Match the complete marking
Use FX-USI-0002 only with a compatible Safety Manager release, R140.1 or later, and the approved replacement procedure. Verify peer-module operation and all configured communication paths.
-
Check the offered item before ordering
This listing concerns FC-USI-0002. The FX successor is a separate item; a quotation for one does not include the other. Controller software and redundant-peer configuration determine the migration path.
Technical specifications for FC-USI-0002
-
Manufacturer:Honeywell
-
Product Category:DCS Systems
-
Spare Part Number:FC-USI-0002
-
Weight:0.7 kg
-
Tariff Code:8537101190
-
Interface role:Universal Safety Interface
-
Controller system:Safety Manager
-
Successor hardware:FX-USI-0002
-
Replacement pin compatibility:Pin-to-pin
-
Replacement functional compatibility:FC-USI-0002 function supported
-
Minimum release for FX replacement:Safety Manager R140.1
-
Redundant peer compatibility:FX-USI-0002 with installed FC-USI-0002
-
Replacement operating mode:Online, subject to supported release and procedure
Information
- Honeywell FC-USI-0002 forms part of the controller communication arrangement in an installed Safety Manager system. Replacement planning must preserve external communication paths and the relationship between redundant controller modules.
Software boundary: FX replacement requires Safety Manager R140.1 or later
Redundant operation: FX can operate with an existing FC-USI-0002
FX-USI-0002 replacement requires Safety Manager software R140.1 or later. A controller running an earlier release cannot support the FX module merely because its connector fits; the software release is a separate compatibility requirement for this migration.
Within the supported controller configuration, an FX-USI-0002 can operate alongside an existing FC-USI-0002 in a redundant Safety Manager controller and can replace the FC module online under the applicable replacement procedure. This mixed-module capability supports staged replacement while retaining the peer interface; it does not authorize simultaneous removal of both redundant interfaces.
FC-USI-0002 Official USI Compatibility Excerpt
Honeywell USI successor architecture and FC replacement scope. FX ratings are not FC-USI-0002 specifications. PDF · 7 pages.FC-USI-0002 Installation & Verification Guide
Release assessment, redundancy preparation, controlled interface migration and communication acceptance. PDF · 5 pages.
Application scope: The applications concern installed-system interface service and replacement engineering. They do not establish an independent safety integrity rating or authorization to bypass the plant change procedure.
Legacy Safety Manager maintenance
Retain the installed interface role and exact release context while assessing service options.Supported successor migration
Plan an FX replacement only after confirming R140.1 or later and the applicable change procedure.Mixed redundant interfaces
Evaluate an FX successor alongside an installed FC-USI-0002 peer with redundancy-state checks.Communication recovery planning
Prepare path-specific tests and a recovery route for changes to a controller communication interface.
Confirm R140.1 or later before an FX migration.
Record both interface types and present redundancy status.
Assess communications affected by removal or reset.
Online capability does not replace the Honeywell maintenance procedure.
Do not copy FX electrical or environmental values into FC equipment records.
Test configured data paths and resolve diagnostics before release.
Alternative Names
Technical notes
Release-specific migration: The replacement path requires R140.1 or later. Preserve the complete release number in the maintenance record.
Redundant configuration: FX-USI-0002 can function with an FC-USI-0002 peer; check the actual controller state before changing either module.
Reference scope: The Downloads hardware excerpt covers the successor interface and its explicit FC replacement relationship. It does not restate FC electrical ratings.
Technical reference: Honeywell Safety Manager Hardware Reference, EP-SM.MAN.6284 Issue 1.10; System HINTS, August 2019.
FAQ View All FAQ
-
Can FC-USI-0002 be replaced by FX-USI-0002 without changing the pin interface?The FX module is pin-to-pin and function compatible with FC-USI-0002. Confirm the installed software release and follow the applicable replacement procedure before changing hardware.
-
Why is R140.1 important when migrating an FC-USI-0002 installation?FX-USI-0002 is not supported on Safety Manager releases earlier than R140.1. Check the full installed release rather than relying on the broad R140 family label.
-
Must both FC-USI-0002 modules in a redundant controller be replaced together?The FX replacement can function with an existing FC-USI-0002 peer in a redundant controller. Mixed operation is supported; use the approved change sequence and confirm redundancy health.
-
Does online replacement of FC-USI-0002 eliminate the need to assess communication interruption?No. Online replacement capability does not prove every external path remains continuously available during a change. Assess the affected paths and verify the application-specific redundancy arrangement.
-
Should FX electrical ratings be entered as FC-USI-0002 engineering data?No. The successor hardware has its own ratings. Pin and function compatibility does not make all component, processor or electrical specifications identical.
-
What is the alternative when an FC-USI-0002 system is older than R140.1?Plan a supported software upgrade before using the FX successor. If the upgrade cannot be scheduled, evaluate an appropriate legacy spare and support plan for the existing release.
-
What communication evidence should be retained before changing FC-USI-0002?Record the controller release, both interface identities, active peer relationships, configured endpoints and current communication status. Use these records to compare the restored paths after replacement.
-
Which result confirms an FC-USI-0002 replacement is ready for service?Verify that the replacement is recognized in the intended role, its redundant peer remains healthy, and every configured communication path exchanges the expected data without unresolved diagnostics.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.