Two probes should observe the same thrust collar or shaft. An out-of-range gap signal can resemble actual axial movement, so dual-channel voting and correct probe adjustment are central to a dependable thrust-protection arrangement.
Important Notice: Verify the actual relay contact circuit and voting configuration before restoring protection. Hermetically sealed relays do not eliminate the need for two correctly adjusted proximity channels.
The technical excerpt covers monitor characteristics and configuration choices. The installation guide addresses two-probe alignment, field connections, direction checks and alarm acceptance.