Technical specifications for 6ES7952-1AM00-0AA0
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES7952-1AM00-0AA0
-
Weight:0.0441 lbs (0.02 kg)
-
Tariff Code:8537101190
-
Product type:MC 952 memory card
-
System:SIMATIC S7-400
-
Memory technology:RAM
-
Capacity:4 Mbytes
-
Design:Long design
-
Operating current:45 mA typical; 100 mA maximum at 5 V
-
Backup current:5 µA typical; 60 µA maximum
-
Storage behavior:RAM retention depends on the host backup arrangement
Information
- Siemens 6ES7952-1AM00-0AA0. RAM-card replacement is a memory-retention task as well as a hardware match; keep the application archive and backup-power arrangement together.
System: SIMATIC S7-400
Memory technology: RAM
Capacity: 4 Mbytes
For this card the MC 952 technical table gives 45 mA typical and 100 mA maximum operating current at 5 V. Backup current is 5 µA typical and 60 µA maximum. These are card values and must be considered within the installed CPU backup design.
Keep a verified program and data archive before a planned power interruption or card replacement. Check the CPU load-memory requirements separately from its work-memory capacity. Commissioning must confirm the expected application, retained data and diagnostic state with the actual host CPU.
-
Siemens 6ES7952-1AM00-0AA0 technical reference
Original manufacturer data sheet - PDF, 2 pages. Exact-model technical characteristics and manufacturer product identification. -
Siemens 6ES7952-1AM00-0AA0 installation guide
Prepared by Apter Power - PDF, 5 pages. Installed-system review, configuration checks, commissioning and handover.
Configuration scope: Technical values apply to the complete 6ES7952-1AM00-0AA0 execution. The card current values use the exact MC 952 order-number entry in the S7-400 CPU specifications.
-
RAM load-memory expansion
Use this RAM card within a supported S7-400 load-memory configuration. Confirm the long-design card identity and the actual CPU support before installation. -
Retention-power assessment
Include the memory card in the installed CPU backup calculation. Retention during supply interruption depends on the complete host backup arrangement. -
Application recovery planning
Keep an independent application archive when preparing RAM-card replacement. Verify the restored program, retained data and diagnostics before returning the controller to service. -
Host memory coordination
Review card load memory and CPU work memory as separate resources. Match the application requirements to the installed CPU configuration and supported card capacity.
This MC 952 card uses RAM. Retention through a supply interruption depends on the actual host backup arrangement.
The complete order number identifies a long-design 4 Mbyte RAM card for the SIMATIC S7-400 family. Verify support for the actual CPU.
At 5 V the card draws 45 mA typically, with a maximum of 100 mA.
The technical table specifies 5 µA typical and 60 µA maximum. Include the card in the host backup-current calculation.
RAM requires retention power. Record the installed CPU backup method and maintain an independent application archive before power interruption or replacement.
The 4 Mbyte value describes the card capacity. CPU work-memory partitions and supported load-memory configuration are separate specifications.
Alternative Names
Technical notes
System relationship: RAM-card replacement is a memory-retention task as well as a hardware match; keep the application archive and backup-power arrangement together.
Configuration boundary: No. This card is RAM. A Flash EPROM card has different retention and program-storage behavior, even where the nominal capacity is the same.
Technical reference: Siemens 6ES7952-1AM00-0AA0 Data Sheet; S7-400 Automation System CPU Specifications, A5E00267840-03. Technical values apply to the complete 6ES7952-1AM00-0AA0 execution. The card current values use the exact MC 952 order-number entry in the S7-400 CPU specifications.
FAQ View All FAQ
-
Is the storage in 6ES7952-1AM00-0AA0 volatile?Yes. This MC 952 card uses RAM. Retention through a supply interruption depends on the actual host backup arrangement.
-
Which controller family uses 6ES7952-1AM00-0AA0?The complete order number identifies a long-design 4 Mbyte RAM card for the SIMATIC S7-400 family. Verify support for the actual CPU.
-
What is the operating-current budget for 6ES7952-1AM00-0AA0?At 5 V the card draws 45 mA typically, with a maximum of 100 mA.
-
How much backup current is specified for 6ES7952-1AM00-0AA0?The technical table specifies 5 µA typical and 60 µA maximum. Include the card in the host backup-current calculation.
-
Why should the backup arrangement be checked with 6ES7952-1AM00-0AA0?RAM requires retention power. Record the installed CPU backup method and maintain an independent application archive before power interruption or replacement.
-
Does the 4 Mbyte rating of 6ES7952-1AM00-0AA0 describe CPU working memory?No. It describes the card capacity. The CPU work-memory partitions and supported load-memory configuration are separate specifications.
-
What must be checked after loading 6ES7952-1AM00-0AA0?Confirm that the intended program and data are present, the hardware configuration matches the installed controller and diagnostics allow the planned startup.
-
Is 6ES7952-1AM00-0AA0 the same storage execution as a Flash EPROM card?No. This card is RAM. A Flash EPROM card has different retention and program-storage behavior, even where the nominal capacity is the same.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.