Product Describe:

GE 8617-FT-NI is the non-incendive PAC8000 field terminal used beneath a compatible 16-channel digital-input module. It provides the field-wiring landing and mechanical interface while the removable I/O module carries channel electronics.
  • Manufacturer part number
    8617-FT-NI
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    8.8cm x 4.1cm x 4.2cm
  • Country of Origin
    USA
Get a quick price for 8617-FT-NI
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the full marking, quantity and label photos. We review the item and any version details that need clarification.
  • 1

    Confirm the offer

    Check the quoted reference, condition, included items and expected dispatch date before approving your order.
  • 2

    Arrange dispatch

    Confirm delivery details and receive the tracking number when it becomes available.
  • Match the complete marking

    Include 8617-FT-NI and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation.
  • Check the offered item before ordering

    Request available label and interface photos. Have your maintenance team compare the offered 8617-FT-NI reference with the installed equipment and applicable General Electric documentation.

Technical specifications for 8617-FT-NI

  • Manufacturer:
    General Electric
  • Product Category:
    PLC Systems
  • Spare Part Number:
    8617-FT-NI
  • Weight:
    0.08 kg
  • Tariff Code:
    8537101190
  • Component role:
    Non-incendive field terminal
  • Compatible I/O position:
    16-channel digital input
  • Mounting system:
    PAC8000 DIN-rail I/O carrier arrangement
  • Module service feature:
    Hot swap supported by the PAC8000 family when site procedure permits
  • Family operating temperature:
    -40 to +70 deg C
  • Family shock withstand:
    30 g
  • Family vibration withstand:
    5 g
  • Family area context:
    Class I Division 2 / Zone 2 system options

Information

Overview Downloads Applications / Compatibility Product Precautions
  • The FT-NI identity is the decisive feature: hazardous-area wiring practice, terminal position and mating module must match the PAC8000 node drawing before the base is installed.
Terminal identity: 8617 FT-NI non-incendive base for a 16-channel digital-input position.
Architecture role: Field conductors land on the terminal while the I/O electronics remain in the mating module.
Area boundary: Apply only with the approved PAC8000 module, carrier and hazardous-area drawing.
The field terminal preserves wiring when the removable module is serviced. Terminal numbering and channel assignment must therefore be recorded independently from the module label.

Non-incendive suitability belongs to the complete installed combination and wiring method. The FT-NI marking alone does not approve an arbitrary module or field circuit.

PAC8000 hot-swap capability is a system feature, but removal remains subject to the site area classification, energy-control procedure and approved module instructions.
Controller platform reference: PAC8000 distributed process-I/O node. Verify terminal map, mating-module identity, contact condition and every digital-input state before returning the node to service.
Technical downloads for General Electric 8617-FT-NI: model-specific technical reference and installation review.
Use the exact order code and installed configuration when applying either document.
Prepare General Electric 8617-FT-NI using the approved machine documentation and site procedure.
Do not treat the terminal as an I/O module

It contains the field interface; channel electronics and ratings belong to the mating module.

Verify exact module compatibility

Use the PAC8000 16-channel DI position documented for the FT-NI base.

Preserve channel labels

Record every conductor before disturbing the removable module or terminal block.

Apply area procedure

Non-incendive work still requires the approved hazardous-location method.

Inspect mating contacts

Reject bent, contaminated or heat-damaged contacts between module and base.

Control shield and common routing

Follow the cabinet drawing rather than inferring connections from adjacent terminal types.

Alternative Names

General Electric 8617-FT-NI non-incendive field terminal for digital input module PAC8000 process I/O field-terminal family 8617-FT-NI

Technical notes

Terminal proof: Check numbering, screw condition, conductor retention and separation from adjacent circuits.

Compatibility proof: Record the mating I/O module article and carrier position.

Channel proof: Exercise each discrete input and compare field state, module indication and controller value.

FAQ View All FAQ

  • What is 8617-FT-NI?
    It is a PAC8000 non-incendive field terminal for a compatible 16-channel digital-input position.
  • Is 8617-FT-NI the digital-input electronics module?
    No. It is the field-wiring base; the removable mating module contains the I/O electronics.
  • Where is 8617-FT-NI mounted?
    It installs in the PAC8000 DIN-rail carrier arrangement at the documented I/O position.
  • Can 8617-FT-NI be used with any PAC8000 module?
    No. Verify the exact 16-channel DI module and carrier compatibility.
  • Does 8617-FT-NI alone establish hazardous-area approval?
    No. Approval depends on the complete system combination and approved wiring method.
  • What must be photographed on 8617-FT-NI?
    Capture full marking, terminal numbering, conductor positions and mating contacts.
  • Can the mating module above 8617-FT-NI be hot-swapped?
    PAC8000 supports hot swap in the family, but only under the site-approved area and maintenance procedure.
  • How is 8617-FT-NI accepted after wiring?
    Exercise all 16 inputs and reconcile terminal state, module indication and controller value.