Match the complete marking
Include the complete Bently Nevada 990-10-70-03-00 marking and any hardware revision on the item. Include the 0-10 mils peak-to-peak scale and 7.0 m transducer chain.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 990-10-70-03-00 with the installed equipment and applicable Bently Nevada documentation.
Technical specifications for 990-10-70-03-00
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:990-10-70-03-00
-
Weight:0.5 kg
-
Tariff Code:8537101190
-
Measurement:Radial vibration
-
Full-scale span:0-10 mils peak-to-peak
-
Electrical system length:7.0 m
-
Signal output:4-20 mA; two-wire
-
Terminal supply:+12 to +35 VDC
-
Maximum loop resistance:1000 ohms at 35 VDC; includes cable
-
Frequency response:5 Hz-6000 Hz; +0/-3 dB
-
Current limit:23 mA typical
-
Mounting:DIN clips and screws
-
Transmitter temperature:-35 to +85 degrees C
-
Fault current:Below 3.6 mA
Information
- Bently Nevada 990-10-70-03-00 brings radial shaft motion into the machinery controller through a powered current loop, while retaining a separate diagnostic connection for the probe signal.
Transducer system: 7.0 m, compatible 3300 NSv probe and cable
Mounting: DIN clips and screws
The two-wire loop supplies power and transmits peak-to-peak shaft vibration amplitude as 4-20 mA. The receiving control system supplies the alarm and protection logic. Non-interacting zero and span adjustments support loop calibration, while the TEST input accepts a AC signal generator for controlled output checks.
The separate PROX OUT/COM and coaxial connection provide the dynamic and gap signal for diagnosis. This output is non-isolated and must be used with the specified test arrangement. Not OK/Signal Defeat drives the loop below 3.6 mA on a faulty transducer connection; power-up and fault recovery require approximately 2-3 seconds.
990-10-70-03-00 Official Technical Excerpt
The original technical excerpt for Bently Nevada 990-10-70-03-00 covers transmitter operation, electrical limits and diagnostic connections. PDF · 6 pages.990-10-70-03-00 Installation & Verification Guide
Apter Power installation and verification guide covering measurement scaling, loop burden, cable matching and controlled loop tests. PDF · 5 pages.
Application scope: Use the 0-10 mils peak-to-peak scale for shaft-vibration supervision of the assigned machine point. Protective alarm logic remains in the receiving system.
Machine-point signal conditioning
Convert one radial vibration measurement into a 4-20 mA input for the controller.Calibrated loop renewal
Retain the 0-10 mils peak-to-peak receiver range and 7.0 m electrical chain when replacing the transmitter.Probe-signal diagnosis
Observe the dynamic and gap signal with the specified diagnostic connection and instrument isolation.Protection-loop verification
Use the TEST input with a AC signal generator to compare signal output and receiving indication.
Keep 0-10 mils peak-to-peak and its units in the receiver configuration.
The probe and extension together must equal 7.0 m.
Provide the required terminal voltage after wiring and receiver losses.
The diagnostic connection is non-isolated.
Distinguish below-3.6 mA fault and startup states from valid measurements.
Remove test inputs and verify stable measurement before clearing the approved bypass.
Alternative Names
Technical notes
Controller scaling: Retain the 0–10 mil peak-to-peak engineering span when testing loop current. A half-span test is meaningful only with the same range configured in the controller.
Fault recovery: Wait for the transducer fault-recovery interval before evaluating a restored signal. Confirm that the controller distinguishes a Not OK current from a valid low vibration value.
FAQ View All FAQ
-
Why must 990-10-70-03-00 use a different controller span from a 0-5 mil transmitter?Its 0-10 mil peak-to-peak range is twice that span. A receiver left at 0-5 mil would under-report the same 4-20 mA fraction of full scale.
-
What is the nominal current at half scale for 990-10-70-03-00?For the proportional 4-20 mA loop, half scale corresponds to 12 mA and 5 mils peak-to-peak. Confirm the actual calibrated endpoints during loop verification.
-
How should 990-10-70-03-00 be mounted when both clips and screws are supplied?The 03 mounting option provides DIN clips and screws. Use the arrangement selected for the installation while keeping adjustment and wiring access clear.
-
Can shortening the probe cable preserve the calibration of 990-10-70-03-00?No. Its 7.0 m electrical length depends on the matched probe and extension cable. Altering that chain changes the transducer relationship.
-
What is the typical current limit of 990-10-70-03-00?The typical current limit is 23 mA. This overload behavior is distinct from the normal 20 mA full-scale measurement and the below-3.6 mA Not OK state.
-
How quickly does 990-10-70-03-00 recover after a corrected transducer fault?Once the Not OK condition is removed, the signal is restored in approximately 2-3 seconds. Verify a stable recovery before restoring protection logic.
-
Which target conditions underlie the performance values for 990-10-70-03-00?Unless specified otherwise, performance is based on a matched 3300 NSv probe and extension cable, an AISI 4140 steel target and +22 degrees Celsius.
-
Where are alarms generated when 990-10-70-03-00 is installed?Alarm thresholds and protective logic belong to the receiving control system. Check its 0-10 mil scaling, fault-current handling and configured setpoints together.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.