Technical specifications for 10101/2/1

  • Manufacturer:
    Honeywell
  • Product Category:
    DCS Systems
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Input channels:
    16
  • Nominal input:
    24 Vdc
  • Safety behavior:
    Fail-to-safe input stage
  • HIGH state:
    Above 15 Vdc
  • LOW state:
    Below 9 Vdc; below 2 mA
  • Typical input current:
    7 mA at 24 Vdc
  • Maximum input:
    36 Vdc
  • Typical delay:
    10 ms
  • Rack space:
    4 HP; 3U
  • Approvals:
    CE; TUV; UL; FM
  • Minimum software:
    3.00
  • 5 Vdc demand:
    8 mA
  • 24 Vdc internal demand:
    110 mA
  • 24 Vdc external demand:
    110 mA

Information

Overview Manuals Common Applications Product Precautions
Honeywell 10101/2/1 is a 16-channel fail-safe 24 Vdc digital input module for FSC safety applications.
  • Acquires sixteen 24 Vdc safety-related field states.
  • Drives a de-energized processor input when the input stage fails.
  • Self-tests logic-zero, logic-one and input crosstalk response.
  • Supports documented non-redundant and redundant FSC wiring.

Direct use of the external 24 Vdc output pins without an FTA requires the manufacturer-specified 500 mA fuse. Preserve internal and external supply assignments.

Important Notice: Verify the complete 10101/2/1 identity, installed system position, connections and controlled functional result before release.

Honeywell 10101/2/1 Manuals & Downloads
Honeywell 10101/2/1 Official Manufacturer Excerpt (PDF)Honeywell 10101/2/1 Installation & Commissioning Guide (PDF)
The first document records verified technical evidence. The second organizes controlled preparation, installation, commissioning and handover.
Emergency shutdown inputs
Acquires sixteen 24 Vdc safety-related field states.
Burner interlock contacts
Drives a de-energized processor input when the input stage fails.
Fire and gas trip inputs
Self-tests logic-zero, logic-one and input crosstalk response.
Fail-safe permissive monitoring
Supports documented non-redundant and redundant FSC wiring.
Honeywell 10101/2/1 installation checks must preserve the exact identity, system assignment and witnessed acceptance record.
1
Confirm the complete 10101/2/1 identity and 16-channel map.
2
Record internal and external 24 Vdc supply assignments.
3
Place the safety function in its approved maintenance state.
4
Use the documented 500 mA fuse when external output pins are used without an FTA.
5
Preserve input polarity, return and FTA terminal identity.
6
Check every channel against the documented HIGH and LOW thresholds.
7
Review module self-test and system diagnostics after energization.
8
Retain the witnessed safety-function acceptance record.

Technical notes

Direct use of the external 24 Vdc output pins without an FTA requires the manufacturer-specified 500 mA fuse. Preserve internal and external supply assignments.

FAQ View All FAQ

  • How many channels does Honeywell 10101/2/1 provide?
    It provides sixteen 24 Vdc digital input channels.
  • Why is Honeywell 10101/2/1 described as fail-safe?
    A component failure in the input stage produces a de-energized processor signal, the safe state in a normally energized system.
  • Which self-tests cover Honeywell 10101/2/1?
    The system tests logic-zero reception, logic-one reception and crosstalk between inputs.
  • What input levels define HIGH and LOW for Honeywell 10101/2/1?
    HIGH is above 15 Vdc; LOW is below 9 Vdc with current below 2 mA.
  • What maximum input is documented for Honeywell 10101/2/1?
    The technical data lists 36 Vdc maximum.
  • When does Honeywell 10101/2/1 require a 500 mA fuse?
    Use it when the external 24 Vdc output pins are wired without an FTA.
  • Which supplies must be checked on Honeywell 10101/2/1?
    Check the 5 Vdc logic supply plus the internal and external 24 Vdc circuits.
  • What completes commissioning of Honeywell 10101/2/1?
    Prove all sixteen inputs, review self-test diagnostics and retain the witnessed safety-function result.
Related reading

Related cases and sourcing guidance

View all case studies
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.