Match the complete marking
Include 8626-FT-IS and its visible revision or assembly identity in your enquiry. Keep the complete reference on the quotation. -
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 8626-FT-IS with the installed equipment and applicable Emerson documents.
Technical specifications for 8626-FT-IS
-
Manufacturer:Emerson
-
Product Category:DCS Systems
-
Spare Part Number:8626-FT-IS
-
Weight:0.15 kg
-
Product role:Intrinsically safe RTD field terminal
-
Matched I/O module:8206-TI-IS, eight-channel RTD input
-
RTD wiring:Two-, three- or four-wire diagrams
-
Field-terminal key:C / 3 with 8206-TI-IS
-
Connector arrangement:Two multipin module connectors
-
Field termination:Screw-clamp terminal rows
-
Terminal voltage limit:30 V maximum, certificate condition
-
Terminal input-power limit:0.9 W maximum, certificate condition
-
Field wiring location:Zone 0 IIC or Class I Div 1 when approved as an assembly
-
Terminal body:Blue moulding for IS field wiring
-
Tagging strip:Present on screw-clamp terminal
-
Material:Modified poly-phenylene oxide
Information
- Emerson 8626-FT-IS. This field terminal joins RTD sensor wiring to an intrinsically safe PAC8000 temperature-input channel; measurement conversion belongs to the paired 8206-TI-IS module.
Matched I/O module: 8206-TI-IS, eight-channel RTD input
RTD wiring: Two-, three- or four-wire diagrams
Field-terminal key: C / 3 with 8206-TI-IS
The intrinsically safe assembly uses mechanical key position C/3 for the 8206-TI-IS pairing. The terminal has module-side multipin connectors, screw-clamp field connections and an identification strip. Its blue moulding identifies IS field wiring; a field terminal alone does not establish the whole loop certificate or replace the module, carrier and power arrangement.
IECEx BAS 12.0023U limits terminal input/output voltage to 30 V and 8626-FT-IS input power to 0.9 W. The certificate also calls for consideration of segregation at 30 V when assessing combined assembly output parameters. Carry the applicable control drawing, sensor entity parameters and area classification through the installation review.
-
Emerson 8626-FT-IS technical reference
Prepared by Apter Power - PDF, 5 pages. Exact-model technical data and source boundaries. -
Emerson 8626-FT-IS installation guide
Prepared by Apter Power - PDF, 5 pages. Identity, installed-system checks, commissioning and handover.
Compatibility boundary: Use the RTD terminal wiring diagram and the approved intrinsic-safety assembly for the selected two-, three- or four-wire sensor.
-
Two-wire RTD
Use the terminal sheet’s two-wire connection diagram when the installed sensor and input configuration require a two-lead RTD. -
Three-wire RTD
Route the compensation conductor according to the dedicated three-wire diagram and verify the corresponding channel configuration. -
Four-wire RTD
Terminate separate excitation and sense conductors using the four-wire diagram for the selected RTD channel. -
Module replacement
Retain the 8206-TI-IS pairing and C/3 key relationship when exchanging a field terminal in a PAC8000 IS assembly.
Follow the site hazardous-area and isolation procedure before disturbing field connections.
Confirm 8206-TI-IS and the C/3 mechanical key before fitting 8626-FT-IS.
Identify every two-, three- or four-wire conductor against the correct terminal diagram.
Assess the 30 V and 0.9 W certificate limits in the complete approved loop.
Check screw-clamp security, conductor identification and separation of IS wiring.
After restoration, compare each temperature channel with a known process or test reference.
Alternative Names
Technical notes
Module relationship: 8626-FT-IS is the RTD field terminal for 8206-TI-IS; the module performs temperature-input conversion.
Protection: Apply the 30 V terminal and 0.9 W input-power limits within the approved intrinsically safe assembly.
Technical reference: Emerson PAC8000 Remote I/O, 00813-0100-0108; MTL Field terminals; IECEx BAS 12.0023U.
FAQ View All FAQ
-
Which input module is paired with Emerson 8626-FT-IS?The listed pairing is the 8206-TI-IS intrinsically safe eight-channel RTD input module.
-
Which sensor wiring forms are documented for Emerson 8626-FT-IS?The field-terminal sheet shows distinct two-, three- and four-wire RTD connection diagrams.
-
What mechanical key position applies to Emerson 8626-FT-IS?The approved 8206-TI-IS pairing uses field-terminal key position C/3.
-
What is the terminal voltage limit for Emerson 8626-FT-IS?IECEx BAS 12.0023U limits the terminal input/output voltage to 30 V; assess the complete loop.
-
What input-power condition applies to Emerson 8626-FT-IS?The certificate sets a 0.9 W maximum input power for this RTD field terminal.
-
Does Emerson 8626-FT-IS itself convert RTD signals?It provides the field-wiring interface; the paired 8206-TI-IS module is the temperature-input module.
-
How should Emerson 8626-FT-IS RTD conductors be checked?Compare the actual sensor lead count and channel designation with the applicable terminal diagram before energizing.
-
What must be checked before replacing Emerson 8626-FT-IS?Match the full terminal reference, 8206-TI-IS module, mechanical key, approved IS parameters and installed RTD wiring.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.