Match the complete marking
Include IS200TBAIH1CDD and every hardware or assembly-revision marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered IS200TBAIH1CDD reference with the installed equipment and applicable General Electric documentation.
Technical specifications for IS200TBAIH1CDD
-
Manufacturer:General Electric
-
Product Category:Gas Turbine Control
-
Spare Part Number:IS200TBAIH1CDD
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
Analog inputs:10
-
Analog outputs:2
-
Processor connectors:3 x DC-37
-
Current input selections:4-20 mA; +/-1 mA
-
Voltage input selections:+/-5 V; +/-10 V
-
Output 1 selections:0-20 mA; 0-200 mA
-
Output 2 range:0-20 mA
-
20 mA load, matched later generation:800 ohm
-
200 mA load:50 ohm
-
Transducer supply current:21 mA continuous per connection
-
Transducer supply voltage:24 V DC
-
Available later-generation output drive:Up to 18 V at terminals
Information
- General Electric IS200TBAIH1CDD separates field-loop conditioning from rack conversion, allowing the terminal settings to be checked before a VAIC channel is condemned.
Loop selection: Current/voltage jumpers must agree with the transmitter circuit.
Redundant wiring: JR1, JS1 and JT1 carry separate processor paths.
The transmitter input type is established at the termination. Eight inputs per TBAI provide voltage or 4-20 mA selection, while two additional circuits support 4-20 mA or the low-current range. The field source, its power arrangement and the terminal jumper must be reconciled before software scaling is applied; changing engineering units cannot correct the wrong electrical input circuit.
In simplex service JR1 provides the rack connection. TMR adds JS1 and JT1, distributes each input to the three VAICs, and diode-ORs transducer power from the racks. The current outputs use processor feedback and median-current operation, so measuring only one disconnected processor leg does not establish the complete loop output.
-
General Electric IS200TBAIH1CDD official technical excerpt
Original GEH-6421H system-architecture pages for the VAIC/TBAI analog path. PDF, 3 pages. -
General Electric IS200TBAIH1CDD engineering guide
Apter Power field guide: transmitter branches, output compliance and terminal-ID diagnosis. PDF, 2 pages.
Integration boundary: One terminal group occupies one processor-cable destination; a full VAIC allocation uses two groups with separately configured channel ranges.
-
Powered transmitter termination
Use the terminal-supplied 24 V circuit only for a transmitter whose consumption fits the individual supply limit. -
Externally powered analog inputs
Preserve the source return and the selected current/voltage circuit; an external supply must not be treated as the terminal excitation source. -
High-burden output loops
Evaluate receiver resistance plus installed wire resistance against the matched later-generation output drive. -
TMR analog distribution
Keep R, S and T cable identities distinct so rack diagnostics can be traced to the correct terminal connection.
Isolate external transmitter supplies as well as the rack before disturbing the TBAI terminals.
Save the actual jumper positions by channel, distinguishing the eight general inputs from the two low-current-capable inputs.
Verify the selectable first output independently of the second 20 mA output before attaching a receiver.
Identify signal return and transducer power return before moving conductors; a correct signal number does not establish its return path.
Seat and latch each DC-37 connection in its recorded JR1/JS1/JT1 location without transferring cable load to the connector.
Measure actual current with the receiver connected and compare it with command and channel feedback before removing the isolation.
Alternative Names
Technical notes
Transducer power: The 21 mA continuous limit applies to an individual transducer-supply connection, not to the selectable 200 mA analog output.
Burden calculation: An 800 ohm receiver at 20 mA uses 16 V. The later pair provides up to 18 V at the terminals; wire and connection losses must remain within the available margin.
Terminal identification: The read-only ID includes board type, revision, serial identity and connector location, allowing a cable-location mismatch to be distinguished from a bad transmitter.
FAQ View All FAQ
-
Why can IS200TBAIH1CDD report hardware incompatibility after a cable exchange?VAIC interrogates the termination ID and connector location. Compare the diagnosed JR/JS/JT location with the cable labels and rack destination before replacing an analog component.
-
How can the current-conversion path of IS200TBAIH1CDD be checked without changing engineering scaling?For the documented 4-20 mA circuit, the 250 ohm conversion resistor gives 1-5 V across that path. With the loop isolated for the approved test, compare injected current and the corresponding conversion voltage before adjusting software scale; a wrong electrical selection cannot be corrected by changing displayed units.
-
How should a current input on IS200TBAIH1CDD be tested when a voltage source gives a plausible reading?Identify whether the channel uses the current-conversion circuit or the voltage circuit, then inject the intended electrical quantity with the loop isolated. A plausible scaled value from the wrong source is not an input-type acceptance test.
-
Why can one rack lose a measurement through IS200TBAIH1CDD while the other two remain healthy?In TMR the three processor-cable paths are separate even though the field signal is shared. Compare rack-specific readings and the affected cable connection before opening the common field loop.
-
What does a transducer-supply short on IS200TBAIH1CDD mean for output troubleshooting?Treat the protected transmitter supply separately from current-output regulation. Check the transmitter branch for a short and verify the receiver loop independently rather than assuming both use the same current limit.
-
How can IS200TBAIH1CDD be accepted with an externally powered transmitter?Confirm the approved common/return relationship and electrical range, then exercise the transmitter or an isolated source at low, middle and high points. Record both the physical signal and the VAIC engineering value.
-
Why can TMR output current through IS200TBAIH1CDD differ from a measurement on one processor leg?The connected output is formed by the redundant drive and feedback arrangement. Evaluate the actual field-loop current and the individual VAIC diagnostics together; a disconnected leg is not a representative load condition.
-
What should be recorded if IS200TBAIH1CDD develops a range-dependent error?Capture the selected input/output circuit, actual source or receiver value, field-loop loading and corresponding rack reading at several points. A repeatable gain error calls for range/scaling review, whereas a load-dependent output collapse calls for loop-burden investigation.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
IS200TBAIH1CDDProduct Details -
531X303MCPBCG1Product Details -
8121-DI-DC-01Product Details -
DS200SLCCG1AFGProduct Details -
8617-FT-NIProduct Details -
DS200SLCCG1ACCProduct Details -
DS200PCCAG8ACBProduct Details -
DS200PCCAG7ACBProduct Details -
IS200TBTCH1CBBProduct Details -
DS200SLCCG1AEEProduct Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.