Match the complete marking
Include the complete Allen-Bradley 81004-286-52-R marking and any hardware revision on the item. Include the installed drive and all 2 matched device positions.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 81004-286-52-R with the installed equipment and applicable Allen-Bradley documentation.
Technical specifications for 81004-286-52-R
-
Manufacturer:Allen-Bradley
-
Product Category:General Automation
-
Spare Part Number:81004-286-52-R
-
Weight:0.56 kg
-
Tariff Code:8537101190
-
Device technology:SGCT
-
Device class:400 A
-
Matched device count:2
-
Assembly form:matched pair
-
Command transmission:Fiber-optic
-
Diagnostic return:Fiber-optic
-
Offline gate-supply window:19.6-20.4 V
Information
- Allen-Bradley 81004-286-52-R restores a defined matched group in the drive switching structure. Device matching, optical gating and diagnostic feedback must be assessed together at the affected power assembly.
Matched group: 2 SGCT devices
Control path: Optical gate command and diagnostic feedback
The drive compares feedback around a gate event during its Offline diagnostic sequence. Feedback remaining low directs a feedback-loss investigation; feedback remaining high directs a gating-loss investigation. The physical device position, firing-card indications and optical path help distinguish these cases.
The associated nominal 20 V firing source, secure power connections, optical interfaces and SGCT resistance checks are part of the diagnostic process. Complete the prescribed Gating Test and investigate associated motor-filter-capacitor causes where indicated before restarting the drive.
81004-286-52-R Official Technical Excerpt
The original technical excerpt for Allen-Bradley 81004-286-52-R covers SGCT diagnostic logic and exact matched-set identification. PDF · 7 pages.81004-286-52-R Installation & Verification Guide
Apter Power installation and verification guide covering matched-group retention, optical paths, auxiliary power and drive tests. PDF · 5 pages.
Application scope: Use the complete spare identity and affected device positions to select the repair. Current class alone does not establish interchangeability.
Matched assembly replacement
Retain the 400 A class and 2-device matching relationship in the approved power structure.Gate-command diagnosis
Trace the optical command path when feedback stays high after gating.Feedback-path recovery
Correlate device state and optical return when feedback remains low.Controlled drive restoration
Complete resistance, driver, gating and restart checks before motor operation.
Keep all group labels and device positions together.
Apply the medium-voltage service and discharge procedure.
Avoid crossed, damaged or pinched gate and return fibers.
Verify the firing source and seated connections.
A nonzero resistance alone does not prove device health.
Confirm diagnostic recovery before restarting the drive.
Alternative Names
Technical notes
Matched pair handling: Preserve the two-device matching relationship and converter location when handling the replacement pair. Similar packaging does not establish the correct electrical class.
Feedback investigation: Check both the outgoing gate signal and returning feedback path. Persistent feedback after a gate command is a diagnostic condition, not proof of successful switching.
FAQ View All FAQ
-
Which current class identifies the pair supplied as 81004-286-52-R?It is a matched pair of 400 A SGCT devices for the PowerFlex 7000 spare-parts system.
-
Why is 81004-286-52-R distinct from a two-piece order of single SGCTs?Its part identity includes a matched two-device relationship. Quantity alone does not prove that two separately sourced singles form the specified pair.
-
Does 81004-286-52-R define whether the installed position is in the inverter or rectifier?The spare identity establishes device class and matched form. Use the installed drive assembly and phase/device designation to determine the actual position; do not infer it from the pair count.
-
Which optical path is checked when feedback from 81004-286-52-R remains high after gating?Check the gate-command path, its optical connections and the DPM-to-OIB connection under the Gating Loss procedure. Unchanged high feedback differs from unchanged low feedback.
-
How should the firing-card supply connections of 81004-286-52-R be assessed?Verify both the associated nominal 20 V supply and the seating of power connectors at each affected device. A healthy source does not prove a sound connection at the firing card.
-
Why is motor-filter-capacitor condition relevant to a feedback-loss investigation around 81004-286-52-R?The drive diagnostic guidance includes a non-operational motor filter capacitor as a possible cause. Resolve that condition, particularly before synchronous-transfer operation.
-
Can the 400 A class of 81004-286-52-R be substituted by a higher-current SGCT without review?No. Device class alone does not establish assembly compatibility. Match the complete spare selection and installed power structure.
-
What proves recovery of each device path in 81004-286-52-R?Compare the drive fault position, gate-driver indication, controlled gating response and returned feedback for both devices. Keep the pair identity and test results together.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.