Measurement integrity: Sensor type, polarity and channel assignment govern the reading.
Selection boundary: Confirm complete board and I/O-pack suffixes before exchange.
GE Vernova identifies IS200STTCH2A as a terminal-board option for the Mark VIe thermocouple input pack. The published assembly uses a 28 V DC, 0.16 A maximum pack input; that value belongs to the I/O pack, not to the passive terminal board by itself.

The published thermocouple signal range is −8 to +45 mV DC for the specified pack-and-board assembly. It must not be read as a universal temperature range because thermocouple type, compensation and configuration determine the engineering units.

The certified terminal-board field interface has very low energy output limits. Retain the approved field-wiring design, sensor polarity and channel mapping; recheck the complete measurement chain after changing the board.
Controller platform reference: GE Mark VIe thermocouple input system. Confirm the installed pack, sensor types and approved channel drawings.
A GE-sourced technical reference identifies the IS200STTCH2A terminal-board role and published thermocouple circuit limits. A separate guide covers as-found wiring and controlled replacement.
The technical reference and field guide are separate Apter Power resources. Check the installed thermocouple input design and applicable GE instructions before a change.
Prepare GE IS200STTCH2A for its configured installation using these checks.
Isolate the measurement circuit

Follow the approved maintenance state before lifting thermocouple conductors.

Record sensor polarity

Photograph positive and negative conductor positions and channel markers.

Preserve sensor type

Do not change thermocouple type or compensation settings during a board swap.

Protect low-level signals

Maintain the approved shielding, routing and separation from power wiring.

Check companion pack

Confirm the fitted pack suffix and approved terminal-board combination.

Prove every changed channel

Compare reading and diagnostics with a known source or accepted machine baseline.

Alternative Names

GE IS200STTCH2A thermocouple terminal board GE Mark VIe IS200STTCH2A field termination board

Technical notes

Signal boundary: The mV range describes the GE listed thermocouple input assembly.

Power boundary: The 28 V DC pack input is not a board-only supply specification.

Field energy: Published low-energy output parameters apply to the certified terminal-board circuit.

Configuration: Sensor type, polarity and channel mapping must match the installed project records.

FAQ View All FAQ

  • Why must the I/O-pack suffix be checked with IS200STTCH2A?
    The published ratings describe an assembled input channel. Compare the board and pack markings with the approved system drawing before ordering.
  • How should thermocouple polarity be preserved when replacing IS200STTCH2A?
    Photograph the positive and negative field conductors and channel labels before disconnection, then compare the restored reading with the accepted baseline.
  • Does the millivolt range of IS200STTCH2A specify a temperature range?
    No. The listed −8 to +45 mV is an electrical input range for the paired system; the temperature scale also depends on sensor type and configuration.
  • Can the 28 V DC figure be applied to IS200STTCH2A alone?
    No. The 28 V DC, 0.16 A maximum rating is assigned to the companion input pack in the published assembly.
  • What field-energy limits should be checked for IS200STTCH2A?
    Compare the published Uo, Io, Po, Co and Lo values with the approved field circuit and its complete certification documentation.
  • How can a channel mismatch after installing IS200STTCH2A be isolated?
    Check conductor polarity, channel mapping, sensor type and pack diagnostics before attributing the mismatch to the board.
  • What shielding check is useful for IS200STTCH2A thermocouple wiring?
    Restore the approved shield termination and separation from high-energy wiring, then compare noise and stable readings against the prior baseline.
  • What acceptance record should follow an IS200STTCH2A exchange?
    Retain label and wiring photographs, input-pack identity, changed-channel readings, diagnostics and responsible sign-off.