Technical specifications for 6DD1688-0AE0
-
Manufacturer:Siemens
-
Product Category:DCS Systems
-
Spare Part Number:6DD1688-0AE0
-
Weight:0.12 kg
-
Tariff Code:8537101190
-
Product series:SIMADYN D
-
Submodule designation:SS5
-
Support module:CS7
-
Bus protocol:PROFIBUS-FMS / SINEC L2-FMS
-
Bus role:Master interface
-
Electrical interface:Isolated RS485 at X5
-
OLM supply:Isolated 5 V at X5
-
Configuration tool:COMSS5
-
Host capacity:Up to 3 communications submodules per CS7
Information
- SS5 is distinct from the SS52 PROFIBUS-DP/MPI execution, so the bus protocol must be matched to the fitted submodule.
Product series: SIMADYN D
Submodule designation: SS5
The CS7 support module, communications submodule and selected receptacle are configured in HWConfig. Up to three communications submodules can be fitted to one CS7, while CPU data exchange uses the 16 kbyte dual-port RAM located on the support module. Connector X5 provides the electrically isolated RS485 PROFIBUS interface and an isolated 5 V supply for an Optical Link Module.
SS5 operation requires a COM database generated with COMSS5 and loaded into the submodule. The legacy tool runs on a suitable S5-DOS programmer or PC arrangement. The bus connector or terminal supplies switchable terminating resistors; cable layout and drop capacitance must suit the baud rate. Ground the cable screen over a large contact area at cabinet entry and preserve front-panel bonding to CS7. CS7 diagnostic LEDs distinguish missing database, initialization and bus activity.
-
Siemens 6DD1688-0AE0 technical reference
Original Siemens technical excerpt - PDF, 4 pages. Product-specific technical information and applicable configuration details. -
Siemens 6DD1688-0AE0 installation guide
Prepared by Apter Power - PDF, 5 pages. Model identification, interface checks, configuration review and commissioning verification.
Application scope: SS5-specific FMS data applies to 6DD1688-0AE0. The 16 kbyte dual-port memory belongs to CS7; SS52 DP/MPI and RS232 functions are separate.
-
FMS client/server communication
Provide the configured PROFIBUS-FMS master interface through the CS7 support module. -
Legacy bus integration
Connect compatible SINEC L2-FMS nodes with matched bus settings and termination. -
Optical-link arrangements
Use the isolated OLM supply and an appropriately configured optical bus arrangement where required. -
Communications restoration
Restore the COMSS5 database and validate initialization and the expected data exchange.
Match the SS5 FMS execution; do not substitute SS52 DP/MPI behavior.
Match the CS7 support, selected receptacle and HWConfig configuration.
Retain the COMSS5 database and verify bus termination, screen bonding and the X5 connection.
Check initialization and CS7 diagnostic indications, then validate the expected client/server data exchange.
Use the applicable isolation and electrostatic-discharge controls. Preserve connectors, identification and mechanical retention during handling.
Apply the approved site acceptance procedure and compare actual behavior with the recorded system configuration before returning equipment to service.
Alternative Names
Technical notes
System relationship: Match the CS7 support, selected receptacle and HWConfig configuration.
Applicability: SS5-specific FMS data applies to 6DD1688-0AE0. The 16 kbyte dual-port memory belongs to CS7; SS52 DP/MPI and RS232 functions are separate.
Technical reference: Siemens Hardware - SIMADYN D, Communications Support Modules, Edition 12/2004; 6DD1688-0AE0 product information.
FAQ View All FAQ
-
Which protocol does 6DD1688-0AE0 support?The SS5 execution provides a PROFIBUS-FMS / SINEC L2-FMS master interface.
-
Is 6DD1688-0AE0 the SS52 DP/MPI submodule?No. SS5 and SS52 have different protocol roles; the SS52 DP/MPI functions do not establish SS5 capability.
-
Which support module accepts 6DD1688-0AE0?It plugs into a CS7 communications support module.
-
How many communications submodules can share the CS7 used by 6DD1688-0AE0?Up to three can be fitted, with each receptacle configured appropriately.
-
Where is the dual-port RAM used by 6DD1688-0AE0?The 16 kbyte dual-port RAM used for CPU data exchange is on the CS7 support module.
-
Which interfaces are available at X5 on 6DD1688-0AE0?X5 provides isolated RS485 PROFIBUS and an isolated 5 V supply for an Optical Link Module.
-
Which configuration database does 6DD1688-0AE0 require?A COM database must be generated with COMSS5 and loaded into SS5.
-
How is bus readiness assessed for 6DD1688-0AE0?Use the associated CS7 LEDs to check initialization and database state, then verify actual bus activity and the configured data exchange.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.