Match the complete marking
Match the complete Siemens 6AV6642-0BA01-1AX0 marking, hardware execution and connection arrangement to the installed position before approving the order.
-
Check the offered item before ordering
Request clear photographs of the offered 6AV6642-0BA01-1AX0 and ask your maintenance team to compare its markings and interfaces with the installed equipment and applicable Siemens instructions.
Technical specifications for 6AV6642-0BA01-1AX0
-
Manufacturer:Siemens
-
Product Category:HMI Panels
-
Spare Part Number:6AV6642-0BA01-1AX0
-
Weight:0.8 kg
-
Tariff Code:8537101190
-
Display technology:5.7-inch STN, 256 colors
-
Pixel resolution:320 x 240
-
Touch technology:Analog resistive
-
User-data memory:2048 kbyte
-
Ethernet interfaces:1; 10/100 Mbit/s
-
Serial interfaces:RS422 and RS485
-
USB interfaces:1
-
Memory-card slot:Multimedia Card; up to 128 MB
-
Engineering software:WinCC flexible Compact 2005 or later
-
Enclosure protection:IP65 front; IP20 rear
-
Clock backup:No battery backup
Information
- Siemens 6AV6642-0BA01-1AX0 supports operator actions that must remain coordinated with controller permissions, recipe destinations and alarm states.
Project services: Alarms and recipe management
Recovery path: Compatible project, runtime image and communication settings
Runtime screens, alarms and recipes belong to the downloaded HMI project. Keep a recoverable engineering project and a compatible runtime image together. A panel that boots successfully can still display stale or incorrectly mapped process information.
The resistive touch surface and enclosure seal form separate acceptance checks. Verify touch targeting with controlled commands, then inspect the installed front seal. Rear connections remain within the cabinet protection boundary.
6AV6642-0BA01-1AX0 Original Technical Excerpt
The original technical excerpt supports 6AV6642-0BA01-1AX0 configuration review. The separate Apter Power field guide organizes practical diagnostic checks. PDF · 3 pages.6AV6642-0BA01-1AX0 Installation & Verification Guide
Apter Power engineering guide for the installed signal, power or communication path and controlled acceptance. PDF · 5 pages.
Application scope: The following uses describe supported engineering roles; they do not establish interchangeability with another model or remove application-specific validation.
Machine visualization
Display tags from the configured controller connection.Recipe-controlled changeovers
Transfer validated setpoint groups through the project recipe design.Local alarm acknowledgement
Acknowledge configured messages while preserving controller interlocks.Legacy HMI maintenance
Restore the appropriate WinCC flexible project and original network settings.
Preserve the TP177B engineering project, runtime compatibility information, alarm and recipe data, and the MPI/PROFIBUS or Ethernet settings. Identify the controller tags behind operator commands and record the access levels required to use them. Check that the recovery method can restore the project, rather than relying on an image of the visible screens.
Place machine commands in the approved inhibited state before testing the touch interface or replacing the panel. Inspect the front seal separately from the rear cabinet connections. Check the power feed and supported MMC arrangement without assuming that arbitrary removable media or a similar connector is suitable.
Restore the project and the MPI/PROFIBUS or Ethernet with the correct controller endpoint. Check changing values at both the controller and panel, then compare units and tag destinations. Retain the original baseline until the new runtime and connection have been demonstrated under controlled conditions.
Generate an authorized test alarm and trace its acknowledgement back to the controller. Check a permitted setpoint or recipe transfer against controller limits and destination tags. Include clock synchronization after power interruption in the acceptance sequence so that a hardware-specific behavior is not concealed by a general screen test.
Restore normal operator access only after commands, indications and clock synchronization after power interruption have passed the agreed tests. Remove temporary test data and confirm that the production recipe and communication settings remain intact. Retain the accepted project and recovery files together with the installed TP177B hardware identity.
Use the exact hardware execution with the supported system configuration and installation conditions.
Alternative Names
Technical notes
Configuration baseline: Keep the installed SIMATIC HMI arrangement aligned with the complete 6AV6642-0BA01-1AX0 reference and its assigned system role.
Acceptance boundary: Compare the electrical or communication response with the intended application outcome before releasing maintenance controls.
Technical reference: Siemens product data sheet, 6AV6642-0BA01-1AX0. Use the exact hardware execution with the supported system configuration and installation conditions.
FAQ View All FAQ
-
Why can 6AV6642-0BA01-1AX0 show valid screens while all process values are stale?The screen project can run without a healthy PLC connection. Check the selected driver, controller address and communication diagnostics before editing tags. Verify changing test values at the PLC and at the panel rather than judging by the appearance of the screen.
-
What must accompany a backup intended to restore 6AV6642-0BA01-1AX0?Retain the engineering project, compatible runtime version, connection settings and required recipe data. A copied screen image is not an editable project. Verify the recovery method before removing the installed panel from service.
-
Can 6AV6642-0BA01-1AX0 be moved from PROFIBUS to Ethernet by changing the cable only?No. The HMI connection and controller endpoint must be configured for the chosen protocol. Preserve the original project until the new connection is validated, including tag addressing, update behavior and alarm acknowledgements.
-
How can a touch-calibration problem on 6AV6642-0BA01-1AX0 be tested safely?Use a controlled test screen or inhibited process state to compare the touched position with the selected object. Do not test by repeatedly pressing a live start command. Inspect calibration and surface condition before changing application coordinates.
-
Why should recipe restoration on 6AV6642-0BA01-1AX0 be checked against the PLC?A recipe file can contain values that are valid in the HMI yet inappropriate for the current controller program. Compare units, limits and destination tags, then prove a controlled transfer with equipment in a safe state.
-
What distinguishes a dark backlight from a failed 6AV6642-0BA01-1AX0 project?Check supply and startup behavior, then assess whether the panel still communicates or responds through the supported service path. Display illumination failure and project corruption require different remedies; do not overwrite a recoverable project merely because the screen is dark.
-
Why can time-stamped alarms change after a power interruption on 6AV6642-0BA01-1AX0?Its hardware clock has no battery backup. Restore the intended clock synchronization and compare timestamps with the controller after restart. Event sequence analysis is unreliable when the devices use different time references.
-
How should 6AV6642-0BA01-1AX0 alarm acknowledgement be verified after replacement?Generate a permitted test alarm, confirm its text and state, acknowledge it at the panel and observe the controller acknowledgement path. A disappearing HMI message alone does not prove that the machine-side alarm state was reset.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.