Completes the CEX-Bus physical layer at the end of an AC 800M communication chain so the bus maintains its intended electrical termination.
- Signal or energy path: The device is a passive end-of-line accessory; it does not measure a process variable or execute control logic.
- Companion components: Install it only at the documented final bus position with the approved controller communication unit, connector chain and cabinet hardware.
- Engineering check: Verify bus order, connector seating, screw retention, cable continuity and the absence of an unintended second termination.
- System boundary: Only the documented end of the CEX-Bus chain is to be terminated; an additional terminator can disrupt communication.
AC 800M controller cabinets and System 800xA communication-bus installations.
Important Notice: Verify the complete TB850 3BSC950193R1 nameplate, installed-system documentation, companion hardware and current ABB instructions before installation or replacement.
Apter Power TB850 3BSC950193R1 Manuals and Guides
Important Notice: The first link is the product-parameters PDF prepared only from the cited manufacturer information; the second link is the Apter Power product manual. Confirm the physical nameplate, current manufacturer documents, and host-system requirements before installation or replacement.
CEX-Bus end termination
Installed on the last unit of an AC 800M CEX-Bus, exactly as required by ABB.
BC810 interconnection assemblies
Used as one of the two TB850 terminators supplied in ABB's BC810K02 CEX-Bus interconnection package.
BC820 redundant-controller interconnection
Used as one of the two TB850 terminators supplied in ABB's BC820K02 CEX-Bus interconnection package.
System 800xA or Compact AC 800M cabinets
Provides the specified end termination in controller communication-bus layouts; it is not an I/O module.
Read and follow the current ABB documentation and host-equipment instructions before work. Verify the complete physical nameplate and system configuration.
1
Verify both TB850 and article number 3BSC950193R1 on the physical label before installation.
2
Install the TB850 only at the last unit on the CEX-Bus, as ABB explicitly requires.
3
Do not substitute TB851: TB850 is DB25P male, while ABB lists TB851 as DB25S female for a different termination position/topology.
4
Secure the screw fixing and inspect the DB25 connector for damage before energizing the controller system.
5
Follow the current ABB AC 800M hardware manual and the project-specific CEX-Bus topology; do not add extra terminators or omit the required end terminator.