Product Describe:

Triconex 3601E is a 16-point, non-commoned triple-modular-redundant digital-output module for 115 V AC field loads in a Tricon system. It uses a separate external termination panel.
  • Manufacturer part number
    3601E
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    2.2cm × 40.8cm × 39.8cm
  • Country of Origin
    USA
Get a quick price for 3601E
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the complete 3601E marking, installed Tricon TMR controller / AC digital output configuration and relevant photos with your enquiry.
  • 1

    Confirm the offer

    Check that the quotation names 3601E and states the supplied module or terminal, revision and separately required accessories.
  • 2

    Arrange dispatch

    Confirm delivery details and receive tracking information when the shipment is arranged.
  • Match the complete marking

    Include 3601E and its visible revision or assembly identity in your enquiry. Keep the complete reference on the quotation.
  • Check the offered item before ordering

    Request available label and connector photos. Have your maintenance team compare the offered 3601E with the installed equipment and applicable Triconex documents.

Technical specifications for 3601E

  • Manufacturer:
    Invensys
  • Product Category:
    DCS Systems
  • Spare Part Number:
    3601E
  • Weight:
    2.84 kg
  • Tariff Code:
    8537101190
  • Product role:
    TMR 115 V AC digital-output module
  • Output points:
    16, non-commoned
  • Nominal field voltage:
    115 V AC
  • Operating field range:
    80–155 V AC
  • Frequency range:
    47–63 Hz
  • Maximum point current:
    2 A per output
  • Surge rating:
    12 A per cycle
  • Maximum load leakage:
    2 mA at 60 Hz
  • Maximum chassis leakage:
    4 mA at 60 Hz
  • Field fuse:
    3 A fast-acting per output, on termination
  • Point isolation:
    1500 V DC for 3601E
  • Module indicators:
    PASS, FAULT, ACTIVE
  • Field alarm:
    LOAD/FUSE
  • Termination:
    Separate external termination panel

Information

Overview Downloads Applications / Compatibility Product Precautions
  • Triconex 3601E. This Tricon output module votes three processor-channel commands into field switching for 16 separate 115 V AC loads.
Product role: TMR 115 V AC digital-output module
Output points: 16, non-commoned
Nominal field voltage: 115 V AC
Operating field range: 80–155 V AC
The 3601E is a TMR digital-output module with 16 non-commoned, optically isolated points. The Tricon backplane delivers each processor-channel command to the module, whose voter circuitry produces the output to a separate external termination panel. Field power is supplied at each termination point; the module is mechanically keyed for its configured chassis location and supports a hot spare in the documented architecture.

For 3601E, the product guide specifies 115 V AC nominal, an 80–155 V AC operating range and 47–63 Hz. Each point is rated at a maximum 2 A, with 12 A surge per cycle. A 3 A fast-acting fuse belongs at each field termination. The 3601E point-isolation figure is 1500 V DC; the higher 2500 V DC figure in the shared table is explicitly marked for 3601T.

A voltage-loopback circuit checks output-switch behavior against the command, and the LOAD/FUSE indication reports a field-voltage mismatch. PASS, FAULT and ACTIVE show module status; an indicated channel fault calls for diagnosis and does not alone prove complete module failure. Assess the 2 mA maximum load leakage and 4 mA chassis leakage at 60 Hz when selecting sensitive field devices.
Installed-system reference: Tricon TMR controller / AC digital output. Match the termination panel and 115 V AC field loads.
Technical downloads for Triconex 3601E: original manufacturer excerpt and an Apter Power installation and commissioning guide.
The technical excerpt reproduces selected Triconex source pages. The installation guide is prepared by Apter Power; verify the complete 3601E marking and apply the full manufacturer and site procedures.
Installation and commissioning checks for Triconex 3601E.
Isolate field power

Treat each 115 V AC output point as a separately powered circuit before handling the panel.

Match the E variant

Confirm 3601E and its configured chassis key; do not use 3601T isolation limits.

Check termination

Verify the external termination panel and backplane cable before commissioning.

Fit point fuses

Confirm one 3 A fast-acting fuse for each output on the field termination.

Assess the load

Keep steady and surge demand within 2 A per point and 12 A per cycle.

Prove diagnostics

Test commanded ON/OFF state, point indication and LOAD/FUSE alarms at the field device.

Alternative Names

Triconex 3601E

Technical notes

Output relationship: 3601E votes TMR commands for 16 non-commoned 115 V AC field points through an external termination panel.

Variant boundary: Use the 3601E 1500 V DC isolation value; the 2500 V DC footnote applies only to 3601T.

Technical reference: Triconex Technical Product Guide for Tricon Systems, 9791007-013.

FAQ View All FAQ

  • How many output points does Triconex 3601E provide?
    It has 16 non-commoned TMR digital-output points.
  • What field-voltage range applies to Triconex 3601E?
    The guide specifies 115 V AC nominal and an 80–155 V AC operating range at 47–63 Hz.
  • What current can each Triconex 3601E output carry?
    The maximum is 2 A per point, with a 12 A surge per cycle.
  • Where are the output fuses for Triconex 3601E?
    The field termination uses one 3 A fast-acting fuse per output.
  • What external termination does Triconex 3601E require?
    A separate external termination panel connects to the Tricon backplane through its cable interface.
  • What does the LOAD/FUSE indication mean on Triconex 3601E?
    It signals a mismatch between detected field voltage and the commanded output state.
  • What point-isolation value belongs to Triconex 3601E?
    The shared model table gives 1500 V DC for 3601E; the 2500 V DC footnote applies to 3601T.
  • How should a Triconex 3601E channel fault be interpreted?
    A FAULT indication calls for channel diagnosis; the guide distinguishes a channel fault from proof of a complete module failure.