Provides independent magnetic overcurrent detection for an AC or DC power circuit and transfers the trip indication through its auxiliary contact.
Signal or energy path: Circuit current energizes the magnetic sensing mechanism; when the configured threshold is exceeded, the relay changes contact state for the external control or trip circuit.
Companion components: Use with the correctly rated conductor path, contactor or breaker control circuit, enclosure and terminal hardware documented for the feeder.
Engineering check: Confirm conductor routing, current-setting method, coordination with upstream protection and reset or test procedure before service.
System boundary: The relay supplies an overcurrent trip indication and does not replace coordinated feeder isolation or short-circuit protection.
Motor feeders and industrial power circuits requiring adjustable high-current magnetic protection.
Important Notice: Verify the complete RM1XA315 nameplate, installed-system documentation, companion hardware and current Schneider Electric instructions before installation or replacement.
Important Notice: The first link is the product-parameters PDF prepared only from the cited manufacturer information; the second link is the Apter Power product manual. Confirm the physical nameplate, current manufacturer documents, and host-system requirements before installation or replacement.
Starter-circuit peak protection
Instantaneously detects an abnormal current peak in a starter circuit that is not normally subject to current peaks.
Resistor-circuit overcurrent supervision
Protects a resistor circuit where the normal process does not include repeated current peaks.
Slip-ring motor starting-peak control
Supervises the current peak during starting of a slip-ring motor within the cataloged range.
Contactor trip and fault indication
Uses the RM1ZG21 changeover contact in the Schneider 2-wire or 3-wire control schemes to drop a contactor and, where engineered, signal a trip.
Read and follow the current Schneider Electric documentation and host-equipment instructions before work. Verify the complete physical nameplate and system configuration.
1
Read the complete physical reference: RM1XA315 is non-latching, while RM1XA3151 is the latching/manual-reset version.
2
Do not use the 250...800 A trip-setting range as the motor continuous-current range; Schneider separately specifies 146...230 A recommended motor In and 315 A maximum continuous current.
3
Use the relay only in a circuit whose normal behavior matches Schneider's stated application; repeated normal current peaks can cause unwanted instantaneous trips.
4
Do not exceed 12 operating cycles per hour, and do not describe this relay as suitable for frequent cycling.
5
Order and verify the correct RM1ZG21 non-latching 1 C/O contact block; do not fit latching/reset accessories by reference similarity alone.
Alternative Names
Schneider Electric RM1XA315Schneider Electric RM1-XA315Schneider RM1-XA315RM1XA315
Technical notes
Equipped with a 250–800 A adjustable magnetic trip range and 315 A maximum continuous current, dedicated to instantaneous overcurrent defense for industrial high-current heating resistors or heavy-load startup circuits.
It is a TeSys RM1 single-pole, non-latching electromagnetic overcurrent relay for instantaneous detection of current peaks.
Is RM1-XA315 the official Schneider reference?
Schneider's catalog prints the commercial reference as RM1XA315 without a hyphen. A nameplate shown only as RM1-XA315 should be verified before normalization.
What current range does RM1XA315 monitor?
The catalog gives a 250...800 A trip-current setting range, a 146...230 A recommended motor-current range and a 315 A maximum continuous current.
Does RM1XA315 latch after a trip?
No. RM1XA315 is the non-latching reference. RM1XA3151 is the separate latching/manual-reset version.
It senses power-circuit current and mechanically changes the auxiliary contact state on trip. Schneider's schemes show 91-92 and 93-94 changeover paths; no analog or network output is documented.
Can RM1XA315 be used for frequent operation?
No. Schneider states that RM1XA relays are not suitable for frequent operation and limits them to 12 operating cycles per hour.
What is the maximum circuit voltage?
The RM1XA characteristics specify a maximum rated operational voltage of 600 V AC or DC and a 0...60 Hz frequency range.
Where is RM1XA315 typically applied?
Schneider lists circuits without normal current peaks, such as starters and resistors, and control of starting peaks on slip-ring motors.
Can RM1XA3151 replace RM1XA315 directly?
No direct substitution should be assumed. The latching behavior, reset method, contact block and control wiring differ and must be engineered for the application.