Bently Nevada 125680-01 is a Proximitor I/O Module with Internal Terminations. It connects up to four proximity-transducer circuits to the rear of the machinery-protection rack.
Get a quick price for 125680-01
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for 125680-01

  • Manufacturer:
    Bently Nevada
  • Product Category:
    Machinery Monitoring Systems
  • Spare Part Number:
    125680-01
  • Estimated shipping dimensions:
    2.5x11.2x24.2cm
  • Weight:
    0.38 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • I/O module type:
    Proximitor
  • Termination arrangement:
    Internal
  • Matched monitor:
    3500/40M
  • Signal inputs:
    1 to 4 proximity transducers
  • Input impedance:
    10 kOhm
  • Transducer power supply:
    -24 Vdc
  • Buffered output impedance:
    550 Ohm
  • Radial direct filter:
    4-4000 Hz or 1-600 Hz
  • Radial gap filter:
    -3 dB at 0.09 Hz
  • Direct and gap accuracy:
    +/-0.33% FS typical; +/-1% maximum
  • Alarm setpoint range:
    0-100% of full scale
  • Operating temperature:
    -30 to +65 degC
  • Storage temperature:
    -40 to +85 degC
  • Humidity:
    95% non-condensing
  • Rear rack space:
    1 full-height slot
  • External termination blocks:
    Not applicable

Information

Overview Manuals Common Applications Product Precautions
Bently Nevada 125680-01 is the internal-termination Proximitor I/O module for a 3500/40M monitor. It connects up to four proximity-transducer circuits to the rear of the machinery-protection rack.
  • Terminates up to four proximity-transducer circuits inside the 3500 rack
  • Routes conditioned probe inputs to the paired 3500/40M front monitor
  • Supplies the documented negative transducer excitation through the I/O assembly
  • Supports the monitor's vibration, position, eccentricity, expansion and REBAM channel types

125680-01 installs with 3500 rack rear slot, 3500/40M 176449-01 monitor, Proximity probes and extension cables, Internal field-wiring connectors in an engineered 3500/40M Proximitor Monitor configuration.

The commissioning workflow covers installed-hardware matching, controlled start-up and functional verification for this proximitor i/o module with internal terminations.

Important Notice: Confirm the complete 125680-01 marking, installed-system configuration, field connections and controlled functional test before commissioning or replacement.

Apter Power 125680-01 Manuals and Guides
Apter Power 125680-01 Product Technical Reference PDFBently Nevada 125680-01 Official Manual PDF
The first document is an Apter Power model-specific technical reference. The second supports model-specific installation, configuration and engineering verification.
Internal probe-circuit terminationTerminates up to four proximity-transducer circuits inside the 3500 rack
Four-channel vibration rack assemblyRoutes conditioned probe inputs to the paired 3500/40M front monitor
Thrust-position transducer connectionSupplies the documented negative transducer excitation through the I/O assembly
REBAM proximity-signal marshallingSupports the monitor's vibration, position, eccentricity, expansion and REBAM channel types
Read the applicable Bently Nevada installation instructions before work. Verify 125680-01 and the installed 3500/40M Proximitor Monitor configuration.
1Confirm 125680-01 and its assigned 3500/40M rear-slot position before disconnection.
2De-energize the rack and isolate transducer wiring before removing internal connectors.
3Label all four channel connectors so probe assignments cannot be interchanged.
4Use ESD controls and inspect the internal-termination headers for bent or recessed contacts.
5Do not connect an external termination block to the 125680-01 internal-termination execution.
6Seat the rear I/O module and front monitor as the documented matched assembly.
7Confirm negative transducer power and stable gap voltage before restoring channel alarms.
8Prove each measurement path using the configured radial, thrust, expansion or REBAM duty.

Technical notes

Keep each probe, extension cable and Proximitor circuit assigned to its original channel, verify internal connector seating and measure stable gap voltage before enabling monitor alarms.

FAQ View All FAQ

  • What as-found information should an engineer record before removing 125680-01?
    Record every channel or port assignment, connector identity, configured function, cable tag and diagnostic state associated with 125680-01.
  • How should 125680-01 be isolated before field wiring is disturbed?
    Place the protected machine in its approved maintenance state, isolate rack and field energy applicable to Proximity probes and extension cables, and prove the terminals safe before disconnection.
  • Which configuration should be restored after replacing 125680-01?
    Restore the approved 3500/40M Proximitor Monitor slot, channel or interface configuration and verify that every connected circuit retains its original assignment.
  • How can 125680-01 be commissioned for internal probe-circuit termination?
    Apply a controlled input or command, review the model-specific diagnostics and prove the expected measurement, indication and protection response before releasing the channel.
  • What technical value deserves special attention when checking 125680-01?
    Verify the published termination arrangement value of Internal against the installed configuration and test record.
  • Can 125680-01 be exchanged with another 3500 I/O or monitor execution?
    Only when the complete part number, termination style, transducer or interface type and approved rack configuration match the installed duty; do not transfer settings from an adjacent model.
  • What evidence should be retained after 125680-01 returns to service?
    Retain the full 125680-01 identity, as-left connections, restored configuration, final diagnostics and the controlled functional-test result for four-channel vibration rack assembly.
  • Which rack hardware must be matched before installing 125680-01?
    Match 125680-01 to the documented 3500 rack rear slot and 3500/40M 176449-01 monitor; confirm the front/rear slot pairing and the complete physical marking before connection.
Related reading

Related cases and sourcing guidance

View all case studies
Manufacturers

Product Browsing History

Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.