Match the complete marking
Match the complete Siemens 6GK7342-5DA02-0XE0 marking and installed configuration. Compare the DA02 order code, firmware marking, RS-485 connector and mode switch.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 6GK7342-5DA02-0XE0 with the installed equipment and applicable Siemens documents.
Technical specifications for 6GK7342-5DA02-0XE0
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6GK7342-5DA02-0XE0
-
Weight:0.26 kg
-
Tariff Code:8537101190
-
PROFIBUS interface:RS-485; 9-pin D-sub female
-
Transmission rates:9.6 kbit/s to 12 Mbit/s; discrete configured rates
-
DP slaves as master:124 maximum
-
Master input / output area:2160 bytes each
-
Data per slave as master:244 input bytes / 244 output bytes maximum
-
DP slave input / output area:240 bytes each
-
Supply:24 V DC
-
Typical supply current:0.25 A at 24 V
-
Typical backplane current:150 mA
-
Power loss:6 W
Information
- Siemens 6GK7342-5DA02-0XE0 handles the fieldbus exchange separately from CPU program execution. Correct data consistency depends on the configured DP role, buffer lengths and repeated processing of the communication blocks.
Service selection: DP, S7 communication and FDL connections
Engineering workflow: STEP 7 configuration and NCM diagnostics
DP_SEND and DP_RECV exchange the CPU buffers with the communication processor. Transfers larger than a single block segment require repeated block calls, so the bus transmission speed alone does not determine application response. The CPU scan, competing services and consistent treatment of returned status must also be considered.
The DA02 version can act as a DP slave but does not accept slave-mode SYNC/FREEZE. A later DA03 has different capabilities and block behavior. Preserve the configured role and evaluate any replacement against the application program rather than assuming that all CP342-5 versions are interchangeable.
6GK7342-5DA02-0XE0 Original Technical Excerpt
Siemens CP 342-5 / CP 342-5 FO Manual, C79000-G8976-C146/01. Selected original pages retain the relevant technical context. PDF · 10 pages.6GK7342-5DA02-0XE0 Installation & Verification Guide
Apter Power installation workbook covering capture the bus assignment, confirm the rack path, restore fieldbus wiring, validation and handover. PDF · 5 pages.
Application scope: These applications describe the intended system function. Select the actual configuration for that function; accessories are included only when itemized.
Distributed I/O master
Exchange configured process buffers with PROFIBUS DP slaves in an S7-300 system.Subordinate controller interface
Present a defined slave I/O area to a higher-level DP master.S7 station communication
Use configured S7 connections while accounting for combined communication workload.Legacy electrical bus service
Maintain a copper PROFIBUS segment with the correct termination and supported baud rate.
Save the STEP 7 station and network configuration. Record the PROFIBUS address, rate, DP role, I/O buffer lengths and connections. Identify the CPU blocks that exchange data and establish a controlled process state before disconnecting a live segment.
Isolate the station supply and verify the target rack carries the S7 communication bus. Inspect the interconnector and power terminals; do not place the CP behind an IM365 expansion link. Retain the approved reference-potential grounding arrangement.
Trace A/B conductors, shield connection and termination at the segment ends. Reconnect the electrical bus without changing node addresses on neighboring stations. Review cable length against the configured transmission speed.
Restore the correct configuration through an available engineering path; use MPI for changed bus parameters. Run the approved application and inspect communication-block completion and status. Exercise more than one buffer segment where the configured transfer requires it.
Compare received values with field conditions and confirm output response under controlled demand. Check recovery following the approved communication fault test, then retain the final CPU/CP configuration and diagnostics.
Retain the final tested settings, physical connections and accepted operating response for 6GK7342-5DA02-0XE0.
Alternative Names
Technical notes
Consistent buffers: Treat CPU data-area updates and communication-block completion as one application design problem. Partial updates can produce inconsistent process information.
Electrical segment: A/B assignment, shield bonding and termination belong to the entire RS-485 segment. Check both ends before blaming the CP for communication errors.
Version-sensitive behavior: Retain the DA02 identity when reviewing slave functions and application blocks; later DA03 features do not retroactively change this hardware.
FAQ View All FAQ
-
Why does raising the bus rate on 6GK7342-5DA02-0XE0 not guarantee a shorter CPU response?The CPU must still execute DP_SEND and DP_RECV. Segmented transfers, scan time and concurrent services contribute to the complete response.
-
Can 6GK7342-5DA02-0XE0 be installed behind an IM365 expansion connection?No. The IM365 does not route the communication bus required by this CP; use a supported rack arrangement.
-
When can 6GK7342-5DA02-0XE0 be replaced without downloading from a programming device?When CP configuration is stored in the CPU and retained in its load memory. Verify that the retained configuration corresponds to the replacement execution.
-
Why may a bus-parameter download to 6GK7342-5DA02-0XE0 require MPI?Changed bus parameters can disrupt the PROFIBUS path used for the download. The DA02 procedure uses MPI for this change.
-
How should large data buffers be handled with 6GK7342-5DA02-0XE0?Continue the prescribed communication-block calls until the segmented exchange completes, and evaluate status rather than treating one call as a completed large transfer.
-
Does the slave behavior of 6GK7342-5DA02-0XE0 match every later CP342-5 version?No. In particular, DA02 slave mode does not support SYNC/FREEZE. Review role-dependent behavior and block compatibility during migration.
-
What can be lost when a CPU retaining 6GK7342-5DA02-0XE0 configuration loses backup power?Configuration stored only in volatile load memory can be lost. Verify battery-backed or nonvolatile retention before relying on automatic replacement loading.
-
How can the wrong GSD affect a slave application using 6GK7342-5DA02-0XE0?An incorrect device description can create mismatched identification and I/O lengths. Match the electrical CP execution and the configured input/output areas.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studies-
Bently Nevada Cables and Proximitors Delivered to DubaiRead case > -
GE IS420UCSBH4A: Confirm the Offered Controller and Release TermsRead case > -
Siemens TP1500 Comfort: Check the Panel and Machine ProjectRead case > -
24 Siemens Spare Parts Delivered to an Australian Waste Management FacilityRead case >