Match the complete marking
Include 6ES5470-4UC12 and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 6ES5470-4UC12 with the installed equipment and applicable Siemens documentation.
Technical specifications for 6ES5470-4UC12
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES5470-4UC12
-
Weight:0.48 kg
-
Tariff Code:8537101190
-
System family:SIMATIC S5
-
Module function:Analog output
-
Output channels:8
-
Voltage output range:1–5 V
-
Current output range:4–20 mA, parallel with voltage output
-
Value representation:12-bit two's complement
-
Nominal command scale:0–1024 units for 4UC variant
-
Output delay:≤1 ms after data transfer
-
Voltage-mode load:≥3.3 kΩ; maximum output current 3 mA
-
Current-mode load:≤300 Ω
-
Operating error:±0.6% over 0–60 °C
-
Capacitive load:<100 nF including line capacitance
Information
- Siemens 6ES5470-4UC12 converts controller output values into continuous process signals. Its voltage and current connections require the corresponding load and reference-potential arrangement.
Output channels: 8
Signal ranges: 1–5 V and 4–20 mA
The output-value representation is 12-bit two's complement. The common 470 specification gives a delay of no more than 1 ms from data transfer to the analog output, and an operating error limit of ±0.6% over 0–60 °C. The eight outputs share the external reference Mext; isolation does not mean separate isolation between individual channels.
For voltage operation, the load resistance must be at least 3.3 kΩ and output current must not exceed 3 mA. Current-output loads must not exceed 300 Ω; the maximum no-load voltage is 18 V. Keep total capacitive loading below 100 nF and check the front-connector assignment, module enable and installed address before reconnecting process wiring.
-
Siemens 6ES5470-4UC12 technical reference
Original Siemens excerpt - PDF, 3 pages, 122.0 KB. The 470-4UC12 output ranges apply to this order code; shared 470 module specifications retain their stated load and operating conditions. -
Siemens 6ES5470-4UC12 installation planning guide
Prepared by Apter Power - PDF, 5 pages, 96.8 KB. Identity, configuration, connection and controlled acceptance planning.
Platform applications: The following applications describe SIMATIC S5 functions. Match the complete 6ES5470-4UC12 identity to the installed system before selecting a replacement.
-
Process setpoints
Use the 1–5 V outputs for compatible process interfaces while preserving the controller scale and reference potential. -
Current-loop commands
Use the 4–20 mA connections with loads within 300 Ω and verify the receiving device range. -
S5 maintenance
Retain the complete 4UC12 order code, rack arrangement and existing program addressing during replacement. -
Loop verification
Check command-to-output response at controlled test points before releasing the connected process.
Place the machine in a safe state and isolate power before handling the module or front connector.
Use the complete 6ES5470-4UC12 reference; other 470 suffixes have different output ranges.
Keep voltage loads at or above 3.3 kΩ and current loads at or below 300 Ω.
Check Mext and the front-connector wiring. The eight outputs are not individually isolated channels.
Record the address and output scaling before removal; verify them against the installed S5 application.
Apply controlled output commands and confirm the receiving equipment response before restoring normal operation.
Alternative Names
Technical notes
Installation relationship: The output-value representation is 12-bit two's complement. The common 470 specification gives a delay of no more than 1 ms from data transfer to the analog output, and an operating error limit of ±0.6% over 0–60 °C. The eight outputs share the external reference Mext; isolation does not mean separate isolation between individual channels.
Configuration: The 470-4UC12 output ranges apply to this order code; shared 470 module specifications retain their stated load and operating conditions.
Technical reference: Siemens SIMATIC S5 analog input/output module instructions, C79000-B8576-C300-06.
FAQ View All FAQ
-
How many output channels does 6ES5470-4UC12 provide?It provides eight analog output channels with voltage and current output connections.
-
Which signal ranges apply to 6ES5470-4UC12?The 4UC12 variant provides 1–5 V and 4–20 mA in parallel; the nominal command scale is 0–1024 units.
-
How are output values represented by 6ES5470-4UC12?The module uses a 12-bit two's-complement representation. Preserve the installed program scaling.
-
What voltage-mode load is required for 6ES5470-4UC12?Use a load of at least 3.3 kΩ and observe the maximum voltage-output current of 3 mA.
-
What current-mode load can 6ES5470-4UC12 drive?The specified load resistance is no more than 300 Ω; maximum no-load voltage is 18 V.
-
How quickly does 6ES5470-4UC12 update its analog output?The specified delay between data transfer and analog output is no more than 1 ms.
-
Are the channels of 6ES5470-4UC12 individually isolated?The eight outputs use the common external reference Mext. Do not interpret the module isolation specification as individual channel isolation.
-
What accuracy condition applies to 6ES5470-4UC12?The operating error limit is ±0.6% over 0–60 °C. Correct load, wiring and scaling remain necessary.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.