Speak to a sourcing specialist
sales13@apterpower.com

8C-PCNT03

Series 8 C300 Controller
In Stock
Ships by Friday, November 6
Fast Shipping Available
Honeywell 8C-PCNT03
Honeywell 8C-PCNT03
Honeywell 8C-PCNT03
Honeywell 8C-PCNT03
Honeywell 8C-PCNT03
Honeywell 8C-PCNT03
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

Honeywell 8C-PCNT03 is a Series 8 C300 controller. It executes Experion control strategies, communicates with Series 8 I/O and exchanges controller data over redundant Fault Tolerant Ethernet.
Get a quick price for 8C-PCNT03
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for 8C-PCNT03

  • Manufacturer:
    Honeywell
  • Product Category:
    Machinery Monitoring Systems
  • Spare Part Number:
    51454363-375
  • Estimated shipping dimensions:
    7.3x15.3x16.2cm
  • Weight:
    0.46 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Controller model:
    8C-PCNT03; coated
  • Program memory:
    16 MB
  • Processor:
    Single core
  • Supported Experion releases:
    R110, R120, R500, R51x, R520
  • Execution units:
    5500
  • Tagged objects:
    4095
  • Memory units:
    16384
  • Control execution period:
    50 to 60000 ms
  • CPU reserved capacity:
    20%
  • I/O links:
    2
  • I/O link rate:
    750 kbit/s
  • I/O units per controller:
    80
  • I/O units per link:
    40
  • Maximum I/O:
    2560
  • FTE interfaces:
    Dual 100 Mbit/s
  • Redundancy:
    IOTA based; bumpless switchover
  • RAM retention:
    Optional; 50 h
  • Coating:
    G3; ANSI/ISA S71.04-1985

Information

Overview Manuals Common Applications Product Precautions
Honeywell 8C-PCNT03 is series 8 c300 controller. It executes Experion control strategies, communicates with Series 8 I/O and exchanges controller data over redundant Fault Tolerant Ethernet.
  • Executes configured Control Builder strategies
  • Connects as many as eighty I/O units over two I/O links
  • Provides dual one-hundred-megabit FTE interfaces
  • Supports IOTA-based redundant controller operation

8C-PCNT03 operates with 8C-TCNTA1 controller IOTA, Series 8 I/O modules, FTE network, Experion server and Control Builder project.

Engineered applications include Continuous-process control, Redundant C300 controller service, Series 8 I/O coordination, Experion control-node modernization.

Important Notice: Back up the approved Control Builder project, verify the 8C-TCNTA1 IOTA and supported Experion release, then prove FTE, I/O links and redundancy before production release.

Apter Power 8C-PCNT03 Manuals and Guides

Apter Power 8C-PCNT03 Product and System Technical Reference PDFApter Power 8C-PCNT03 Field Installation and Functional Acceptance Workbook PDF

The first document organizes model-specific identity, technical data and system context. The second provides a separate installation, connection, commissioning and acceptance workflow.

Continuous-process control

Runs regulatory and sequential strategies for a process unit.

Redundant C300 controller service

Provides bumpless controller resilience in a redundant pair.

Series 8 I/O coordination

Coordinates local Series 8 I/O over the two controller links.

Experion control-node modernization

Modernizes the control processor while retaining the validated project.

Read the applicable Honeywell instructions before work. Verify 8C-PCNT03 and the installed Experion PKS C300 configuration.
1

Verify the complete 8C-PCNT03 marking and its assigned C300 controller position before work.

2

Place the connected process and control strategy in the approved maintenance state.

3

Isolate the applicable cabinet supply and I/O-link and FTE field energy before disconnecting conductors.

4

Record terminal numbers, channel assignments, polarity, shields and configured ranges before removal.

5

Use ESD controls and protect the backplane connector, terminal hardware and coated electronics.

6

Confirm the installed 8C-TCNTA1 IOTA and carrier arrangement against the approved project.

7

Restore power in a controlled sequence and clear only diagnostics created by the maintenance activity.

8

Complete project-load, I/O-link, FTE and redundancy acceptance tests and retain the measured result before returning the channel to automatic service.

Technical notes

Back up the approved Control Builder project, verify the 8C-TCNTA1 IOTA and supported Experion release, then prove FTE, I/O links and redundancy before production release.

FAQ View All FAQ

  • Which Experion releases support 8C-PCNT03?
    Use 8C-PCNT03 only with an approved project for R110, R120, R500, R51x or R520, and validate the Control Builder database before loading it.
  • How is redundant operation implemented for 8C-PCNT03?
    A redundant C300 arrangement is built through the controller IOTA and is designed for bumpless switchover; confirm both controller positions and redundancy links before service.
  • How should 8C-PCNT03 I/O capacity be allocated?
    The controller supports two I/O links, up to 40 I/O units on each link and 80 units in total; verify the configured allocation before moving any Series 8 I/O.
  • What execution-period range can be configured on 8C-PCNT03?
    Control execution periods can be set from 50 to 60000 ms. Match each control module period to the approved process strategy and CPU loading plan.
  • Why is CPU reserve important when commissioning 8C-PCNT03?
    The controller reserves 20 percent CPU capacity. Confirm execution-unit loading and controller statistics remain within the approved engineering limit before production release.
  • How should the FTE connections of 8C-PCNT03 be verified?
    Check both 100 Mbit/s Fault Tolerant Ethernet interfaces, network identity, redundancy path and controller diagnostics before accepting communication.
  • What does optional RAM retention mean for 8C-PCNT03 maintenance?
    The optional retention arrangement supports 50 hours. Verify the installed memory-backup hardware and preserved controller state rather than assuming retention is fitted.
  • What should be proven after replacing an 8C-PCNT03 controller?
    Restore the approved project, confirm the 8C-TCNTA1 IOTA, verify both I/O links, test FTE communication, exercise redundancy and review all controller diagnostics.
Related reading

Related cases and sourcing guidance

View all case studies