Match the complete marking
Send the complete FBM207B marking, revision or option label, connector photographs and installed application details.
-
Check the offered item before ordering
Compare the offered FBM207B with the installed 16-channel 24 v dc contact-sense input module, termination hardware and approved Foxboro documentation before ordering.
Technical specifications for FBM207B
-
Manufacturer:Invensys
-
Product Category:DCS Systems
-
Spare Part Number:FBM207B
-
Weight:0.32 kg
-
Tariff Code:8537101190
-
Module designation:FBM207b
-
Input channels:16 isolated and independent
-
Input function:24 V DC contact sense
-
Open-circuit voltage:24 V DC ±15%
-
Short-circuit current:3.2 mA typical
-
ON-state resistance:1.0 kΩ maximum
-
OFF-state resistance:100 kΩ minimum
-
Input filter:None, 4, 8, 16 or 32 ms
-
Pulse-count rate:0 to 250 Hz without missing pulses
-
Fieldbus rate:2 Mbps redundant Module Fieldbus
-
Input voltage:24 V DC +5%, -10%
-
Power consumption:4 W
-
Channel isolation:600 V AC for one minute
-
Redundancy:Adjacent module pair with RH926ZY adapter
-
Operating temperature:-20 to +70 °C
-
Relative humidity:5–95%, non-condensing
Information
- Foxboro FBM207B is a sixteen-channel 24 V DC contact-sense input module for discrete status monitoring in the I/A Series control environment.
24 V DC sensing interface: Applies the documented discrete-input excitation and threshold arrangement.
Redundant-ready fieldbus role: Supports the approved system architecture while preserving channel-to-database mapping.
Use the verified technical rows below to screen the offer, then compare the installed drawing and manufacturer instructions. Input channels: 16; Nominal input class: 24 V DC contact sense; Channel isolation: Channel-isolated. These values do not authorize transferring specifications from a neighboring model.
During replacement, preserve the approved configuration and connection map. Perform a controlled visual, electrical and functional check, record the as-left result, and release the equipment only after the responsible site authority accepts the restored 16-channel 24 v dc contact-sense input module.
FBM207B Manufacturer Data Reference
Model-specific technical reference assembled from verified manufacturer-family records. PDF · 2 pages.FBM207B Installation & Verification Guide
Field guide covering identity capture, connection checks, controlled installation and acceptance evidence for FBM207B. PDF · 2 pages.
Application scope: Application suitability depends on the exact reference, hardware revision and installed configuration. Use site-approved drawings and manufacturer instructions for the final design decision.
Signal and communication acquisition
Use FBM207B only in the compatible I/A Series discrete input arrangement identified by the approved system documentation.Channel-map preservation
Preserve the installed identity, connector orientation and configuration while restoring the documented function.Diagnostic maintenance
Use recorded as-found values and approved tests to distinguish connection, companion-hardware and product faults.System commissioning
Keep the complete FBM207B reference and acceptance evidence with the asset record for future service.
Do not shorten FBM207B or transfer data from an adjacent reference.
Photograph connector orientation and label each cable or terminal before removal.
Retain the approved I/A Series discrete input database, jumpers, switches or channel assignment as applicable.
Follow the site energy-isolation and ESD procedure before disturbing hardware.
Check the documented base, cable, terminal, power and partner-module relationship.
Complete visual, electrical and functional checks before return to automatic service.
Alternative Names
Technical notes
Evidence boundary: Technical rows apply to FBM207B or its explicitly identified manufacturer family context.
Compatibility: Physical fit does not establish electrical, firmware or system compatibility.
Commissioning: Use approved Foxboro instructions and site procedures for final installation and release.
FAQ View All FAQ
-
Which channel assignment must be preserved when replacing FBM207B?Record every terminal, channel, signal type and control-database point before removal, then verify the restored mapping point by point.
-
How is the termination hardware for FBM207B selected?Use the exact module specification and installed terminal assembly or cable type; connector fit alone is not proof of compatibility.
-
What live-value checks are useful for FBM207B?Compare raw input or output indication, engineering value, channel status and an independent field reference under a controlled condition.
-
How should isolation claims for FBM207B be applied?Apply only the isolation arrangement documented for this exact module and channel group; do not extend backplane isolation to field channels.
-
Which configuration records should accompany FBM207B?Retain module address, channel configuration, scaling, alarm limits, communication parameters and the approved database revision.
-
How can a wiring fault be distinguished from a FBM207B hardware fault?Use channel status, terminal measurements, a known reference and controlled point substitution while preserving process protection.
-
What redundancy checks apply to FBM207B?Where supported, verify module roles, partner identity, communication health and an approved transfer test before returning to service.
-
What commissioning record should be retained for FBM207B?Keep channel-by-channel as-found/as-left results, communication status, configuration checksum or revision and acceptance signatures.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.