Set W6 for DPU4E or DPU4A/B and confirm the corresponding address use.
Set W1 for the applicable 50 or 60 Hz environment.
Apply A–E input-type jumper positions for each selected signal form.
Check the system or field supply and independently fuse redundant transmitter feeds.
Use the documented external 100-ohm shunts for redundant common-transmitter wiring.
After power-up, confirm Active indication and resolve any coded A/D or calibration fault.
Operating mode: DPU4E uses two addresses and 16 channels; DPU4A/B uses 16 addresses and 15 channels.
Signal setup: Configure each channel’s A–E jumpers for its current or voltage input and supply path.
Technical reference: Metso Automation MAX Controls maxPAC Hardware Reference Guide, 277596.