Match the complete marking
Include IS220PTURH1A and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered IS220PTURH1A with the installed equipment and applicable General Electric documentation.
Technical specifications for IS220PTURH1A
-
Manufacturer:General Electric
-
Product Category:Gas Turbine Control
-
Spare Part Number:IS220PTURH1A
-
Weight:0.4 kg
-
Tariff Code:8537101190
-
Control platform:Mark VIe
-
Function:Turbine-specific primary trip
-
Accessory terminal board:IS200TRPAH1A
-
Power supply:28 V DC
-
Supply current:0.41 A DC
-
Speed input range:−15 to +15 V DC
-
Voltage input range:16–140 V DC
-
Emergency-stop input:18–140 V DC
-
E-stop power output:28 V DC open circuit; 17 mA DC short circuit
-
Contact output:28 V DC, 7 A DC
Information
- General Electric IS220PTURH1A forms part of a turbine primary-trip arrangement. Its speed, voltage and emergency-stop interfaces must match the specified terminal board and installed protection design.
Terminal-board pairing: IS200TRPAH1A
Specified supply: 28 V DC, 0.41 A DC for the paired arrangement
The paired arrangement is rated for a 28 V DC power supply at 0.41 A DC. Its speed input is specified from −15 to +15 V DC, voltage input from 16 to 140 V DC and emergency-stop input from 18 to 140 V DC. These interface ranges serve different circuits and must not be interchanged when checking the installed terminations.
The emergency-stop power output is specified at 28 V DC open circuit and 17 mA DC short circuit; the contact output is rated at 28 V DC, 7 A DC. The open-circuit and short-circuit values describe boundary conditions, not a single normal operating point. Verify field loads, trip wiring and the approved functional test before returning the turbine protection arrangement to service.
-
General Electric IS220PTURH1A technical reference
Original General Electric excerpt - PDF, 5 pages, 132.2 KB. The electrical values apply to IS220PTURH1A with the IS200TRPAH1A accessory terminal board. They are connection ratings for that arrangement, not proof of supplied terminal-board inclusion or an independent system safety rating. -
General Electric IS220PTURH1A installation planning guide
Prepared by Apter Power - PDF, 5 pages, 96.1 KB. Identity, configuration, connection and controlled acceptance planning.
Platform applications: The following applications describe GE Mark VIe functions. Match the complete IS220PTURH1A identity to the installed system before selecting a replacement.
-
Turbine primary trip
Integrate the PTUR module in the approved Mark VIe turbine trip arrangement. -
Speed-signal integration
Match the speed-signal circuit to the specified input range and terminal assignments. -
Emergency-stop circuits
Review input and power-output boundaries against the complete emergency-stop wiring. -
Protection maintenance
Retain the PTUR and TRPA pairing and validate trip behavior under the authorized test procedure.
Use the specified IS200TRPAH1A terminal-board arrangement.
Follow the site procedure before disturbing powered protection or emergency-stop wiring.
Do not interchange speed, voltage and emergency-stop input circuits.
Keep open-circuit voltage separate from short-circuit current when reviewing the E-stop output.
Review the 28 V DC, 7 A DC contact-output rating with the connected load and circuit protection.
Validate the complete turbine trip arrangement before release; a module replacement is not a system-level acceptance test.
Alternative Names
Technical notes
Installation relationship: The paired arrangement is rated for a 28 V DC power supply at 0.41 A DC. Its speed input is specified from −15 to +15 V DC, voltage input from 16 to 140 V DC and emergency-stop input from 18 to 140 V DC. These interface ranges serve different circuits and must not be interchanged when checking the installed terminations.
Configuration: The electrical values apply to IS220PTURH1A with the IS200TRPAH1A accessory terminal board. They are connection ratings for that arrangement, not proof of supplied terminal-board inclusion or an independent system safety rating.
Technical reference: GE Mark VIe Programmable Controller System, DEMKO 12 ATEX 1114875X Rev. 18.
FAQ View All FAQ
-
What is the control function of IS220PTURH1A?PTUR is the Mark VIe turbine-specific primary-trip function.
-
Which terminal board is paired with IS220PTURH1A?The specified accessory terminal board is IS200TRPAH1A. Its inclusion in the offered supply is a separate matter.
-
What supply rating applies to IS220PTURH1A?The IS220PTURH1A and IS200TRPAH1A arrangement is specified for 28 V DC at 0.41 A DC.
-
What speed-input range is specified for IS220PTURH1A?The paired arrangement specifies a speed-input range of −15 to +15 V DC.
-
What voltage-input range is specified for IS220PTURH1A?The voltage input is specified from 16 to 140 V DC for the identified module and terminal-board pairing.
-
What emergency-stop input range applies to IS220PTURH1A?The emergency-stop input is specified from 18 to 140 V DC.
-
How should the emergency-stop power-output values for IS220PTURH1A be interpreted?28 V DC is the open-circuit value and 17 mA DC is the short-circuit value. They are distinct boundary conditions, not a combined normal load rating.
-
What contact-output rating is given for IS220PTURH1A?The paired arrangement specifies 28 V DC, 7 A DC. Check the field load and complete trip-circuit design before commissioning.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.