Match the complete marking
Include MU-KBFT02 80366198-200 and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered MU-KBFT02 80366198-200 with the installed equipment and applicable Honeywell documentation.
Technical specifications for MU-KBFT02 80366198-200
-
Manufacturer:Honeywell
-
Product Category:DCS Systems
-
Spare Part Number:MU-KBFT02 80366198-200
-
Weight:0.38 kg
-
Tariff Code:8537101190
-
Cable function:FTA I/O bridge
-
Design length:2.0 m
-
Termination arrangement:2 relay FTAs
-
Circuits per relay FTA:Up to 16
-
Combined output arrangement:32 points
-
Processor relationship:MU-PDOY22 digital output
-
Screw-terminal FTA relationship:MU-TDOY63 pair
-
Additional FTA trigger:Use of circuits 17–32
Information
- A paired relay-FTA arrangement uses MU-KBFT02 80366198-200 to retain the connection between the first and second termination assemblies.
Design length: 2.0 m for MU-KBFT02
Application: Two 16-circuit relay FTAs for one 32-point output IOP
One relay FTA supports up to 16 circuits. When circuits 17 through 32 are used, the arrangement requires two FTAs and the specified bridge between them. The 2.0 m MU-KBFT02 option supports this FTA-to-FTA connection; the selected terminal style and FTA identities must agree with the installed design.
For the screw-terminal arrangement, two MU-TDOY63 relay FTAs serve the MU-PDOY22 output IOP. Preserve the first/second FTA channel allocation, connector orientation and cable routing. Confirm the actual assembly marking and available routing length, then check the intended output channels after controlled reconnection.
-
Honeywell MU-KBFT02 80366198-200 technical reference
Original Honeywell excerpt - PDF, 3 pages, 13.8 KB. The cable design and FTA relationships apply to MU-KBFT02. The supplied 80366198-200 marking is retained for exact item matching; confirm its connector and assembly identity against the offered unit. -
Honeywell MU-KBFT02 80366198-200 installation planning guide
Prepared by Apter Power - PDF, 5 pages, 96 KB. Identity, configuration, connection and controlled acceptance planning.
Platform applications: The following applications describe TPS Process Manager I/O functions. Match the complete MU-KBFT02 80366198-200 identity to the installed system before selecting a replacement.
-
Relay output expansion
Connect the second 16-circuit relay FTA when the configured output arrangement uses circuits 17–32. -
Paired terminations
Maintain the intended bridge between the two relay FTAs rather than substituting a processor-interface cable. -
Cabinet routing
Use the specified 2.0 m design option where it matches the installed routing and connector arrangement. -
Output maintenance
Record the channel allocation and verify controlled output operation after reconnection.
Retain MU-KBFT02 80366198-200 and compare the connector details with the original cable.
Confirm the processor, both FTAs and the required terminal style.
Identify the first 16 circuits and the second 16 circuits before removal.
Isolate or manage affected outputs before disconnecting the bridge.
Preserve orientation and avoid strain or unsupported cable routing.
Verify the intended field response for both relay FTAs before release.
Alternative Names
Technical notes
Installation relationship: One relay FTA supports up to 16 circuits. When circuits 17 through 32 are used, the arrangement requires two FTAs and the specified bridge between them. The 2.0 m MU-KBFT02 option supports this FTA-to-FTA connection; the selected terminal style and FTA identities must agree with the installed design.
Configuration: The cable design and FTA relationships apply to MU-KBFT02. The supplied 80366198-200 marking is retained for exact item matching; confirm its connector and assembly identity against the offered unit.
Technical reference: Honeywell TPS Process Manager I/O Specification and Technical Data, IO03-500, November 1997; HPM Planning, HP02-500, Release 530 Revision 05.
FAQ View All FAQ
-
What is the function of MU-KBFT02 80366198-200?The MU-KBFT02 design bridges two relay Field Termination Assemblies in a configured Process Manager digital-output arrangement.
-
What design length applies to MU-KBFT02 80366198-200?The MU-KBFT02 cable option is 2.0 m. Match the complete cable marking and actual connector arrangement before installation.
-
How many circuits does one relay FTA support in the arrangement for MU-KBFT02 80366198-200?One relay FTA supports up to 16 circuits.
-
When is a second relay FTA needed with MU-KBFT02 80366198-200?A second FTA is required when circuits 17 through 32 of the 32-point output arrangement are used.
-
Which output IOP is associated with MU-KBFT02 80366198-200?The documented bridge arrangement uses the MU-PDOY22 32-point digital-output IOP.
-
Which screw-terminal relay FTAs are connected by MU-KBFT02 80366198-200?The documented screw-terminal arrangement combines two MU-TDOY63 relay FTAs.
-
Does MU-KBFT02 80366198-200 replace the IOP-to-FTA cable?No. The bridge is the FTA-to-FTA connection; the processor connection is a separate cable function.
-
What must be retained when reconnecting MU-KBFT02 80366198-200?Retain the first/second FTA channel allocation, connector orientation and approved routing, then verify the intended output circuits.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.