Technical specifications for CC-TAID11

  • Manufacturer:
    Honeywell
  • Product Category:
    DCS Systems
  • Spare Part Number:
    51306731-175
  • Estimated shipping dimensions:
    29.4x12x8cm
  • Weight:
    0.42 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    Xiamen, Fujian, China
  • IOTA function:
    Redundant analog input IOTA
  • Input channels:
    16
  • Differential channels:
    1 to 16 with CC-TAIDx1
  • Redundancy:
    Supported
  • IOTA size:
    12 inch; 304 mm nominal
  • Compatible I/O modules:
    CC-PAIH02; CC-PAIX02
  • Input type:
    Voltage; current; 2-wire or self-powered transmitters
  • Input ranges:
    0 to 5 V; 1 to 5 V; 0.4 to 2 V; 4 to 20 mA through 250 ohm
  • Common-mode rejection:
    70 dB; dc to 60 Hz
  • Common-mode voltage:
    -6 to +5 V peak; dc to 60 Hz
  • A/D resolution:
    16 bits
  • Normal-mode rejection:
    19 dB at 60 Hz
  • Normal-mode filter:
    Single-pole RC; -3 dB at 6.5 Hz
  • Maximum differential input:
    +/-30 V; no damage
  • Channel crosstalk:
    -60 dB; dc to 60 Hz
  • Voltage-input impedance:
    >10 Mohm; powered
  • Input scan rate:
    50 ms
  • Hardware accuracy at 23.5 degC:
    +/-0.075% of full scale
  • Hardware accuracy at 0 to 60 degC:
    +/-0.15% of full scale
  • Field conductor capacity:
    Up to 12 AWG; 2.5 mm2 stranded
  • IOM field power:
    Supplied through IOTA
  • IOTA supply source:
    24 Vdc carrier bus
  • Field terminals:
    Two-level detachable terminals
  • Mounting orientation:
    Vertical
  • Transmitter power protection:
    Individually protected current-limiting circuits
  • Non-incendive interface:
    Class I, Division 2
  • Inline channel fusing:
    Not required

Information

Overview Manuals Common Applications Product Precautions
Honeywell CC-TAID11 is a 16-channel differential analog-input IOTA for redundant Series C I/O. It terminates measurement loops for paired high-level or universal analog-input modules.
  • Terminates sixteen differential analog input channels
  • Supports paired analog-input modules
  • Connects field measurement loops to Series C I/O
  • Maintains one field interface during module redundancy

CC-TAID11 installs with Series C carrier, Paired CC-PAIH or CC-PAIX modules, Differential analog field wiring, C300 control configuration in an engineered Experion Series C I/O configuration.

The commissioning workflow covers installed-hardware matching, controlled start-up and functional verification for this redundant sixteen-channel analog input iota.

Important Notice: Confirm the complete CC-TAID11 marking, installed-system configuration, field connections and controlled functional test before commissioning or replacement.

Apter Power CC-TAID11 Manuals and Guides
Apter Power CC-TAID11 Product Technical Reference PDFHoneywell CC-TAID11 Official Manual PDF
The first document is an Apter Power model-specific technical reference. The second supports model-specific installation, configuration and engineering verification.
Redundant process-transmitter inputsTerminates sixteen differential analog input channels
Critical pressure and flow measurementSupports paired analog-input modules
High-availability temperature acquisitionConnects field measurement loops to Series C I/O
Series C analog cabinet replacementMaintains one field interface during module redundancy
Read the applicable Honeywell installation instructions before work. Verify CC-TAID11 and the installed Experion Series C I/O configuration.
1Verify the complete CC-TAID11 marking and its assigned Experion Series C I/O position before work.
2Isolate the energy associated with Series C carrier before disconnecting CC-TAID11.
3Protect the CC-TAID11 connectors and electronic assembly using approved ESD controls.
4Record the as-found Paired CC-PAIH or CC-PAIX modules connections and configured assignment before replacement.
5Confirm Differential analog field wiring matches the approved installation record for CC-TAID11.
6Restore CC-TAID11 under controlled conditions and review its model-specific diagnostics.
7Complete a documented functional test for redundant process-transmitter inputs before release.

Technical notes

Confirm both module types, preserve channel polarity and shield treatment, then verify redundancy status and scaled values on every restored loop.

FAQ View All FAQ

  • How should engineers validate CC-TAID11 after configuration?
    Restore the documented Experion Series C I/O assignment, review diagnostics and run a controlled test of its role: terminates sixteen differential analog input channels.
  • Can CC-TAID11 be moved to a different slot or duty without review?
    No. Confirm keying, companion hardware and the approved configuration before assigning CC-TAID11 to another position or function.
  • Which technical value is especially important during CC-TAID11 commissioning?
    Verify Normal-mode rejection is 19 dB at 60 Hz and use the named manufacturer procedure for the controlled functional test.
  • What should be checked if CC-TAID11 does not support critical pressure and flow measurement after installation?
    Check seating, Paired CC-PAIH or CC-PAIX modules, Differential analog field wiring, field energy and the model-specific diagnostics before replacing additional hardware.
  • What evidence should be retained after CC-TAID11 returns to service?
    Retain the full model identity, as-left connections, configuration, diagnostic result and the final controlled test record for redundant process-transmitter inputs.
  • How is CC-TAID11 identified before installation in a Experion Series C I/O cabinet?
    Match the full CC-TAID11 marking and part number 51306731-175 to the assigned position and installed Series C carrier.
  • Which companion hardware must be checked when replacing CC-TAID11?
    Verify Series C carrier, Paired CC-PAIH or CC-PAIX modules and Differential analog field wiring against the approved cabinet and project record before fitting the Redundant Sixteen-Channel Analog Input IOTA.
  • What wiring information should be recorded before removing CC-TAID11?
    Record terminal identifiers, polarity or phase, shields, cable tags and the as-found channel or port assignment for CC-TAID11.
Related reading

Related cases and sourcing guidance

View all case studies