Match the complete marking
Provide the complete Siemens 6SL3000-0KH14-0AA0 marking.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 6SL3000-0KH14-0AA0 with the installed equipment and applicable Siemens instructions.
Technical specifications for 6SL3000-0KH14-0AA0
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6SL3000 0KH14 0AA0
-
Weight:18.24 kg
-
Tariff Code:8537101190
-
Nominal resistance:4.0 Ω
-
Resistance tolerance:±10%
-
Pulse-load energy:18000 W·s
-
Associated line-voltage range:500–690 V, three phase
-
Associated infeed architecture:Diode-based Basic Line Module, frame GD
-
Resistor quantity per phase:1, or 2 in parallel according to design
-
Total resistor quantity:3 or 6 for the specified three-phase circuit
-
Precharge-contactor control:Basic Line Module X9:5,6
-
Bypass-contactor control:Basic Line Module X9:3,4
Information
- Siemens 6SL3000-0KH14-0AA0 limits DC-link charging current during the resistor-based precharge sequence before the main bypass path is closed.
Sequence dependency: The precharge and bypass contactor paths operate at different stages.
Energy assessment: Component quantity and connection depend on the configured infeed and capacitance.
Resistor quantity and phase connection depend on the engineered precharge circuit. The selected arrangement must match the DC-link capacitance and the associated infeed execution.
The precharge and bypass controls act in sequence. Successful component resistance checks do not by themselves establish that the complete charging circuit operates correctly.
6SL3000-0KH14-0AA0 Official Technical Excerpt
Siemens 6SL3000-0KH14-0AA0: original manufacturer technical information covering the specified interfaces and operating limits. PDF · 1 pages.6SL3000-0KH14-0AA0 Installation & Verification Guide
Apter Power guide covering precharge architecture, resistance paths, thermal and capacity, sequence and protection, charging acceptance. PDF · 5 pages.
Application boundary: Its intended use is charging-current limitation in that arrangement, not general braking-energy dissipation.
DC-link charging limitation
The resistor limits current during the initial charging of the specified infeed circuit.Frame-GD Basic Infeed
It forms part of a diode-based S120 Basic Line Module arrangement.Parallel precharge paths
Two resistors per phase can be used where the engineered capacitance arrangement requires them.Sequenced infeed control
The resistor operates in the internally controlled charging and bypass sequence of the compatible Basic Infeed arrangement.
Follow the drive isolation and discharge procedure before touching the resistor or contactors. Verify the safe electrical state and account for every connected DC-link source and possible backfeed path.
Use the appropriate disconnected-component test method and compare the result with 4.0 ohms ±10%. Account for parallel paths before interpreting a measured resistance as the value of one resistor.
Compare the connected DC-link capacitance with the permitted arrangement for the Basic Line Module. Include changes to the drive line-up that may have occurred since the original precharge design was commissioned.
Use the correct conductor, terminal and protective-device arrangement for the complete circuit. Inspect all phase paths and mechanical supports before energization, keeping the resistor pulse-energy limit distinct from continuous-load ratings.
Record resistor values, quantity per phase, capacitance assessment and sequence-test results. Return the infeed to service only after the complete precharge and bypass arrangement operates as designed.
Run the approved commissioning sequence and verify that the link charges before the bypass path takes over. Investigate abnormal timing, repeated retries or excessive heating before enabling normal drive operation.
Alternative Names
Technical notes
Operating boundary: 18000 W·s is pulse energy, not a continuous-power claim.
Integration details: Match resistor quantity, DC-link capacitance and internally controlled contactor sequence.
FAQ View All FAQ
-
Why is the pulse-energy value of 6SL3000-0KH14-0AA0 not a continuous power rating?Energy is the integral of power over the charging event. It does not authorize a continuous load of the same numerical value; assess the actual precharge pulse and permitted operating sequence.
-
Can 6SL3000-0KH14-0AA0 be used as a braking resistor simply because both dissipate energy?No. It serves the specified precharge circuit. Braking duty has a different function and load profile, so resistance alone does not establish suitability.
-
How can parallel paths distort a resistance test on 6SL3000-0KH14-0AA0?A connected parallel resistor or circuit path changes the measured result. Use the approved isolated-component method before comparing the reading with the individual component tolerance.
-
Why must the bypass sequence be checked after replacing 6SL3000-0KH14-0AA0?The resistor limits charging current before the bypass takes over. Incorrect timing can defeat current limitation or leave the resistor carrying an unintended load.
-
What changes when a design uses two 6SL3000-0KH14-0AA0 resistors per phase?The effective resistance and energy distribution differ from a single-resistor path. Restore the specified quantity and connection in every phase rather than changing one branch in isolation.
-
How does a DC-link expansion affect 6SL3000-0KH14-0AA0 selection?Additional capacitance changes the charging requirement. Reassess the permitted Basic Infeed arrangement instead of assuming the existing resistor set remains suitable.
-
Why are repeated unsuccessful precharge attempts relevant to 6SL3000-0KH14-0AA0 diagnosis?Repeated charging events add thermal stress and can indicate an unresolved sequence or load problem. Investigate the underlying fault before repeatedly restarting the infeed.
-
Does a correct cold resistance prove that 6SL3000-0KH14-0AA0 will precharge the system correctly?No. Contactor operation, circuit connections and the connected capacitance still determine the event. Verify the complete approved charging sequence after the component check.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.