Product Describe:

GE IS200PAICH1B is a analog input and output board for GE Mark VIe analog I/O system.
  • Manufacturer part number
    IS200PAICH1B
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    20cm x 15cm x 10cm
  • Country of Origin
    USA
Get a quick price for IS200PAICH1B
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the complete IS200PAICH1B marking, installed-position photographs and required quantity.

  • 1

    Confirm the offer

    Confirm the offered revision, condition, included items and documented system fit in the quotation.

  • 2

    Arrange dispatch

    Agree quantity, dispatch date and delivery details in the quotation.

  • Match the complete marking

    Include IS200PAICH1B and any visible revision or assembly number on the enquiry and quotation.

  • Check the offered item before ordering

    Request available label and connector or terminal photos. Have your maintenance team compare the offered IS200PAICH1B with the installed equipment and applicable GE documentation.

Technical specifications for IS200PAICH1B

  • Manufacturer:
    General Electric
  • Product Category:
    Gas Turbine Control
  • Spare Part Number:
    IS200PAICH1B
  • Weight:
    0.35 kg
  • Tariff Code:
    8537101190
  • Board function:
    Analog input and output
  • Analog inputs:
    10
  • Analog outputs:
    2
  • Output range:
    0–20 mA
  • Control family:
    Mark VIe
  • Signal role:
    Field analog I/O interface
  • Hardware identity:
    PAICH1B

Information

Overview Downloads Applications / Compatibility Product Precautions
  • Within the GE Mark VIe analog I/O system arrangement, IS200PAICH1B performs its documented 2 role and must be matched by complete marking.
Mixed-signal coordination: Connects configured analog sensing and command loops with the Mark VIe controller.
Channel-map discipline: Signal type, loop power, polarity and terminal assignment remain part of the installed identity.
Bidirectional verification: Acceptance combines calibrated input injection with controlled output checks.
IS200PAICH1B is identified as the Mark VIe analog I/O hardware providing ten analog inputs and two analog outputs. It connects configured field loops with the controller through the installed termination arrangement.

Input type, output range, loop power and terminal assignment depend on the companion hardware and application configuration. The full channel map therefore remains part of the replacement identity.

Before removal, capture channel assignments, signal types, polarity, shielding and baseline readings. Recommission with controlled input injection and output checks while comparing controller values with calibrated instruments.
Controller platform reference: GE Mark VIe analog I/O system. Follow the approved system drawing and manufacturer procedure for installation and commissioning.
Product references for GE IS200PAICH1B: a technical identity reference and a separate installation and verification guide.
The separate technical reference and field guide provide product identity and controlled service information for IS200PAICH1B.
Prepare GE IS200PAICH1B for its configured installation using these checks.
Confirm the full marking

Match IS200PAICH1B and every visible revision or assembly identifier.

Preserve the as-found map

Record connectors, terminals, orientation and companion hardware before removal.

Apply the approved isolation

Use the complete system maintenance procedure and prove the required isolation.

Protect the hardware

Use ESD control and prevent mechanical load on connectors or board surfaces.

Restore configuration deliberately

Reapply only the approved installed settings, wiring and application records.

Retain acceptance evidence

Keep label photographs, test results, deviations and responsible sign-off.

Alternative Names

GE IS200PAICH1B IS200PAICH1B Analog Input and Output Board

Technical notes

Installation relationship: IS200PAICH1B belongs to the configured GE Mark VIe analog I/O system hardware chain; the complete installed relationship governs replacement.

Protection: Follow the approved isolation, ESD and system-specific commissioning procedure before handling IS200PAICH1B.

Technical reference: GE Mark VIe lifecycle references and exact-model industrial records. The H1B identity is used as the offered analog I/O board marking; the documented platform function is 10 analog inputs and 2 analog outputs, with terminal-board and loop details installation dependent.

FAQ View All FAQ

  • How should the ten inputs and two outputs of IS200PAICH1B be distinguished during replacement?
    Create a direction-specific channel map showing each terminal, signal type, loop-power arrangement and field-device tag. Keep input and output circuits separate during disconnection and testing.
  • What signal-type checks are required before connecting IS200PAICH1B?
    Confirm the configured range, polarity and loop-power source for each analog point from the approved drawing and controller record. Do not assume that all twelve channels use the same electrical arrangement.
  • Which termination relationship must be preserved for IS200PAICH1B?
    Record the connected terminal hardware, cable identity and controller-side channel mapping. Restore the same physical and logical path before applying field signals or output commands.
  • How should shielding and grounding be reviewed for IS200PAICH1B?
    Follow the project loop drawings for shield drains, signal returns and cabinet earth. Remove unintended parallel ground paths that could affect low-level input accuracy.
  • How can an analog-input fault be isolated with IS200PAICH1B?
    Compare the field-device signal, loop power, terminal reading, board diagnostics and controller value. Use a calibrated source at the approved point to determine whether the error is in the field loop or input path.
  • How should the analog outputs of IS200PAICH1B be tested?
    Command controlled values within the approved 0-20 mA range, measure the loop current and confirm the corresponding field-device response. Test one output at a time and retain the result.
  • What calibration evidence should be retained for IS200PAICH1B inputs?
    Record the injected reference values, controller readings, channel configuration and measured error at the selected test points. Keep the calibration source identity with the maintenance record.
  • What complete acceptance test is appropriate for IS200PAICH1B?
    Verify representative inputs and both outputs, confirm diagnostics and channel mapping, then compare the controller and field responses with the approved baseline before returning automatic control.