Speak to a sourcing specialist
sales13@apterpower.com

HE693SNP232A

Series 90-30 SNP-to-RS-232 Adapter
In Stock
Ships by Sunday, November 29
Fast Shipping Available
General Electric HE693SNP232A SNP-to-RS-232 adapter, angled view with top label
General Electric HE693SNP232A SNP-to-RS-232 adapter, angled view with unlabeled recessed panel
General Electric HE693SNP232A SNP-to-RS-232 adapter, top view of label above D-sub connector
General Electric HE693SNP232A SNP-to-RS-232 adapter, angled view with top label
General Electric HE693SNP232A SNP-to-RS-232 adapter, angled view with unlabeled recessed panel
General Electric HE693SNP232A SNP-to-RS-232 adapter, top view of label above D-sub connector
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

GE HE693SNP232A is an SNP-to-RS-232 adapter for the Series 90-30 PLC programmer port. It is powered by the PLC port and provides a 9-pin RS-232 connection for a straight-through PC/AT cable.
Get a quick price for HE693SNP232A
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for HE693SNP232A

  • Manufacturer:
    General Electric
  • Product Category:
    PLC Systems
  • Spare Part Number:
    HE693SNP232A
  • Estimated shipping dimensions:
    3.5x13.5x13.5cm
  • Weight:
    0.24 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Product designation:
    SNP-to-RS-232 adapter
  • PLC interface:
    15-pin SNP connector
  • Serial interface:
    9-pin RS-232 connector
  • Installation:
    Plugs directly into the PLC programmer port
  • Power source:
    PLC programming port
  • Maximum power demand:
    100 mA at 5 V DC
  • PC cable:
    Straight-through 1:1 PC/AT cable
  • RS-232 transmit data:
    Pin 2
  • RS-232 receive data:
    Pin 3
  • RS-232 signal ground:
    Pin 5
  • RS-232 clear to send:
    Pin 7
  • RS-232 request to send:
    Pin 8
  • SNP signals:
    Differential TXD, RXD, CTS and RTS pairs

Information

Overview Manuals Common Applications Product Precautions
GE HE693SNP232A provides SNP-to-RS-232 serial conversion for a documented Series 90-30 programmer port.
  • 15-pin SNP PLC connector
  • 9-pin RS-232 device connector
  • Port-powered at 5 V DC
  • Straight-through PC/AT cable support

The adapter plugs directly into the Series 90-30 CPU-rack programmer port and connects to the documented RS-232 device. Commissioning preserves the port, cable and serial settings and verifies controlled SNP communication.

Important Notice: Confirm HE693SNP232A, the exact Series 90-30 CPU rack and programmer port, adapter orientation, RS-232 cable, connected-device settings, handshaking and communication evidence before release.

General Electric HE693SNP232A Manuals & Downloads

These documents are different: the first consolidates exact product and system data; the second provides model-specific installation checks, commissioning steps and acceptance guidance.

Series 90-30 programming
Connects an RS-232 programming device to the documented PLC programmer port.
SNP diagnostics
Provides the physical conversion path for controlled serial troubleshooting.
Legacy workstation connection
Supports a documented straight-through PC/AT serial cable.
Adapter replacement
Restores the exact port, cable and handshaking assignments before communication testing.
Read Horner MAN0079-06 and the applicable GE Fanuc Series 90-30 instructions before work. Verify HE693SNP232A, the PLC programmer port and the connected RS-232 device.
1
Confirm HE693SNP232A and the 15-pin SNP to 9-pin RS-232 adapter execution.
2
Place the connected PLC and controlled process in the approved maintenance state.
3
Record the programmer port, adapter orientation, cable route and connected device settings.
4
Power down the Series 90-30 rack before installing or removing the adapter.
5
Inspect the 15-pin and 9-pin connectors and use a straight-through 1:1 PC/AT cable.
6
Confirm the programmer port can supply the documented 5 V DC, 100 mA maximum demand.
7
Restore the approved serial data rate, parity and handshaking configuration.
8
Verify transmit, receive, CTS, RTS and successful SNP communication before release.

Technical notes

Install HE693SNP232A only on the documented GE Fanuc Series 90-30 programmer port. Record the PLC port, adapter orientation, RS-232 cable, connected-device settings and successful SNP communication baseline before replacement, then verify transmit, receive and handshaking under controlled conditions.

FAQ View All FAQ

  • What exact interface conversion does HE693SNP232A provide?
    HE693SNP232A converts the Series 90-30 SNP programmer interface to a 9-pin RS-232 connection.
  • Where is HE693SNP232A installed on a Series 90-30 PLC?
    The 15-pin SNP connector plugs directly into the programmer port on the CPU rack power supply.
  • How is HE693SNP232A powered?
    The adapter receives power from the PLC programming port and draws no more than 100 mA at 5 V DC.
  • Which cable is used between HE693SNP232A and a PC/AT serial port?
    The official adapter data sheet specifies a direct straight-through 1:1 RS-232 cable.
  • Which HE693SNP232A RS-232 pins carry transmit and receive data?
    Transmit data is on pin 2 and receive data is on pin 3 of the 9-pin connector.
  • Which HE693SNP232A pins are used for ground and handshaking?
    Signal ground is pin 5, clear to send is pin 7 and request to send is pin 8.
  • What should be recorded before replacing HE693SNP232A?
    Record the PLC port, adapter orientation, RS-232 cable, connected device settings and the successful SNP communication baseline.
  • Which official records support the HE693SNP232A page?
    Horner MAN0079-06 documents the HE693SNP232 adapter and MAN0051 explicitly lists the HE693SNP232A part number for Series 90-30 serial conversion.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.