Match the complete marking
Include 8617-FT-NI and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered 8617-FT-NI reference with the installed equipment and applicable General Electric documentation.
Technical specifications for 8617-FT-NI
-
Manufacturer:General Electric
-
Product Category:PLC Systems
-
Spare Part Number:8617-FT-NI
-
Weight:0.08 kg
-
Tariff Code:8537101190
-
Component role:Non-incendive field terminal
-
Compatible I/O position:16-channel digital input
-
Mounting system:PAC8000 DIN-rail I/O carrier arrangement
-
Module service feature:Hot swap supported by the PAC8000 family when site procedure permits
-
Family operating temperature:-40 to +70 deg C
-
Family shock withstand:30 g
-
Family vibration withstand:5 g
-
Family area context:Class I Division 2 / Zone 2 system options
Information
- The FT-NI identity is the decisive feature: hazardous-area wiring practice, terminal position and mating module must match the PAC8000 node drawing before the base is installed.
Architecture role: Field conductors land on the terminal while the I/O electronics remain in the mating module.
Area boundary: Apply only with the approved PAC8000 module, carrier and hazardous-area drawing.
Non-incendive suitability belongs to the complete installed combination and wiring method. The FT-NI marking alone does not approve an arbitrary module or field circuit.
PAC8000 hot-swap capability is a system feature, but removal remains subject to the site area classification, energy-control procedure and approved module instructions.
-
General Electric 8617-FT-NI official technical excerpt
Selected manufacturer pages covering the applicable family, technical data and exact order-code fields. -
General Electric 8617-FT-NI engineering guide
Apter Power installation, configuration, diagnostic and acceptance guidance.
Platform applications: The uses below require the documented PAC8000 distributed process-I/O node companion components and approved machine drawing.
-
PAC8000 digital-input marshalling
Land 16 discrete field circuits according to the exact channel and common arrangement. -
Non-incendive Zone 2 node
Use only where the selected module, carrier and field wiring appear on the approved control drawing. -
Module maintenance base
Retain field conductors while exchanging the compatible I/O electronics under the authorized procedure. -
Remote process-I/O cabinet
Mount on the specified DIN-rail carrier with accessible channel labels and segregation.
It contains the field interface; channel electronics and ratings belong to the mating module.
Use the PAC8000 16-channel DI position documented for the FT-NI base.
Record every conductor before disturbing the removable module or terminal block.
Non-incendive work still requires the approved hazardous-location method.
Reject bent, contaminated or heat-damaged contacts between module and base.
Follow the cabinet drawing rather than inferring connections from adjacent terminal types.
Alternative Names
Technical notes
Terminal proof: Check numbering, screw condition, conductor retention and separation from adjacent circuits.
Compatibility proof: Record the mating I/O module article and carrier position.
Channel proof: Exercise each discrete input and compare field state, module indication and controller value.
FAQ View All FAQ
-
What is 8617-FT-NI?It is a PAC8000 non-incendive field terminal for a compatible 16-channel digital-input position.
-
Is 8617-FT-NI the digital-input electronics module?No. It is the field-wiring base; the removable mating module contains the I/O electronics.
-
Where is 8617-FT-NI mounted?It installs in the PAC8000 DIN-rail carrier arrangement at the documented I/O position.
-
Can 8617-FT-NI be used with any PAC8000 module?No. Verify the exact 16-channel DI module and carrier compatibility.
-
Does 8617-FT-NI alone establish hazardous-area approval?No. Approval depends on the complete system combination and approved wiring method.
-
What must be photographed on 8617-FT-NI?Capture full marking, terminal numbering, conductor positions and mating contacts.
-
Can the mating module above 8617-FT-NI be hot-swapped?PAC8000 supports hot swap in the family, but only under the site-approved area and maintenance procedure.
-
How is 8617-FT-NI accepted after wiring?Exercise all 16 inputs and reconcile terminal state, module indication and controller value.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.