Match the complete marking
Include 330101-00-24-10-02-05 and any revision or approval marking visible on the probe. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label, tip and connector photos. Have your maintenance team compare the offered 330101-00-24-10-02-05 with the installed equipment and applicable Bently Nevada documentation.
Technical specifications for 330101-00-24-10-02-05
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330101-00-24-10-02-05
-
Weight:0.05 kg
-
Tariff Code:8537101190
-
Probe family:3300 XL 8 mm proximity probe
-
Order-code thread:3/8-24 UNF, no armor
-
Unthreaded length:0.0 in
-
Overall case length:2.4 in
-
Integral probe cable:1.0 m total length
-
Connector:Miniature coaxial ClickLoc
-
Connector protector:Not selected in option 02
-
Cable type:Standard FEP-insulated triaxial cable
-
Agency approval option:05: CSA, ATEX and IECEx; verify nameplate
-
Probe tip material:Polyphenylene sulfide
-
Probe case material:AISI 303 or 304 stainless steel
-
Nominal probe DC resistance:7.59 ±0.50 Ω for 1.0 m probe
-
Minimum cable bend radius:25.4 mm
-
Recommended case torque:11.2 N·m for standard forward mount
-
Maximum thread engagement:0.563 in for 3/8-24
-
Standard probe temperature:−52 to +177 °C, operating and storage
-
Matched system linear range:2.0 mm with approved components
-
Matched system scale factor:7.87 V/mm ±5% for standard 1 m system, 0 to 45 °C
-
Recommended radial gap:About 1.27 mm or −9 V DC in matched system
-
Matched system frequency response:0 to 10 kHz, +0/−3 dB
Information
- Bently Nevada 330101-00-24-10-02-05 supports non-contact shaft vibration and position measurement when installed in a matched 3300 XL 8 mm transducer chain.
System relationship: Use the matching Proximitor and cable arrangement for calibrated measurements.
Approval boundary: Confirm the supplied marking and applicable installation drawing for option 05.
The probe forms one part of an eddy-current measuring chain. The manufacturer publishes a 2.0 mm linear range and 7.87 V/mm nominal incremental scale for the matched 1 m system on its reference target. These values depend on the specified Proximitor and cable arrangement; the probe alone does not provide a calibrated voltage output.
Before replacement, compare the target material, cable route and installed monitor channel with the approved machine drawing. Record the existing gap-voltage baseline, set the new probe to the approved gap and verify the response in the complete chain.
Bently Nevada 3300 XL 8 mm transducer-system data sheet
Manufacturer document 141194 Rev. AN; order code, component construction and matched-system performance.330101-00-24-10-02-05 engineering guide
Apter Power installation, diagnostic and acceptance guide for the selected probe.
Platform applications: The uses below describe a correctly matched 3300 XL 8 mm chain. Check the installed target, monitor and machine drawing before applying a system rating.
-
Radial shaft vibration
Locate the sensing point at the approved bearing case and retain clearance for shaft orbit and target runout. -
Axial position
Face a conductive thrust target; validate travel within the matched transducer range and machine gap limits. -
Keyphasor reference
Select a suitable target feature and matched channel; confirm timing and once-per-turn indication in the installed monitor. -
Maintenance replacement
Preserve the 3/8-24 fit, 2.4 in case, 1 m lead and electronics configuration when replacing the probe.
Confirm the 3/8-24 thread, 2.4 in case length, maximum engagement and target clearance before insertion.
The published matched-chain scale uses the manufacturer reference target; verify correction for a different alloy or geometry.
Keep the 1 m FEP triaxial lead above its 25.4 mm minimum bend radius and away from abrasion.
Option 02 uses miniature coaxial ClickLoc without a separate protector. Keep mating surfaces clean and fully seated.
The 05 selection identifies approval options; inspect the actual marking and associated drawing for the installed circuit.
After fitting, set the approved gap and compare output and trend with the recorded machine baseline.
Technical notes
Installation relationship: This 1.0 m probe requires the matching 3300 XL 8 mm Proximitor and approved cable arrangement. Verify the 3/8-24 case, 2.4 in overall length and operating gap against the machine drawing.
System performance: The published linear range, scale factor and frequency response describe the matched transducer system under the manufacturer reference conditions, not a standalone probe voltage output.
Technical reference: Bently Nevada 3300 XL 8 mm Proximity Transducer System, 141194 Rev. AN. The 05 approval option must be verified against the supplied marking and installation approval.
FAQ View All FAQ
-
Why might 330101-00-24-10-02-05 show a changed gap voltage after replacement?Check that the probe is seated at the documented gap, that the ClickLoc connector is fully engaged and that the 1 m Proximitor channel is the approved match. Compare the voltage with the machine baseline before altering alarm settings.
-
How can an open circuit be distinguished from a gap change on 330101-00-24-10-02-05?With the channel isolated under the site procedure, check center-to-outer resistance and connector continuity against the manufacturer 1 m probe reference. A cable or connector defect should be excluded before resetting the gap.
-
What could reduce high-frequency response from 330101-00-24-10-02-05?Inspect the total field wiring length, cable route, connector condition and monitor filtering. Compare measurements at the same operating state; the published response applies to the complete matched transducer system.
-
What should be reviewed if 330101-00-24-10-02-05 is installed on a small shaft?Verify shaft diameter, target width and the calibration target. Shafts below the recommended size can change scale factor, and nearby probes can introduce cross-talk. Use the machine drawing and applicable manufacturer guidance.
-
How should the cable of 330101-00-24-10-02-05 be routed?Maintain at least the published minimum bend radius, protect the standard unarmored cable from abrasion and keep the connector dry. Do not treat the probe pressure seal as cable ingress protection.
-
What is the replacement boundary for 330101-00-24-10-02-05 on a 5 m channel?The ordered 1.0 m probe is one element of the chain. Select the extension length so probe plus extension equals the Proximitor total length; verify the installed sensor variant before acceptance.
-
How should 330101-00-24-10-02-05 be checked for cross-talk?Confirm separation from adjacent probe tips and compare the installed geometry with manufacturer guidance. If both channels respond together unexpectedly, inspect target size, cable routing and monitor channel assignments.
-
What must be verified before using 330101-00-24-10-02-05 in a hazardous area?Read the actual approval marking and approved installation drawing for this supplied unit. The 05 ordering option identifies the approval selection but does not itself prove the complete barrier, cable and area classification arrangement.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
330101-00-24-10-02-05Product Details -
330102-00-35-10-02-00Product Details -
330102-00-10-10-01-05Product Details -
330130-045-12-05Product Details -
330930-045-01-05Product Details -
330730-080-03-05Product Details -
KJ4001X1-BE1Product Details -
330153-01Product Details -
1SAR330020R0000Product Details -
KC6-22ZProduct Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.