Match the complete marking
Include 22B-B024N104 and every hardware, firmware or assembly-revision marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available rating-label, power-terminal and keypad photos. Have your maintenance team compare the offered 22B-B024N104 with the installed equipment and applicable Allen-Bradley documentation.
Technical specifications for 22B-B024N104
-
Manufacturer:Allen-Bradley
-
Product Category:General Automation
-
Spare Part Number:22BB024N104
-
Weight:4.3 kg
-
Tariff Code:8537101190
-
Supply voltage:200-240 V AC, 3-phase
-
Permitted input range:180-264 V AC
-
Rated output current:24.0 A
-
Motor power:5.5 kW / 7.5 HP
-
Frame:C
-
Enclosure:IP20 / NEMA Type Open
-
Power factor:0.98
-
Brake transistor:Included
-
Output frequency:0-400 Hz, programmable
-
Voltage-reference input:0-10 V DC; 100 kOhm
-
Current-reference input:4-20 mA; 250 Ohm
-
Digital-input current:6 mA
-
Analog-output resolution:10 bit
-
Opto output:30 V DC, 50 mA; non-inductive
-
Relay resistive rating:3 A at 30 V DC / 125 V AC / 240 V AC
-
Carrier frequency:2-16 kHz; rating based on 4 kHz
-
Acceleration/deceleration:0-600 s; 0.1 s increments
-
Operating ambient:-10 to +50 deg C, IP20 open type
-
Altitude without derating:1000 m maximum
-
Relative humidity:0-95%, non-condensing
-
Serial interface:RS-485 / DSI
-
Built-in EMC filter:Not fitted
Information
- PowerFlex 40 combines programmable motor control with independent start-command and speed-reference selection, allowing a machine to retain its existing terminal or serial control scheme.
Panel integration: The N enclosure is open type, so the surrounding cabinet must provide the required protection.
EMC arrangement: The unfiltered selection needs installation-specific filtering and grounding review.
The start source and frequency reference are selected independently. P036 controls the command path, while P038 controls the speed source; changing only one can leave a drive responding to a different control location than the machine expects. Motor nameplate voltage, base frequency and overload current remain motor-specific settings.
The integral brake IGBT provides the switching element for a properly selected braking arrangement; it does not supply the external braking resistor. Regenerative loads and aggressive deceleration must be reviewed together with the bus regulator, stopping requirements and resistor selection, rather than judging the drive only by its motor kilowatt value.
-
Allen-Bradley 22B-B024N104 official technical excerpt
Applicable original manufacturer excerpt, PDF, 10 pages. Exact voltage, current, frame and installed options are established by the model cutsheet. Family electrical and FRN 3.xx parameter data apply with the stated installation and firmware conditions. -
Allen-Bradley 22B-B024N104 engineering guide
Apter Power engineering guide, PDF, 2 pages. Motor-data setup, start/reference ownership, DSI commissioning and fault-directed checks.
Integration boundary: A drive replacement must preserve the motor settings, command source, speed reference and stopping behavior of the complete machine.
-
Motor-speed retrofit
Retain the 240 V motor/supply relationship and validate the connected motor current before transferring an existing variable-speed application. -
Terminal-based control
Match source/sink wiring and the actual stop circuit to P036 and P037; preserve the selected analog or preset-speed reference. -
DSI/Modbus RTU network
Use the RS-485 DSI wiring and supported Modbus functions; the RJ45 interface must not be treated as Ethernet. Match the serial address and rate to the host. -
Controlled deceleration
Coordinate the load inertia, braking resistor and bus-regulator behavior with the required stopping response. The fitted IGBT requires a separately selected resistor.
Isolate the line supply and follow the applicable PowerFlex discharge and voltage-verification procedure before touching power terminals; a dark display is not proof of discharge.
Match the incoming phases to the line terminals and the motor leads to the output terminals. Verify protective earth and the supply grounding arrangement before energizing.
Set P031, P032 and P033 from the connected motor; check minimum/maximum frequency before enabling a run command.
Test the intended stop circuit and command/reference sources with the machine in its approved test state; review restart behavior before restoring production control.
Review cable routing, cabinet bonding and any external EMC filter for the actual supply system. An open-type unfiltered order does not establish machine EMC compliance.
For an F5 event, compare incoming voltage, regeneration and deceleration timing before replacing hardware. Use an approved braking solution where the application requires it.
Alternative Names
Technical notes
Control relationship: Start commands and frequency reference have separate source parameters. A successful keypad run does not prove that the terminal or serial command path has been restored.
Braking coordination: The included brake transistor and the optional resistor serve different roles. Review resistor duty and stopping requirements with the actual regenerative load.
Reference scope: The product cutsheet establishes this exact drive selection. FRN 3.xx parameter examples require comparison with the delivered firmware before settings are transferred.
FAQ View All FAQ
-
Why can 22B-B024N104 run from the keypad but ignore the machine speed command?Compare P036 Start Source and P038 Speed Reference separately. Prove the selected analog, preset or DSI source at a controlled test point; changing the run-command source does not automatically change the frequency reference.
-
What should be checked before moving motor parameters into 22B-B024N104?Read the connected motor voltage, frequency and allowable current, then reconcile P031-P033 and the frequency limits with the saved file. A parameter backup from another motor can retain an unsuitable overload setting even when the drive rating matches.
-
How should an F5 overvoltage during stopping on 22B-B024N104 be investigated?Record the event and review line voltage, regenerative energy and the commanded deceleration. Extending deceleration or using a correctly sized braking arrangement addresses different causes; do not assume an included brake transistor means that a resistor is already connected.
-
Can the RJ45 connector on 22B-B024N104 be connected to an Ethernet switch?The installed interface is RS-485 DSI. Use the documented DSI pinout and network accessories; the connector shape is not an Ethernet compatibility indication. Check network termination and node settings before applying serial control.
-
Why can a Modbus master read 22B-B024N104 but fail to start it?Read and write access do not select control ownership. Verify the DSI start and reference selections, the stop input state and the master addressing convention; some masters offset the published register address by one.
-
How should sink/source input wiring be checked when replacing 22B-B024N104?Compare the existing control circuit with the selected SNK/SRC configuration and its common connection. Test the stop and run states in an approved machine test mode; a shared common arrangement suitable for source wiring must not be assumed suitable for sink wiring.
-
Does the unfiltered selection of 22B-B024N104 determine the machine EMC result?No. Cabinet bonding, motor cable routing, shielding, supply grounding and any external filter form the installation-level EMC arrangement. Confirm the applicable installation requirements instead of treating the drive order code as a machine compliance result.
-
Is the proposed 25B replacement for 22B-B024N104 a direct exchange?It is an engineering replacement. Review the physical installation, terminal functions, motor control setup, serial integration and braking arrangement, then commission the changed system rather than copying the PowerFlex 40 settings without comparison.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
22B-B024N104Product Details -
330102-00-28-05-02-05Product Details -
330102-00-60-05-02-05Product Details -
07NG63R1 GJV3074313R1Product Details -
07KP64 GJR5240600R0101Product Details -
07EA61R1 GJV3074351R1Product Details -
330130-040-03-CNProduct Details -
190501-07-00-04Product Details -
330500-07-02Product Details -
21747-045-00Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.