Technical specifications for 330103-00-05-20-02-CN
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330103-00-05-20-02-CN
-
Estimated shipping dimensions:21x18x1.8cm
-
Weight:0.1 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Probe construction:Without armor
-
Mounting thread:M10 x 1
-
Unthreaded length:0 mm
-
Case length:50 mm
-
Total lead length:2.0 m
-
Connector option:Miniature coaxial ClickLoc
-
Approval option:CN execution
-
Probe-tip diameter:8.0 mm
-
System linear range:2.0 mm (80 mils)
-
Recommended gap:1.27 mm (50 mils)
-
Incremental scale factor:7.87 V/mm (200 mV/mil)
-
Frequency response:0 to 10 kHz, +0/-3 dB
-
Probe cable impedance:75 ohm
-
Probe temperature:-52 to +177 deg C
-
Proximitor supply:-17.5 to -26 VDC
-
Field wiring:0.2 to 1.5 mm2
-
Maximum field wiring:305 m
Information
- Detects shaft-to-bearing relative movement without mechanical contact
- Forms the field sensing element of the matched eddy-current loop
- Carries the probe signal through the specified service connection
- Supports static-position and vibration measurements on rotating machinery
The probe is fitted to the engineered M10 x 1 machine position and connected to the selected extension cable and Proximitor Sensor. Commissioning includes order-code, clearance, cable-route, total-system-length, static-gap and controlled response checks.
Important Notice: Confirm 330103-00-05-20-02-CN, M10 x 1 host thread, 0 mm unthreaded length, 50 mm case execution, without armor, Miniature coaxial ClickLoc, extension cable, Proximitor Sensor, total system length, target material, wiring, shielding, grounding, monitor configuration, static gap and controlled response-test results before commissioning.
Apter Power 330103-00-05-20-02-CN Manuals and Guides
- Apter Power 330103-00-05-20-02-CN Probe Configuration Technical Reference PDF
- Apter Power 330103-00-05-20-02-CN Gap, Cable and Response Verification Workbook PDF
The first document is the model-specific technical and system reference. The second is a distinct field workbook for installation, wiring, commissioning and acceptance records.
Technical notes
FAQ View All FAQ
-
What makes 330103-00-05-20-02-CN the correct execution for this installation?Confirm 330103-00-05-20-02-CN, M10 x 1 host thread, 0 mm unthreaded length, 50 mm case execution, without armor, Miniature coaxial ClickLoc, extension cable, Proximitor Sensor, total system length, target material, wiring, shielding, grounding, monitor configuration, static gap and controlled response-test results before commissioning.
-
Where is 330103-00-05-20-02-CN used within the documented Bently Nevada 3300 XL 8 mm Proximity Transducer System architecture?Detects shaft-to-bearing relative movement without mechanical contact. It senses shaft-to-bearing relative displacement in a matched proximity transducer system.
-
Which companion components must remain matched to 330103-00-05-20-02-CN?The probe is fitted to the engineered M10 x 1 machine position and connected to the selected extension cable and Proximitor Sensor. Commissioning includes order-code, clearance, cable-route, total-system-length, static-gap and controlled response checks.
-
What pre-work evidence is needed before disconnecting 330103-00-05-20-02-CN?Place the monitored machine and associated protection channel in the approved maintenance state. Protect the 8.0 mm probe tip and keep the mounting thread free from burrs and contamination.
-
How should the physical interface of 330103-00-05-20-02-CN be inspected?Confirm the installed extension cable and Proximitor Sensor match the approved total system length.
-
What configuration values must agree with the installed 330103-00-05-20-02-CN?Set the static gap within the documented linear region while maintaining target clearance.
-
Which commissioning observations prove 330103-00-05-20-02-CN is operating normally?Confirm the complete 330103-00-05-20-02-CN marking, M10 x 1 thread and 50 mm case execution. Keep the Miniature coaxial ClickLoc connection clean, dry and finger-tight.
-
What maintenance evidence closes the work on 330103-00-05-20-02-CN?Prove polarity, static position, dynamic response and alarm action before returning the channel to service.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
330103-00-05-20-02-CNProduct Details -
330103-00-10-10-02-CNProduct Details -
330104-10-20-10-02-05Product Details -
330104-00-24-50-02-00Product Details -
330101-00-12-10-02-CNProduct Details -
330103-03-12-05-02-00Product Details -
330104-06-12-10-02-00Product Details -
330104-00-13-10-01-CNProduct Details -
330104-12-20-10-01-00Product Details -
330103-00-02-05-01-00Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.