Product Describe:

Siemens 6ES7952-1AM00-0AA0 is a long-design 4 MB RAM memory card for SIMATIC S7-400 load-memory applications with host-dependent backup.
  • Manufacturer part number
    6ES7952-1AM00-0AA0
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    0.7cm x 8.6cm x 5.6cm
  • Country of Origin
    Germany
Get a quick price for 6ES7952-1AM00-0AA0
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the complete 6ES7952-1AM00-0AA0 marking, revision and installed SIMATIC S7-400 configuration with your enquiry.

  • 1

    Confirm the offer

    Review the condition, included items and dispatch date. Confirm the RAM card only, application contents and host backup arrangement; CPU and batteries are separate.

  • 2

    Arrange dispatch

    Confirm delivery details and receive the tracking reference when the shipment is arranged.

  • Match the complete marking

    Include 6ES7952-1AM00-0AA0 and the visible revision or assembly identity in your enquiry. Keep the complete reference on the quotation.

  • Check the offered item before ordering

    Request available label and connector photos. Have your maintenance team compare the offered 6ES7952-1AM00-0AA0 with the installed equipment and applicable Siemens documentation.

Technical specifications for 6ES7952-1AM00-0AA0

  • Manufacturer:
    Siemens
  • Product Category:
    PLC Systems
  • Spare Part Number:
    6ES7952-1AM00-0AA0
  • Weight:
    0.0441 lbs (0.02 kg)
  • Tariff Code:
    8537101190
  • Product type:
    MC 952 memory card
  • System:
    SIMATIC S7-400
  • Memory technology:
    RAM
  • Capacity:
    4 Mbytes
  • Design:
    Long design
  • Operating current:
    45 mA typical; 100 mA maximum at 5 V
  • Backup current:
    5 µA typical; 60 µA maximum
  • Storage behavior:
    RAM retention depends on the host backup arrangement

Information

Overview Downloads Applications / Compatibility Product Precautions
  • Siemens 6ES7952-1AM00-0AA0. RAM-card replacement is a memory-retention task as well as a hardware match; keep the application archive and backup-power arrangement together.
Product type: MC 952 memory card
System: SIMATIC S7-400
Memory technology: RAM
Capacity: 4 Mbytes
The long-design MC 952 card provides 4 Mbytes of RAM for the S7-400 platform. RAM is volatile storage, so its behavior during loss of system power depends on the host backup arrangement. It must not be treated as a nonvolatile Flash card solely because the capacity matches.

For this card the MC 952 technical table gives 45 mA typical and 100 mA maximum operating current at 5 V. Backup current is 5 µA typical and 60 µA maximum. These are card values and must be considered within the installed CPU backup design.

Keep a verified program and data archive before a planned power interruption or card replacement. Check the CPU load-memory requirements separately from its work-memory capacity. Commissioning must confirm the expected application, retained data and diagnostic state with the actual host CPU.
Controller platform reference: Siemens SIMATIC S7-400.
Technical downloads for Siemens 6ES7952-1AM00-0AA0: a Siemens technical reference and an Apter Power installation and commissioning guide.
The technical reference preserves Siemens technical pages. The installation guide is prepared by Apter Power for planning and verification. Apply the complete Siemens and machine procedures during work.
Apply the approved SIMATIC S7-400 maintenance procedure and verify the following model-specific conditions before release.
Protect RAM retention

This MC 952 card uses RAM. Retention through a supply interruption depends on the actual host backup arrangement.

Verify the host CPU

The complete order number identifies a long-design 4 Mbyte RAM card for the SIMATIC S7-400 family. Verify support for the actual CPU.

Budget operating current

At 5 V the card draws 45 mA typically, with a maximum of 100 mA.

Check backup demand

The technical table specifies 5 µA typical and 60 µA maximum. Include the card in the host backup-current calculation.

Retain a safe application archive

RAM requires retention power. Record the installed CPU backup method and maintain an independent application archive before power interruption or replacement.

Keep card and CPU memory distinct

The 4 Mbyte value describes the card capacity. CPU work-memory partitions and supported load-memory configuration are separate specifications.

Alternative Names

6ES79521AM000AA0 Siemens 6ES7952-1AM00-0AA0

Technical notes

System relationship: RAM-card replacement is a memory-retention task as well as a hardware match; keep the application archive and backup-power arrangement together.

Configuration boundary: No. This card is RAM. A Flash EPROM card has different retention and program-storage behavior, even where the nominal capacity is the same.

Technical reference: Siemens 6ES7952-1AM00-0AA0 Data Sheet; S7-400 Automation System CPU Specifications, A5E00267840-03. Technical values apply to the complete 6ES7952-1AM00-0AA0 execution. The card current values use the exact MC 952 order-number entry in the S7-400 CPU specifications.

FAQ View All FAQ

  • Is the storage in 6ES7952-1AM00-0AA0 volatile?
    Yes. This MC 952 card uses RAM. Retention through a supply interruption depends on the actual host backup arrangement.
  • Which controller family uses 6ES7952-1AM00-0AA0?
    The complete order number identifies a long-design 4 Mbyte RAM card for the SIMATIC S7-400 family. Verify support for the actual CPU.
  • What is the operating-current budget for 6ES7952-1AM00-0AA0?
    At 5 V the card draws 45 mA typically, with a maximum of 100 mA.
  • How much backup current is specified for 6ES7952-1AM00-0AA0?
    The technical table specifies 5 µA typical and 60 µA maximum. Include the card in the host backup-current calculation.
  • Why should the backup arrangement be checked with 6ES7952-1AM00-0AA0?
    RAM requires retention power. Record the installed CPU backup method and maintain an independent application archive before power interruption or replacement.
  • Does the 4 Mbyte rating of 6ES7952-1AM00-0AA0 describe CPU working memory?
    No. It describes the card capacity. The CPU work-memory partitions and supported load-memory configuration are separate specifications.
  • What must be checked after loading 6ES7952-1AM00-0AA0?
    Confirm that the intended program and data are present, the hardware configuration matches the installed controller and diagnostics allow the planned startup.
  • Is 6ES7952-1AM00-0AA0 the same storage execution as a Flash EPROM card?
    No. This card is RAM. A Flash EPROM card has different retention and program-storage behavior, even where the nominal capacity is the same.
Related reading

Related cases and sourcing guidance

View all case studies