-
Match the complete marking
Include the complete 1762-IQ16 marking and series, host controller model and installed expansion-slot position.
-
Check the offered item before ordering
Compare the offered 1762-IQ16 with field-device polarity, common groups, simultaneous input demand and cabinet temperature.
Technical specifications for 1762-IQ16
-
Manufacturer:Allen-Bradley
-
Product Category:PLC Systems
-
Spare Part Number:1762-IQ16
-
Weight:0.25 kg
-
Tariff Code:8537101190
-
Digital inputs:16
-
Input voltage category:24 V DC, sinking/sourcing
-
Input voltage envelope:10–30 V DC; 10–26.4 V DC subject to thermal point-count limits
-
Isolated input groups:Two groups of eight: 0–7 and 8–15
-
Maximum expansion-bus demand:70 mA at 5 V DC; 0.35 W
-
Maximum on-delay:8 ms
-
Maximum off-delay:8 ms
-
Maximum off-state voltage:5 V DC
-
Maximum off-state current:1.5 mA
-
Minimum on-state voltage:10 V DC
-
Minimum on-state current:2.0 mA at 10 V DC
-
Nominal on-state current:8.0 mA at 24 V DC
-
Maximum on-state current:12.0 mA at 30 V DC
-
Nominal input impedance:3 kΩ
-
Input-group/backplane test:1200 V AC for 1 s or 1697 V DC for 1 s
-
Working isolation voltage:75 V DC, IEC Class 2 reinforced insulation
-
Input data allocation:One read-only word; bits 0–15
-
Maximum heat dissipation at 30 V:5.4 W
-
Maximum heat dissipation at 26.4 V:4.3 W
-
Operating temperature:−20 to +65 °C; simultaneous-point derating applies
-
Nonoperating temperature:−40 to +85 °C
-
Relative humidity:5–95%, non-condensing
-
Maximum operating altitude:2000 m
-
Operating vibration:5 g, 10–500 Hz
-
Operating shock:30 g
-
Nonoperating shock:50 g panel-mounted; 40 g DIN-mounted
-
Terminal screw torque:0.90 N·m
-
Solid conductor range:0.34–2.5 mm² copper, 90 °C
-
Stranded conductor range:0.34–1.5 mm² copper, 90 °C
-
Required ventilation space:50.8 mm on all sides of the assembly
-
Mounting orientation:Horizontal only
-
Protection rating:IP20; installation enclosure required
-
Pollution degree:2
-
Overvoltage category:II
-
ESD immunity:4 kV contact/indirect; 8 kV air
-
Radiated RF immunity:10 V/m, 80–2700 MHz, 80% AM at 1 kHz
-
EFT immunity, signal ports:±2 kV at 5 kHz
-
Surge immunity, signal ports:±1 kV differential; ±2 kV common mode
-
Conducted RF immunity:10 V rms, 150 kHz–80 MHz, 80% AM at 1 kHz
Information
- Allen-Bradley 1762-IQ16 converts field switching states into a controller input word. Separate common groups allow circuit references to be planned by bank, while correct polarity, input duration and thermal loading determine whether the application receives reliable state changes.
State visibility: Input indication supports comparison of field conditions with the controller data image.
Integration discipline: Electrical thresholds, input filtering and controller execution must be assessed together.
Input data is presented as a read-only word whose bits follow the physical terminal numbers. Expansion position is part of the address, so moving a module can change the meaning of existing logic even when all its field wires remain attached. Match the retained hardware configuration before commissioning.
The upper operating temperature is not an unconditional all-inputs-on rating. Input voltage and simultaneous active points determine the thermal allowance. Budget expansion-bus demand separately from field-device current, and allow for controller scan timing when assessing short sensor pulses.
1762-IQ16 Official Installation Instructions Excerpt
Original English module identification, mounting, field wiring, input addressing and electrical/environmental specifications. PDF · 9 pages.1762-IQ16 Installation & Verification Guide
Apter Power commissioning workbook for common-group mapping, sensor checks, addressing, timing and restored-input acceptance. PDF · 5 pages.
Application scope: Application scope: These examples concern ordinary discrete monitoring. The module is not a safety-rated input, and filtered process inputs should not be assumed to capture high-speed pulses.
Machine status acquisition
Read compatible limit switches and auxiliary contacts, with the approved field supply and common path assigned to each input bank.Powered sensor interfaces
Connect compatible sourcing or sinking DC sensors after checking off-state leakage and on-state voltage at the input terminals.Sequence supervision
Observe discrete conditions used by the controller sequence. Include input delay and scan timing in the minimum event-duration assessment.Existing MicroLogix expansion
Restore or extend a supported station only after checking the installed module position, bus-current budget and thermal input allowance.
s
e
e
s
e
e
Alternative Names
Technical notes
Common-group boundary: Inputs 0–7 share the first bank; inputs 8–15 share the second. A missing common can affect a complete bank. Channel-level isolation must not be inferred from group isolation.
Pulse recognition: The module delay is only one part of the observation path. A field pulse must remain valid long enough for both the input circuit and the controller program to observe it.
Terminal work: Keep the fingersafe cover in place while wiring, secure the conductor under the pressure plate and apply the specified terminal torque. Inspect for loose strands before energization.
Thermal demand: At 26.4 V DC, the all-on allowance extends to 55 °C and decreases to 12 points at 65 °C. At 30 V DC, the chart permits 16 points at 30 °C, 10 at 55 °C and 8 at 65 °C. Use actual simultaneous states, not the average duty cycle.
FAQ View All FAQ
-
Why might a two-wire sensor keep an input of 1762-IQ16 on after the sensor switches off?Residual sensor current or an added indicator can keep the input above its off-state limits. Measure the actual off-state voltage and current with the sensor connected; select a compatible interface instead of assuming that a nominal 24 V sensor is suitable.
-
Would a 4 ms pulse be reliably captured by 1762-IQ16?Not from the module rating alone. The specified input on-delay can be as long as 8 ms, and controller scan timing adds another observation constraint. Use an approved pulse-capture or high-speed input solution when the event duration cannot satisfy the complete timing path.
-
Can sixteen active inputs remain on 1762-IQ16 at 26.4 V DC and 65 °C?No. The thermal chart permits twelve simultaneous points at that condition. Reduce the active-point load or change the approved thermal arrangement; do not average short inactive periods to justify an excessive simultaneous load.
-
What can explain a whole bank of 1762-IQ16 changing state together?Investigate the bank common, shared field supply and common wiring before suspecting eight independent sensor faults. Compare terminals 0–7 or 8–15 as a group, then check individual branches under controlled conditions.
-
Why can moving 1762-IQ16 one expansion position change which machine function responds?The expansion slot forms part of the controller input address. The terminal number still identifies the bit, but its slot prefix changes. Update and verify the hardware configuration and program references before returning the machine to service.
-
Does the 70 mA bus demand of 1762-IQ16 include its connected field sensors?No. That value is the module load on the 5 V expansion bus. Sensor and input-circuit demand belongs in the external field-supply budget. Calculate the two power paths separately and include all installed modules and devices.
-
Can an input-group isolation rating make 1762-IQ16 suitable for a 120 V AC field signal?No. The input is intended for the specified DC switching range. Dielectric test and working-isolation values do not expand its signal range; use a correctly rated input or approved interface for a different signal type.
-
Why should the protective debris strip be removed before operating 1762-IQ16?It protects the module during nearby mounting and wiring work, but leaving it in place restricts ventilation. Finish the work, inspect for wire strands or metal debris, and remove the strip before controlled energization.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.










