Speak to a sourcing specialist
sales13@apterpower.com

IOP302

4-20 mA Analog Input Module
In Stock
Ships by Tuesday, November 10
Fast Shipping Available
Metso Automation IOP302 analog input module, angled view with perforated black cover and front terminals
Metso Automation IOP302 input module, underside view of green circuit board with gold edge connector
Metso Automation IOP302 analog input module, close-up of Metso label with model and part number
Metso Automation IOP302 analog input module, angled view with perforated black cover and front terminals
Metso Automation IOP302 input module, underside view of green circuit board with gold edge connector
Metso Automation IOP302 analog input module, close-up of Metso label with model and part number
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

Metso IOP302 is a maxPAC common analog input module that accepts sixteen 4-20 mA channels. It supplies individually fused 24 V transmitter loop power through the backplane and transfers converted input data to the DPU.
Get a quick price for IOP302
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for IOP302

  • Manufacturer:
    Metso Auttomation
  • Product Category:
    DCS Systems
  • Spare Part Number:
    IOP302
  • Estimated shipping dimensions:
    4.4x31.5x25.6cm
  • Weight:
    0.62 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Module type:
    4-20 mA common analog input module
  • Input channels:
    16 common current-input channels
  • Input span:
    4 to 20 mA
  • Transmitter loop supply:
    24 V from the backplane, individually fused per channel
  • DPU4A/B mode:
    16 addresses and 15 available channels
  • DPU4E mode:
    2 addresses and 16 available channels
  • Frequency-selection jumper:
    W1 installed for 50 Hz; removed for 60 Hz
  • DPU-selection jumper:
    W6 installed for DPU4A/B; removed for DPU4E
  • Conversion method:
    Sigma-delta oversampling with one A/D per channel
  • Resolution:
    15 bits plus sign
  • Scan rate:
    20 ms
  • Accuracy:
    ±0.1% of reading at 25 °C
  • Input impedance:
    300 ohms
  • Normal-mode voltage:
    50 V
  • Normal-mode rejection:
    60 dB at 50/60 Hz
  • Input power:
    125 mA from the 24 V system supply
  • Calibration:
    Self-calibration at power-up and periodically online
  • Field connectors:
    P2 for channels 1-8; P3 for channels 9-16

Information

Overview Manuals Common Applications Product Precautions
Within a maxPAC input subsystem, Metso IOP302 conditions current-loop signals, performs channel conversion and delivers the resulting data to the selected DPU architecture.
  • Sixteen common 4-20 mA analog input channels
  • Individually fused 24 V transmitter loop power
  • DPU4A/B and DPU4E operating modes selected by jumper
  • Power-up diagnostics with periodic online self-calibration

The installed DPU determines the address and channel arrangement: DPU4A/B operation uses sixteen addresses for fifteen channels, while DPU4E operation uses two addresses for all sixteen channels. The W1 and W6 jumpers, P2/P3 field connections, loop-power path and bus position must therefore be preserved during replacement. Commissioning should confirm the Active LED state, diagnostic codes, channel readings and the intended 50/60 Hz rejection setting.

Important Notice: Confirm the complete IOP302 marking, installed DPU type, W1/W6 jumper positions and every P2/P3 field connection before energization.

Metso IOP302 Manuals & Downloads
Metso IOP302 Official Technical Reference Excerpt (PDF)Metso IOP302 Installation & Commissioning Guide (PDF)

The first document contains the applicable manufacturer reference pages for this exact product; the second organizes preparation, wiring, diagnostics and handover checks.

Sixteen-loop current acquisition
Collects sixteen common 4-20 mA field signals through one maxPAC analog input module.
DPU4E input expansion
Provides all sixteen channels while occupying two bus addresses in the documented DPU4E mode.
DPU4A/B cabinet service
Supports the legacy operating mode with fifteen available channels and sixteen assigned addresses.
Controlled analog-module replacement
Restores recorded jumper, address and P2/P3 wiring arrangements before functional testing.
Read the applicable Metso instructions before work. Verify IOP302 and the installed system configuration before isolation or replacement.
1
Record the complete Metso IOP302 marking, rack position and DPU type.
2
Place every connected 4-20 mA loop and the controller in the approved maintenance state.
3
Isolate the 24 V system and transmitter-loop supplies before moving field wiring.
4
Label all P2 and P3 conductors so channels 1-16 retain their recorded assignments.
5
Match W6 to DPU4A/B or DPU4E operation and restore the correct bus-address plan.
6
Set W1 for the installed 50 Hz or 60 Hz rejection requirement.
7
Inspect the individually fused loop-power paths, connectors and channel wiring before energization.
8
Review the Active LED, diagnostic code behavior and every used channel value before release.

Technical notes

IOP302 uses one sigma-delta converter per channel with 15-bit-plus-sign resolution and a 20 ms scan rate. Published performance includes ±0.1% accuracy at 25 °C, 300 Ω input impedance and 60 dB normal-mode rejection at 50/60 Hz. The module draws 125 mA from the 24 V system supply, so subsystem power budgeting should include that load separately from field-transmitter demand.

FAQ View All FAQ

  • How many current inputs does Metso IOP302 provide?
    Metso IOP302 provides sixteen common 4-20 mA analog input channels in its DPU4E operating mode.
  • Which address arrangement applies when Metso IOP302 operates with DPU4A/B?
    The DPU4A/B configuration assigns sixteen addresses to Metso IOP302 and makes fifteen input channels available.
  • What changes when Metso IOP302 is configured for DPU4E?
    DPU4E operation reduces the Metso IOP302 address requirement to two while enabling all sixteen channels.
  • How does jumper W6 configure Metso IOP302?
    Jumper W6 selects the DPU interface: the installed position is for DPU4A/B, and the removed position is for DPU4E.
  • Which frequency setting is controlled by W1 on Metso IOP302?
    W1 configures Metso IOP302 for 50 Hz rejection when installed and for 60 Hz rejection when removed.
  • How is transmitter loop power distributed by Metso IOP302?
    The backplane supplies 24 V transmitter power to Metso IOP302, and an individual electronic fuse protects each channel's loop-power path.
  • What conversion performance is specified for Metso IOP302?
    Metso IOP302 uses sigma-delta oversampling with one A/D per channel, 15-bit-plus-sign resolution and a 20 ms scan rate.
  • Which checks complete commissioning of Metso IOP302?
    Commissioning should confirm the DPU mode, W1/W6 positions, P2/P3 channel mapping, Active LED behavior, diagnostic status and every used 4-20 mA input.