Technical specifications for 330103-00-08-10-02-05
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330103-00-08-10-02-05
-
Estimated shipping dimensions:19x19x2cm
-
Weight:0.2 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Probe construction:Without armor
-
Mounting thread:M10 x 1
-
Unthreaded length:0 mm
-
Case length:80 mm
-
Total lead length:1.0 m
-
Connector option:Miniature coaxial ClickLoc
-
Approval option:Multiple approvals
-
Probe-tip diameter:8.0 mm
-
System linear range:2.0 mm (80 mils)
-
Recommended gap:1.27 mm (50 mils)
-
Incremental scale factor:7.87 V/mm (200 mV/mil)
-
Frequency response:0 to 10 kHz, +0/-3 dB
-
Probe cable impedance:75 ohm
-
Probe temperature:-52 to +177 deg C
-
Proximitor supply:-17.5 to -26 VDC
-
Field wiring:0.2 to 1.5 mm2
-
Maximum field wiring:305 m
Information
- Detects shaft-to-bearing relative movement without mechanical contact
- Forms the field sensing element of the matched eddy-current loop
- Carries the probe signal through the specified service connection
- Supports static-position and vibration measurements on rotating machinery
The probe is fitted to the engineered M10 x 1 machine position and connected to the selected extension cable and Proximitor Sensor. Commissioning includes order-code, clearance, cable-route, total-system-length, static-gap and controlled response checks.
Important Notice: Confirm 330103-00-08-10-02-05, M10 x 1 host thread, 0 mm unthreaded length, 80 mm case execution, without armor, Miniature coaxial ClickLoc, extension cable, Proximitor Sensor, total system length, target material, wiring, shielding, grounding, monitor configuration, static gap and controlled response-test results before commissioning.
Apter Power 330103-00-08-10-02-05 Manuals and Guides
- Apter Power 330103-00-08-10-02-05 Probe Configuration Technical Reference PDF
- Apter Power 330103-00-08-10-02-05 Gap, Cable and Response Verification Workbook PDF
The first document is the model-specific technical and system reference. The second is a distinct field workbook for installation, wiring, commissioning and acceptance records.
Technical notes
FAQ View All FAQ
-
Which complete article marking distinguishes 330103-00-08-10-02-05 from nearby variants?Confirm 330103-00-08-10-02-05, M10 x 1 host thread, 0 mm unthreaded length, 80 mm case execution, without armor, Miniature coaxial ClickLoc, extension cable, Proximitor Sensor, total system length, target material, wiring, shielding, grounding, monitor configuration, static gap and controlled response-test results before commissioning.
-
What system function is assigned specifically to 330103-00-08-10-02-05?Detects shaft-to-bearing relative movement without mechanical contact. It senses shaft-to-bearing relative displacement in a matched proximity transducer system.
-
How should the host position and mating hardware for 330103-00-08-10-02-05 be verified?The probe is fitted to the engineered M10 x 1 machine position and connected to the selected extension cable and Proximitor Sensor. Commissioning includes order-code, clearance, cable-route, total-system-length, static-gap and controlled response checks.
-
Which power, signal or field circuits must be controlled before servicing 330103-00-08-10-02-05?Place the monitored machine and associated protection channel in the approved maintenance state. Protect the 8.0 mm probe tip and keep the mounting thread free from burrs and contamination.
-
What wiring or connector checks are required for 330103-00-08-10-02-05?Confirm the installed extension cable and Proximitor Sensor match the approved total system length.
-
How is the approved software or hardware setup for 330103-00-08-10-02-05 preserved?Set the static gap within the documented linear region while maintaining target clearance.
-
Which alarms or status indications should be reviewed after replacing 330103-00-08-10-02-05?Confirm the complete 330103-00-08-10-02-05 marking, M10 x 1 thread and 80 mm case execution. Keep the Miniature coaxial ClickLoc connection clean, dry and finger-tight.
-
How is a controlled functional release completed for 330103-00-08-10-02-05?Prove polarity, static position, dynamic response and alarm action before returning the channel to service.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
330103-00-08-10-02-05Product Details -
330103-00-02-05-01-00Product Details -
330910-00-11-10-02-05Product Details -
330104-00-08-10-01-05Product Details -
330103-01-06-05-02-00Product Details -
330103-01-07-05-02-00Product Details -
330195-02-12-05-CNProduct Details -
330505-01-02-02Product Details -
330130-085-01-05Product Details -
330730-040-00-05Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.