Match the complete marking
Include CI520V1 3BSE012869R1 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered CI520V1 3BSE012869R1 reference with the installed equipment and applicable ABB documentation.
Technical specifications for CI520V1 3BSE012869R1
-
Manufacturer:ABB
-
Product Category:DCS Systems
-
Spare Part Number:CI520V1 3BSE012869R1
-
Weight:0.12 kg
-
+5 V rail power:3.7 W
-
+24 V rail power:2 x 2.5 W
-
Bus connector pins:9 per D-sub female
-
Auxiliary output current, maximum:60 mA
-
Typical RS-485 input impedance:12 kohm
-
Handled cyclic data packets:Approximately 4000
-
Redundant bus cable paths:2
-
TK515 modem cable length:1.80 m
Information
- CI520V1 must be distinguished from the original CI520 variant without redundant-media support. It also differs from CI626, whose coaxial media modems are integrated rather than external.
Redundant-path continuity: Two cable paths require separately identified media connections.
Controller-side fit: Carrier and modem-cable choice depend on the Advant Controller installation.
The interface is installed in an AC450/460 submodule carrier or an AC410 CPU arrangement. TK515 is the documented modem cable for AC450/460 and TK593 for AC410. The external TC625, TC512 or TC516 relationship must match the installed medium and physical connection scheme.
X8 and X9 identify the two bus-cable paths. For redundant coaxial installation, each path requires its own external TC625 modem and the bus must be terminated and grounded according to the media topology. X12 is a test strap and must remain unstrapped in service; it is not a field configuration link.
CI520V1 3BSE012869R1 Original Technical Reference Excerpt
Selected original manufacturer pages for the applicable interfaces and technical data. PDF · 6 pages · 3142.8 KB.CI520V1 3BSE012869R1 Installation & Commissioning Guide
Controller Carrier and Dual-Media AF100 Review. Decide carrier/cable and media/modem relationships separately, then prove the redundant network paths without relying on a single healthy connection. PDF · 2 pages · 91.8 KB.
Application scope: V1 redundant-media support, modem type, controller cable and bus termination must agree as one installation; the interface alone does not define the complete network.
AC450/460 interface
Match the submodule carrier and TK515 modem-cable arrangement. Confirm the installed controller position before transferring media connections.AC410 CPU connection
Use the documented TK593 relationship for AC410. Do not carry the AC450 cable assumption into the different receiving arrangement.Redundant coaxial media
Keep the two paths and their TC625 modems identifiable. Restore the specified termination and common grounding location for the paired bus installation.Twisted-pair media
Reconcile TC512/TC516 and the selected AF100 topology. Check the installed media conversion and terminations rather than treating the D-sub port as the field bus cable itself.
Do not replace a redundant-media requirement with the earlier non-redundant variant.
The manufacturer test strap must not be fitted during operation.
Record the two cables and the modem assigned to each path.
Distinguish the AC450/460 TK515 and AC410 TK593 arrangements.
Use the approved coaxial or twisted-pair termination and grounding scheme.
Check each redundant media route independently before accepting normal network operation.
Alternative Names
Technical notes
Version significance: CI520V1 redundant-media support must not be assigned to the original CI520 variant.
Test strap: X12 is reserved for testing and must remain unstrapped.
Path-specific acceptance: Redundant coaxial media uses a separate TC625 on each bus cable. A healthy path must not hide a second cable, modem or termination defect.
FAQ View All FAQ
-
Can the original CI520 replace CI520V1 3BSE012869R1 where two bus cables are required?The original variant lacks the V1 redundant-media support. Retain the V1 requirement and verify both media paths rather than accepting the shared CI520 family name.
-
Should X12 be fitted to configure CI520V1 3BSE012869R1 for normal bus service?No. The manufacturer identifies X12 as a test strap that must not be fitted in operation. Preserve the documented service condition rather than treating it as a media-selection link.
-
Why does CI520V1 3BSE012869R1 need a modem check even though it has D-sub bus connections?CI520 uses external media modems. The connector does not by itself establish a coaxial or twisted-pair installation; compare the modem, cable and termination arrangement.
-
Is the modem cable the same for CI520V1 3BSE012869R1 in AC410 and AC450/460?No. The documented arrangements use TK593 for AC410 and TK515 for AC450/460. Match the receiving controller and carrier before transferring the existing cable assumption.
-
How many external coaxial modems are needed for a redundant-media installation using CI520V1 3BSE012869R1?The documented architecture uses one TC625 per bus cable. Keep their path identities and connections separate, then prove each route independently.
-
Can an integrated-modem CI626 be treated as the same interface arrangement as CI520V1 3BSE012869R1?No. CI626 integrates coaxial media modems, while CI520 uses external units. A change requires review of the controller connection, network hardware and media topology.
-
Where should troubleshooting start if only one bus path works after installing CI520V1 3BSE012869R1?Compare X8/X9 path allocation, that path’s external modem, cable and termination. For redundant coaxial media each cable has its own TC625; inspect the failed route rather than changing a working common application mapping first.
-
Why does moving CI520V1 3BSE012869R1 between controller types require more than reusing a D-sub cable?The documented AC410 connection uses TK593, while AC450/460 uses TK515 and its carrier arrangement. Confirm the controller/carrier interface and the external modem path together; matching connector shape alone does not select the correct cable.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
CI520V1 3BSE012869R1Product Details -
330101-00-10-10-02-05Product Details -
330101-00-30-05-02-00Product Details -
330103-00-03-05-01-05Product Details -
330102-00-60-05-02-05Product Details -
07NG63R1 GJV3074313R1Product Details -
07KP64 GJR5240600R0101Product Details -
07EA61R1 GJV3074351R1Product Details -
330130-040-03-CNProduct Details -
190501-07-00-04Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.