Select 16/32 input mode, range, units and active channels with the module de-energized.
Use 24 V DC +/-10% with 100 mA available for each module.
Ground the analog cable shield at the transmitter source, not at both ends.
Apply the manual's unused-channel wiring to reduce noise.
Route analog wiring away from motors, high-current switches and transformers.
Compare injected low, mid and high points with the PLC counts and selected data format.
Shared selection: Input range and units jumper selections apply to all enabled channels.
Scan behavior: One channel is supplied per CPU scan; disabling unused channels shortens the complete update cycle.
Diagnostic focus: Check RUN, TB, 24V, NEG and channel indicators together with injected signal values.