Match the complete marking
Include 330709-000-050-10-12-05 and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and probe-connection photos. Have your maintenance team compare the offered 330709-000-050-10-12-05 with the installed equipment and applicable Bently Nevada documentation.
Technical specifications for 330709-000-050-10-12-05
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330709-000-050-10-12-05
-
Weight:0.1 kg
-
Tariff Code:8537101190
-
Probe family:3300 XL 11 mm
-
Mounting thread:M16 x 1.5
-
Unthreaded length:0 mm
-
Overall case length:50 mm
-
Total probe length:1.0 m
-
Cable construction:FluidLoc; without armor
-
Connector:Miniature coaxial ClickLoc
-
Connector protector:Not included by option 12
-
1.0 m probe DC resistance:5.9 +/- 0.5 ohms
-
Matched-system linear span:4.0 mm (160 mils)
-
Matched-system scale factor:3.94 V/mm (100 mV/mil), +/-10%
-
Recommended operating gap:2.5 mm (100 mils)
-
Matched-system response:0-8 kHz, +0/-3 dB typical
-
Maximum M16 thread engagement:24 mm
-
Probe operating temperature:-52 to +177 deg C; pressure-seal caveat below -34 deg C
Information
- The fully threaded metric case of Bently Nevada 330709-000-050-10-12-05 places an 11 mm sensing tip at the shaft or thrust target, while its FluidLoc lead helps restrict oil migration along the cable.
Lead: 1.0 m FluidLoc cable with miniature ClickLoc connector
Measurement system: 3300 XL 11 mm; 4.0 mm nominal linear span
The probe works with a compatible 3300 XL 11 mm extension cable and Proximitor Sensor. Under the specified AISI 4140 target, -24 V DC supply, 10 kilohm load and 2.5 mm gap conditions, the complete system provides a nominal 3.94 V/mm scale factor and 4.0 mm linear span. Typical frequency response is 0-8 kHz at +0/-3 dB, subject to the field-wiring conditions.
For a disconnected 1.0 m probe, center-to-outer conductor resistance is 5.9 +/- 0.5 ohms. This is a continuity reference, not a substitute for checking system calibration. The electrical operating range is -52 to +177 deg C, while exposure below -34 deg C can cause premature pressure-seal failure; electrical and containment limits must be assessed separately.
330709-000-050-10-12-05 Official Technical Reference Excerpt
3300 XL 11 mm Proximity Transducer System, 146256 Rev. T: preserved manufacturer specifications applicable to this product configuration. PDF · 9 pages.330709-000-050-10-12-05 Installation & Verification Guide
Apter Power field guide for metric mounting, FluidLoc cable routing, electrical-length matching and gap verification. PDF · 5 pages.
Application scope: Use the matched system for non-contact shaft motion or position measurements. Target geometry, temperature and surrounding metal affect the measurement boundary.
Radial shaft vibration
Measure shaft-relative motion at a compatible bearing location with a calibrated 11 mm channel.Thrust target position
Use the wider 4 mm system span where an appropriate axial target and installation geometry are available.Metric machine mounting
Fit the M16 x 1.5 case to an approved metric mounting point with controlled engagement.Oil-exposed cable paths
Use FluidLoc construction where limiting liquid migration inside the lead is part of the installation design.
Confirm M16 x 1.5 engagement and avoid binding beyond the 24 mm limit.
Route and support the cable against abrasion, pinching and connector tension.
Keep the probe, extension and Proximitor Sensor at the same specified total length.
Establish the gap using the approved target and measured output, not thread turns alone.
Insulate and protect ClickLoc joints according to the installation environment.
Check gap, response, monitor indication and alarm paths after installation.
Alternative Names
Technical notes
Cable relationship: The 1.0 m FluidLoc lead contributes to the total calibrated system length; do not shorten or splice it.
Calibration boundary: System values require the correct 11 mm sensor chain and specified target conditions.
FAQ View All FAQ
-
How much of the case on 330709-000-050-10-12-05 is unthreaded?The 000 option specifies zero unthreaded length. The 050 option specifies a 50 mm overall case; installation clearance must also allow the sensing tip to face the target correctly.
-
What does FluidLoc cable change on 330709-000-050-10-12-05?FluidLoc construction helps prevent oil and other liquids from migrating through the cable interior. It does not replace the machine seal, connector protection or process-containment design.
-
Does the 12 connection option on 330709-000-050-10-12-05 include a connector protector?No. Option 12 uses a miniature coaxial ClickLoc connector and FluidLoc cable. Option 11 is the FluidLoc version with a connector protector.
-
Which extension lengths can form a standard system with 330709-000-050-10-12-05?Its 1.0 m probe lead can form a 5 m system with a 4 m extension or a 9 m system with an 8 m extension. The 3300 XL 11 mm Proximitor Sensor must be calibrated for the same total electrical length.
-
Why is M16 thread engagement limited on 330709-000-050-10-12-05?The specified maximum engagement for the M16 x 1.5 case is 24 mm. Excessive engagement can cause binding; verify the mating-thread fit and mounting depth before tightening.
-
What resistance is expected across the lead of 330709-000-050-10-12-05?For a 1.0 m 3300 XL 11 mm probe, the center-to-outer conductor DC resistance is 5.9 +/- 0.5 ohms. Check the disconnected probe with suitable equipment; a resistance check alone does not prove calibration.
-
Can 330709-000-050-10-12-05 deliver the 4 mm span on any target material?No. The stated system accuracy and interchangeability apply to the specified AISI 4140 steel target and calibration conditions. Other target materials require their own calibration assessment.
-
How does low temperature affect the pressure seal of 330709-000-050-10-12-05?The probe operating range is -52 to +177 deg C, but exposure below -34 deg C may cause premature pressure-seal failure. Evaluate containment separately from electrical operation.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.